E6581429 Operation s Introduction Contents Read first Connection of e q ui p ment Searching and setting parameters Monitoring the o p eration status List of function ke y functions Measures to satisfy.
.
E6581429 1 I I. Safety precautio ns Thoro ughly fam iliariz e yours elf wit h the sym bols and i ndicat ions show n in “I . Safety Pr ecauti ons,” o f the ins tructio n manual E6581386 and below, and then continue to read manua ls. Make sure that you observe all cautions given.
E6581429 2 II II. Introduction Thank you for you r purchase of the totally enclosed box t ype for IP54 Inverter, “TOSVERT VF-PS1”. Note) Drives with UL Type 12 conformity are optional.
E6581429 i - Contents - I. Safety precautions ·············································································.
.
E6581429 A-1 1 1. Read first 1.1 Check the product T ype indication label Series nam e Power supply Motor capac ity Inverter T y pe Applicable moto r Invert rated o utput cap acity Power supply Related input c urrent Related out put current Serial No.
E6581429 A-2 1 1.3 Structu r e o f th e m ain b o d y 1.3.1 Names and functions 1) Outside v iew [ F r o n t v i e w ] [ S i d e v i e w ] [ Bottom view ] Note: Operation panel is not att ached to the in v erter main unit at the delivery . Attach the panel at the position of the uppe r figure before installing the inverter.
E6581429 A-3 1 Q Operation panel Totally enclosed bo x type VF-PS1 series have a specia l operation panel. (2) (3) (4) (5) (1) (9) (8) (6) (7) (10) (1): LCD panel For explanation of wi ndows displayed, see the next page.
E6581429 A-4 1 Q LCD panel This section explains the features of windo ws available, usin g the top windo w of St atus Monitor Mode as an exampl e. (1): Disp lays the mode cur rent ly selected. (2): Di splay s the oper ating stat us of th e invert er wit h a graphi cal sym bol.
E6581429 A-5 1 2) Main circu it terminal VFPS1-4007PLE~4022PLE Grounding capac itor switching switch M4 screw Grounding term inal ( M5 screw ) PO PA/+ PB PC/ - U/ T1 V /T2 W/ T3 R/ L1 S/ L2 T /L3 VFPS.
E6581429 A-6 1 VFPS1-4037PDE, 405 5PDE M4 screw Grounding term inal (M5 screw ) PO PA/+ PB PC/- W/T 3 T/L3 U/T1 R/L1 S/L2 V/T 2 M4 slotted head screw VFPS1-4075PLE, 41 10PLE Grounding capac itor switc.
E6581429 A-7 1 VFPS1-4150PLE Grounding capac itor switching switch M5 screw Grounding term inal(M5 screw ) W/T3 V/T2 U/T1 PC/- PB PA/+ PO T/L3 S/L2 R/L1 VFPS1-4150PDE M5 screw Grounding term inal (M5 .
E6581429 A-8 1 VFPS1-4185PDE, 422 0PDE M6 sc rew Grounding term inal(M5 screw ) W/T3 V/T2 U/T1 PC/- PB PA/+ PO T/L3 S/L2 R/L1 Grounding term inal(M6 screw ) M5 slotted head screw VFPS1-4300PLE Groundi.
E6581429 A-9 1 VFPS1-4370PLE, 4450PLE Grounding cap acitor sw itc hing sw itc h M10 hexagon socket set screw Grounding term i na l (M10 hexagon socket set sc rew) PA/+ PO Grounding term i nal(M 5 scre.
E6581429 A-10 1 VFPS1-4550PDE~4900PDE M20 hexagon socket hea d cap screw M16 hexagon socket set screw grounding term inal(M16 hex agon socket set screw ) PA/+ PO grounding term i na l(M8 screw) PC/- PB PE PE T/L3 S/L2 V/T 2 U/T1 R/L1 W/T3 Following powe r t erminals are cage type ones.
E6581429 A-1 1 1 1.3.2 Detaching the cov er Danger Mandatory • Never remove the f ront cover while power is on or with in 15 minutes after power off. Never turn on the power while the front cover is open. Circuit boards are e xposed when the front cover is removed and c ont act with them will result in electri c shock .
E6581429 A-12 1 Q Charge lam p Charge lamp is inside the unit front cover open. Never remove the f ront cove r while power is on or within 15 minut es after power off, nor turn on the power while the front cover is open. They can result in electric sho ck.
E6581429 A-13 1 Q VFPS1-4300PLE~4 900PL E A switch or switches enable to reduce grounding capacitance. Q VFPS1-4007PDE~4220PDE There is no switch. Q VFPS1-4300PDE~4900PDE A switch enables to reduce grounding capacitance.
E6581429 A-14 1 1.4 No t es on the ap p lication 1.4.1 Installation Q Inst allation env ironment • Operate in areas where ambient temperature ranges from –10°C to 50°C. Where ambient temperature will rise abo ve 40°C, derating of rated current is ne eded.
E6581429 B-1 2 2. Connection of equipm ent 2.1 Cautions on wiring Q Wi r in g • Following power terminals a re cage type ones. - Input terminals of VFPS1-4007PDE to 4220PDE - All power terminals of VFPS1 -4300PLE to 4900PLE, VFPS1-4300 PDE to 4900PDE For tightening to rq ue and cable s tripping length, refer to 1.
E6581429 B-2 2 2.2 Standard conn ections [St andard connection diagram – s ink logic] The figure below show s an example of typical wiring in the ma in circuit 200V 0.4-45kW/400V 0.75-75kW inv erter. This inverte r has followin g three settin g/monitor mod e s.
E6581429 B-3 2 [St andard connection diagram – so urce logi c] The figure below show s an example of typical wiring in the ma in circuit 200V 0.4-45kW/400V 0.75-75kW inv erter. This inverte r has followin g three settin g/monitor mode s. *1: A DC reacto r (DCL) is incorporated in the position sho wn the figure above.
E6581429 B-4 2 2.3 Description of terminals 2.3.1 Main c ircuit termin als This diag ram sh ows an ex ample of w iring of the mai n circui t. Use opt ions i f necess ary . Q Power supply and motor connections Power suppl y S/L2 T/L3 Moto r No-fus e breaker Connect the power cables to RL1 , S/L2, and T/L3 .
E6581429 C-1 3 3. Operations 3.1 Sett ings to be made at first power on When the inverter is p owered on at the first time after purcha se, the Language selection windo w shown below appears on the LCD panel. In this window , s elect the langua ge you want to displa y on the screen.
E6581429 C-2 3 3.2 Setting/ monito r modes This inverter has following three setting/monitor modes. (1) T op View Mo de When the inverter is p owered on, it enters this mode first. The top window displays the operating statu s. In this mode, you can set a panel operation frequency, use a function key as the EASY key , and so on.
E6581429 C-3 3 3.3 Operation in T op View Mode When the inverter is p owered on, it enters this mode first, which allows you to monitor the operating status , set an operation frequency , use EASY key , and switch between lan guages. When Panel Jog Run is selected, a jog run frequency also can be specified in this mode.
E6581429 C-4 3 2. A fter selecting the pos ition of a figure you want to change, specify /confirm a value with the cont rol dial. (In this example, 30.
E6581429 C-5 3 (2) Loca l / Re mo te ke y f u nc ti on • “Loc/ Rem ” i s displayed. ([F1] key is in OFF State) In this state, remote controlled ope ration via terminal board is available. • If the [F1] ke y is pressed while “Loc/ Rem ” is d isp la yed, it tu rns to “ Loc /Rem ”.
E6581429 C-6 3 1. Press the [F4] key to carry out jog run. The jog run frequenc y is displayed on the screen. (In this example, the operation frequency is set at 5.0 H z.) Operation conti nues as long as the [F4] key is pressed, and it stops when the [F4] key is released.
E6581429 D-1 4 4. Searching and setting p arameters In the Parameter Setu p Mode, you can set basic parameters and extended parameters. This mode also al lows you to use the history function (paramete.
E6581429 D-2 4 4.2 Settin g a ba si c paramet e r When Quick mode is sele cted using the EASY key function, skip step 1. Go straight to step 2. 1. Select/confi rm “Basic p arameters” using the control dial . The Basic Paramete rs window appears. Functio ns of func tion keys : Goes to the T op View M ode.
E6581429 D-3 4 3. Using the control d ial, select/confi rm an item or specify /confirm a value. (In this example, “Panel / LCD-optio n” is selec te d and c onfirm ed or frequ enc y of 90.0Hz is specified and confirmed.) When the change you made is saved, the title of the parameter stops blinking and the s creen returns to the previous window .
E6581429 D-4 4 4.4 Searching for parameters who se setting has been chan ged (Changed Para meters) This function displa ys parameters whose current settings a re dif ferent from thei r d efault settings, and their present settings. 1. Select/confirm “Changed Parameters” using th e control dial.
E6581429 E-1 5 5. Monitoring the operation st atus In the S tatus Monitor Mode, you c an monitor various kinds of st atuses and information, such as the operating sta tus of the inv erter , information on the termi nal board, an d trip informati on. Functions of function keys : Goes to the T op View Mode.
E6581429 E-2 5 5.1 Displaying det ails of an item monitored 1. Select/confirm the desired it em using the control dial. (Ex. Select/confirm “Output current”) The monitor w indow of the it em selected ap pears. * Depending on t he item sel ected, no monit or window may be displayed.
E6581429 F-1 6 6. List of function k ey functions Each function key is corresponding to the function w hose abbrevia ti on or graphic s y mbol is displayed at the bottom of the window and over t he key . And by pressing a f unction key , correspond in g function is performed.
.
E6581429 G-1 7 7. Measures to satisfy the st andards 7.1 How to cope w ith the CE standar ds 7.1.1 Measures to satisfy the EMC directive Concr ete mea sures to EMC di rectiv e are s hown be low . (1) This inverter installs a EMC filter inside. So the conducted and radiated noise can be reduced.
E6581429 G-2 7 Q Ex. Countermeasure – in verter w iring PLE - type PDE - type Power supply wiring (Shielded cables) Power supply wiring (Shielded cables) R / L 1 , S / L 2 , T / L 3 M o t o r w i r .
E6581429 G-3 7 Q Wiring por t pla te PLE – type PDE - type A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) J (mm) 4007PLE~4022PLE 97.5 97.5 84 91.5 83 74 20.5 (20.7) 25.5 (22.8) 16.5 (18.8) 4037PLE, 4055PLE 1 11.5 1 1 1.5 84 91.5 83 74 20.5 (20.
E6581429 G-4 7 7.2 Measurement s to be taken to satisfy the UL/CSA sta ndards 7.2.1 Caution as to periphera l devices When installing a no-fuse c ircu it breaker or a fuse box on the p rimary side of the inverter, use UL-certified one.
E6581429 H-1 8 8. Selection of peripheral devices 8.1 Sele c tion of wiring mat e ri al s and de vic e s Wir e si z e Main circ uit Input terminal (R,S,T) Output terminal (U,V ,W ) DC terminal (option.
E6581429 H-2 8 Q Selection of wiring equipment No-fuse breaker (MCCB) Magnetic contactor (MC) Applicable motor (kW) Inve rter type form Input current [A] Rated current [A] Rated current [A] AC-1 0.75 VFPS1-4007PLE/PDE 1.8 4 25 1.5 VFPS1-4015PLE/PDE 3.
E6581429 I-1 9 9. T able of parameters For parameters, refer t o the instruction manual E6581386. Ho wever , for totally enc losed box type drives, only following points are different. Title Communication No. Fun ct ion Adjustment range CF 0300 PW M carrier frequency 1.
.
E6581429 J-1 10 10. Specifi cations 10.1 Models and their st andard specifications 1) S tandard specifications Item Specif ication V oltage class 400V class Applicable motor (kW) 0.75 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 Applicable motor (HP) 1 2 3 5 7 .
E6581429 J-2 10 2) Common specification Item Specif ication Control system Sinusoidal PWM control Output voltage adjustment Main circuit voltage feedback control. (Sw itchable between automatic adjustment/ fix/control off) Output frequency range Setting between 0.
E6581429 J-3 10 (Con tinued) Item Specifica tion Alarms Stall prevention du ring operation, overload limit, ov erload, undervoltage on power source side, DC circuit undervoltage, setting e rror , in retry , upper limit, lower limit.
E6581429 J-4 10 10.2 Out side dimensions and mass Q Out side dimensions and weight Dimensions (mm) Applicable motor (kW ) Applicable motor (HP) Inverter type W H D W 1 H1 Drawing Approximate mass (kg) [Note 1] 0.75 1 VFPS1-4007PLE(PDE) 1.5 2 VFPS1-4015PLE(PDE) 2.
E6581429 J-5 10 Fig. C Fig. D Fig. E Fig. F.
E6581429 J-6 10 Fig. G Fig. H.
デバイスStreamLight VF-PS1の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
StreamLight VF-PS1をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはStreamLight VF-PS1の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。StreamLight VF-PS1の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。StreamLight VF-PS1で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
StreamLight VF-PS1を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はStreamLight VF-PS1の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、StreamLight VF-PS1に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちStreamLight VF-PS1デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。