INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS W A381 W A423 W A484 W A491 W A602 Manual : 2100-398A Supersedes: 2100-398 File: V olume III T ab 16 Date: 05-28-02 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned.
Contents Figures Figure 1 Unit Dimensions ...................................... 3 Figure 2 Fresh Air Damper Assembly ................... 6 Figure 3 Mounting Instructions .............................. 8 Figure 4 Electric Heat Clearance ..............
Manual 2100-398 Page 1 GETTING OTHER INFORMA TION AND PUBLICA TIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-398 Page 2 W ALL MOUNT GENERAL INFORMA TION HEAT PUMP WALL MOUNT MODEL NOMENCLATURE W A 42 3 – A 10 X N X X X A NOTE: All vent options are without exhaust capability.
Manual 2100-398 Page 3 MIS-1262 FIGURE 1 UNIT DIMENSIONS l e d o M h t d i W ) W ( h t p e D ) D ( t h g i e H ) H ( y l p p u Sn r u t e R EF G I J K L M N O P Q R S T A BCB 8 3 A W 2 4 A W 8 4 A W 9 4 A W 0 6 A W 5 7 0 . 2 42 3 4 . 2 25 7 8 . 4 88 8 .
Manual 2100-398 Page 4 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. l These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors.
Manual 2100-398 Page 5 j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75 ° C copper wire. All wiring must conform to NEC and all local codes. l These “ Minimum Circuit Ampacity ” values are to be used for sizing the field power conductors.
Manual 2100-398 Page 6 FILTERS A one inch throwaway filter is supplied with each unit. The filter slides into position making it easy to service. This filter can be serviced from the outside by removing the service door. A one inch washable filter and two inch pleated filter are also available as optional accessories.
Manual 2100-398 Page 7 INST ALLA TION INSTRUCTIONS W ARNING Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing damage, injury or death. WALL MOUNTING INFORMATION 1.
Manual 2100-398 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS-416.
Manual 2100-398 Page 9 FIGURE 4 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPL Y AIR DUCT FOR W ALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURF ACES. MIS-277 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials.
Manual 2100-398 Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS-548 MIS-549 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR OPENING RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET.
Manual 2100-398 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS-550.
Manual 2100-398 Page 12 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.
Manual 2100-398 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS-1373D.
Manual 2100-398 Page 14 ST ART UP IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. HIGH PRESSURE SWITCH The WA381, WA484, WA491 and WA602 models are supplied with a remote reset high pressure switch.
Manual 2100-398 Page 15 SEQUENCE OF OPERATION COOLING – Circuit R-Y makes at thermostat pulling in compressor contactor, starting the compressor and outdoor motor. The G (indoor motor) circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase of constant air circulation.
Manual 2100-398 Page 16 REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit. 2. Remove the screws holding both grilles, one on each side of unit, and remove grilles. 3. Remove screws holding fan shroud to condenser and bottom. Nine (9) screws. FIGURE 9 FAN BLADE SETTING TROUBLESHOOTING 4.
Manual 2100-398 Page 17 TABLE 9 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY V alues shown are for units equipped with standard 1 inch throwaway filter or 1 inch washable filter .
Manual 2100-398 Page 18 Low side pressure ± 2 PSIG High side pressure ± 5 PSIG Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.
Manual 2100-398 Page 19 TABLE 11 OPTIONAL ACCESSORIES WA381-A WA381-B WA381-C WA423-A WA423-B WA423-C WA484-A WA484-B WA484-C WA491-A WA491-B WA491-C WA602-A WA602-B WA602-C t r a P r e b m u Nn o i t.
デバイスBard WA484の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bard WA484をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBard WA484の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bard WA484の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bard WA484で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bard WA484を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBard WA484の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bard WA484に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBard WA484デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。