SCC 4-Pump 38-Station Controllers Part Number: 882.00253.0 0 Bulletin Number: CV3-640 Effective: 11/27/05 Write Down Your Serial Numbers Here For Future Reference: _________________________ __________.
Please note that our address and phone i nformation has changed. Please reference this page for updated contact information. These manuals are obsolet e and are provided only for their technical inf ormation, data and capacities.
4 –Pump 38-Station Controllers Chapter 1: Safety ii Shipping Information Unpacking and Inspection You should inspect your equipm ent for possible shipping damage. Thoroughl y check the equipment for any damage that m ight have occu rred in transit, such as broken or loose wiring and components, loose hardware and mounting screws, etc.
4 –Pump 38-Station Controllers Chapter 1: Safety iii Table of Contents CHAPTER 1: SAFETY ................................................................ V 1-1 How to Use This Manual ..................................................................
4 –Pump 38-Station Controllers Chapter 1: Safety iv Reviewing Station Status .................................................................................... 23 Reviewing Pump Status ..............................................................
4 –Pump 38-Station Controllers Chapter 1: Safety v Chapter 1: Safety 1-1 How to Use This Manual Use this manual as a guide and reference for installing, operating, and maintaining your equipment. The purpose is to assist you in a pplying efficient, proven techniques that enhance equipment productivity.
4 –Pump 38-Station Controllers Chapter 1: Safety vi 1-2 Warnings and Precautions Our equipment is designed to provide safe and reliable operation when installed and operated within design specifications, following national a nd local safety codes.
4 –Pump 38-Station Controllers Chapter 1: Safety vii 1-3 Responsibility These machines are constructed for maximum operator safety when used under standard operating conditions and when recommended inst ructions are followed in the maintenance and operation of the machine.
4 –Pump 38-Station Controllers Chapter 1: Safety viii Operator Responsibility The operator’s responsibility does not end with e fficient production. The operator usually has the most daily contact with the equipment and intimately knows its capabilities and limitations.
4 –Pump 38-Station Controllers Chapter 2: Functional Description 9 of 44 Chapter 2: Functional Description 2-1 Models Covered in This Manual This manual provides operation, installation, and m aintenance instructions for 4-Pump, 38- Station Conveying Controllers.
4 –Pump 38-Station Controllers Chapte r 2: Functional Description 10 of 44 2-3 Standard Features Mechanical Features Time-fill Capability. The length of time allowed for material to drain from the station to its receiver. During this time, the controller does not attempt to deliver any m ore material to the station.
4 –Pump 38-Station Controllers Chapte r 2: Functional Description 11 of 44 2-4 Optional Features Options marked with “*” indicate options that can be factory installed or retrofitted in the field. 230/1/50 Operation. Required to operate with a 230/1/50 suppl y voltage.
4 –Pump 38-Station Controllers Chapte r 2: Functional Description 12 of 44 Safety Device Lock-Outs Some safety devices disconnect electrical energy from a circuit. T he safety devices that are used in this Controller are primarily con cerned with electrical power disconnection.
4 –Pump 38-Station Controllers Ch apter 3: Installation 13 of 44 Chapter 3: Inst allation 3-1 Uncrating 4-Pump, 38-Station Controllers are shipped mounted on a skid, enclosed in a pla stic wrapper, and contained in a cardboard box. 1. Pry the crating away from the skid.
4 –Pump 38-Station Controllers Ch apter 3: Installation 14 of 44 Connecting the Control Panel to Vacuum Hoppers Note: Wire size dep ends on contr ol voltage, distance, number of vacuum hoppers, and the number of wires in each raceway. Consult a qualified electrician.
4 –Pump 38-Station Controllers Ch apter 3: Installation 15 of 44 Setting the Number of Stations and the Number of Pumps Figure 1: Default “Station Status” Screen Before Setup 1. At the “Station Status” screen (Figure 1) or at the “Pump Status” screen, touch the SYSTEM SETUP button.
4 –Pump 38-Station Controllers Ch apter 3: Installation 16 of 44 Setting Up Alarm Silences When an alarm occurs, a horn sounds and a st robe light flashes at each installed central alarm. An alarm banner appears in the cen ter of the screen. An alarm message a nd Silence button are on the banner.
4 –Pump 38-Station Controllers Ch apter 3: Installation 17 of 44 Setting Up Pump Staging To avoid an excessive power demand at your fac ility when the conveying system starts up, you can stagger the times at which pumps start.
4 –Pump 38-Station Controllers Ch apter 3: Installation 18 of 44 Figure 5: “Station Operator” Screen Before Setup 3. On the “Station Operator” screen (Figure 5), touch the STATION SETUP button. The “Station Setup” screen opens. Figure 6: “Station Setup” Screen 4.
4 –Pump 38-Station Controllers Ch apter 3: Installation 19 of 44 5. As appropriate, setup the rest of the stati ons using either of the following m ethods: • Use the PREVIOUS or NEXT buttons to navigate to other stations. Touch PREVIOUS to go to the previous “Station Setup” screen, or touch NEXT to go to the next “Station Setup” screen.
4 –Pump 38-Station Controllers Ch apter 3: Installation 20 of 44 Figure 8: Pump Setup Screen Before Setup 3. Adjust settings as required. Touching any box that appears in red (for “disabled”) toggles it to green (for “enabled”), and vice versa.
4 –Pump 38-Station Controllers Ch apter 3: Installation 21 of 44 Operator Password If you define a password for operators, then a password will be required to carry out any function (other than reviewing station and pum p status, silencing alarms, reviewing the alarm log, and looking at help screens).
4 –Pump 38-Station Controllers Ch apter 3: Installation 22 of 44 To change the duration of the password, complete the following steps: 1. On the “System Setup” screen, touch the Operator Password Duration button or the Setup Password Duration button, depending on wh ich password duration you want to change.
4 –Pump 38-Station Controllers Ch apter 4: Operation 23 of 44 Chapter 4: Operation 4-1 Overview Your 4-pump, 38-station controller electrically contro ls valves and solenoids to convey material from a central location to individual stations as needed.
4 –Pump 38-Station Controllers Ch apter 4: Operation 24 of 44 The following table explains the status re presented by each color at the “Station Status” screen. Color Label Description Gray outline Offline Station is not enabled. The controller ignore s any demands or alarms.
4 –Pump 38-Station Controllers Ch apter 4: Operation 25 of 44 Reviewing Pump Status The “Pump Status” screen is the counterpart of the “Station Status” screen. To reach the “Pump Status” screen from any other screen, touch PUMP STATUS on any screen.
4 –Pump 38-Station Controllers Ch apter 4: Operation 26 of 44 Logging On and Logging Off Your controller may be set up to require a p assword for any operation (other than reviewing station and pump status, silencing alarms, re viewing the alarm log, and looking a t help screens).
4 –Pump 38-Station Controllers Ch apter 4: Operation 27 of 44 Enabling and Disabling Stations and Pumps When a station or pump is disabled, the controller makes no attempt to use it and ignores any alarms that occur for it. Disabling a station or pump at the controller’s screen is similar to bypassing a station with its bypass switch.
4 –Pump 38-Station Controllers Ch apter 4: Operation 28 of 44 Reviewing and Adjusting Basic Station Settings The 4-pump, 38-station controller has a “Station Operator” screen for each station, as shown below. This screen enables you to review a nd adjust all basic settings for the station.
4 –Pump 38-Station Controllers Ch apter 4: Operation 29 of 44 Adjusting Convey Time and Dump Delay Convey time is the length of time the station’s vacuum valve remains open to allow material to be drawn in.
4 –Pump 38-Station Controllers Ch apter 4: Operation 30 of 44 Activating and Stopping Priority Convey for a Station Note: Before activating priority convey, make sure that all other stations using the same pump have adequate material in reserve to c ontinue operation.
4 –Pump 38-Station Controllers Ch apter 4: Operation 31 of 44 4-3 Adjusting Advanced Settings This section describes the procedures carried out during operation that are normally reserved for setup personnel. These procedures require use of the setup password (if your facility has defined one).
4 –Pump 38-Station Controllers Ch apter 4: Operation 32 of 44 Transferring Stations to a Standby Pump If a pump fails, you can transfer all of the controller’s station assignments for that pump to a standby pump.
4 –Pump 38-Station Controllers Ch apter 4: Operation 33 of 44 Figure 15: Transfer To Standby Pump Button Note: When you enter the second pump number, th e controller checks to make sure that both pumps are offline and that the standby pump has no stations assigned to it.
4 –Pump 38-Station Controllers Ch apter 4: Operation 34 of 44 Filter cleaning Our pumps have two options available for filter cleaning; these are vacuum pulse or compressed air filter cleaning.
4 –Pump 38-Station Controllers Chapter 5: Maintenance 35 of 44 Chapter 5: Maintenance No Periodic maintenance is required on this unit..
4 –Pump 38-Station Controllers Chapter 6: Configurable Settings 36 of 44 Chapter 6: Configurable Settings This section describes the proper setup of the 4 pump, 38-station control s ystem parameters. These parameters are operator changeable; however, these items sh ould require setup only during the initial installation.
4 –Pump 38-Station Controllers Chapter 6: Configurable Settings 37 of 44 Name Description Options Default Special convey When this option is enabled, the station’s vacuum valve remains open for the convey time, even if the station is not demanding material and is indicating that it is full.
4 –Pump 38-Station Controllers Chapter 6: Configurable Settings 38 of 44 6-2 Options for Pump Setup Several of the items in this screen are not setup options but are instead intended for use during operation. These items (hour meter and transferring stations to a standby pump) are described in Chapter 4, which cover operation procedures.
4 –Pump 38-Station Controllers Ch apter 7: Troubleshooting 39 of 44 Chapter 7: T roubleshooting 7-1 General Troubleshooting Problem Possible Cause Solution The control panel is not turned on. Turn on the control panel. Fuse/circuit breaker in the power drop is blown/tripped.
4 –Pump 38-Station Controllers Ch apter 7: Troubleshooting 40 of 44 7-2 Alarms The format for all station alarms is “Station n [alarm text],” for example, “Station 12 receiver low level.” The format for all pump alarms is “Pump n [alarm text].
4 –Pump 38-Station Controllers Chapter 8: Appendix 41 of 44 Chapter 8: Appendix 8-1 Warranty The Manufacturer warrants all equipment manufactured by it to be free from defects in workmanship and material when used un der recommended conditions.
4 –Pump 38-Station Controllers Chapter 8: Appendix 42 of 44 8-3 Drawings and Diagrams Figure 17: 4 pump 38 station Controller with 6" Display Also, review electrical drawings supplied in the packet with this manual.
4 –Pump 38-Station Controllers Chapter 8: Appendix 43 of 44 8-5 Returned Material Policy Credit Returns Prior to the return of any material, authoriz ation must be given by the manufacturer. A RMS number will be assigned for the equipment to be returned.
4 –Pump 38-Station Controllers Chapter 8: Appendix 44 of 44 8-7 Controller Identification (Serial Number) Tag (Located on the side of the controller box) 8-8 Technical Assistance (Contact Informatio.
デバイスSterling Plumbing 882.00253.00の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Sterling Plumbing 882.00253.00をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSterling Plumbing 882.00253.00の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Sterling Plumbing 882.00253.00の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Sterling Plumbing 882.00253.00で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Sterling Plumbing 882.00253.00を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSterling Plumbing 882.00253.00の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Sterling Plumbing 882.00253.00に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSterling Plumbing 882.00253.00デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。