ECONOMIZERS WITH EXHAUST Model EIFM-5C For Use with Bard 3-1/2 through 6 T on W all Mount Air Conditioners and Heat Pump s INST ALLA TION INSTRUCTIONS Manual : 2100-447 Supersedes: File: V olume III T ab 19 Date: 12-14-04 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914.
Manufactured under U.S. Patent number 5,301,744. Other patents pending. COPYRIGHT DECEMBER 2004 BARD MANUFACTURING COMPANY BRYAN, OHIO USA 43506 CONTENTS GENERAL General Information ................................................. 1 Unpacking .......
Manual 2100-447 Page 1 GENERAL GENERAL INFORMATION The economizer should only be installed by a trained heating and air conditioning technician. These instructions serve as a guide to the technician installing the economizer package.
Manual 2100-447 Page 2 INST ALLA TION BASIC INSTALLATION 1. Unpack the economizer assembly which includes the integral economizer with attached electrical harness, mixed air thermistor, miscellaneous hardware and installation instructions.
Manual 2100-447 Page 3 IMPORTANT: Position front lip of economizer on top of front grille and condenser partition (See Figure 2 inset.) This is important to ensure proper drainage of any water entering damper assembly. LEFT HAND UNITS – Slide the economizer to the left until it is tight against the back of the corner panel.
Manual 2100-447 Page 4 FIGURE 3 MIS-1356.
Manual 2100-447 Page 5 FIGURE 4 TOP VIEW OF CONTROL PANEL MIS-350 MIS-350.
Manual 2100-447 Page 6 10. Connect leads with fork terminal to corresponding points on terminal strip. RE: C.Y.G. (See wiring diagram.) 11. Wire nut leads with 5/8" stripped ends to Y1 and Y2 leads from thermostat. See wiring diagram in this manual.
Manual 2100-447 Page 7 FIGURE 5 ECONOMIZER OPERATION F. Readjust temperature on the thermostat to engage the second stage of cooling (Y2). The damper motor should return to previously set minimum position. Compressor motor should start. G. Switch thermostat to OFF fan and OFF heat/ cool positions to de-energize unit.
Manual 2100-447 Page 8 CONDITION B – WARM OUTDOORS First stage cooling cycles the compressor and dampers remain in mechanical cooling mode. FIGURE 6 MECHANICAL COOLING OPERATION MIS-348.
Manual 2100-447 Page 9 WALL THERMOSTATS FOR HEAT PUMPS WITH ECONOMIZER Thermostat Part 8403-027 (White Rodgers IF92-71) Electronic Heat Pump Thermostat 2 Stage Cool / 3 Stage Heat FOR AIR CONDITIONING.
Manual 2100-447 Page 10.
デバイスBard EIFM-5Cの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bard EIFM-5Cをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBard EIFM-5Cの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bard EIFM-5Cの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bard EIFM-5Cで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bard EIFM-5Cを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBard EIFM-5Cの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bard EIFM-5Cに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBard EIFM-5Cデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。