BardメーカーWL4823の使用説明書/サービス説明書
ページ先へ移動 of 21
INST ALLA TION INSTRUCTIONS W ALL MOUNTED P ACKAGE AIR CONDITIONERS MODELS WL4822 WL4823 WL6022 WL6023 WL602N Manual : 2100-351D Supersedes: 2100-351C File: V olume III T ab 16 Date: 09-20-01 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned.
Contents Figures Figure 1 Unit Dimensions ..................................... 3 W A602N, WA6023, W A4823 Figure 2 Unit Dimensions ..................................... 4 W A6022, WA4822 Figure 3 Mounting Instructions ............................. 8 W A602N, WA6023, W A4823 Figure 4 Mounting Instructions .
Manual 2100-351 Page 1 Getting Other Information and Publications These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Manual 2100-351 Page 2 W ALL MOUNT GENERAL INFORMA TION AIR CONDITIONING WALL MOUNT MODEL NOMENCLATURE WL 60 2 3 A 10 X N X X X A NOTE: All vent options are without exhaust capability. May require separate field supplied barometric relief in building.
Manual 2100-351 Page 3 FIGURE 1 UNIT DIMENSIONS WL602N, WL6023, WL4823 ONLY MIS-1451.
Manual 2100-351 Page 4 FIGURE 2 UNIT DIMENSIONS WL6022, WL4822 ONLY MIS-1452.
Manual 2100-351 Page 5 TABLE 2 ELECTRICAL SPECIFICATIONS j k l Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75 ° C copper wire. All Wiring must conform to NEC and all local codes.
Manual 2100-351 Page 6 A 1/4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required. See Wall Mounting Instructions and Figures 3 and 3A for further details. Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity.
Manual 2100-351 Page 7 INST ALLA TION INSTRUCTIONS WALL MOUNTING INFORMATION 1. Two holes for the supply and return air openings must be cut through the wall as shown in Figure 1 or 2. Figure 1 is for models WL4823, and WL6023. Figure 2 is for Models WL822 and WL6022.
Manual 2100-351 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS WL602N, WL6023, WL4823 ONLY MIS-1349.
Manual 2100-351 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS WL6022, WL4822 ONLY MIS-1444.
Manual 2100-351 Page 10 FIGURE 5 ELECTRIC HEAT CLEARANCE SIDE SECTION VIEW OF SUPPL Y AIR DUCT FOR W ALL MOUNTED UNIT SHOWING 1/4 INCH CLEARANCE TO COMBUSTIBLE SURF ACES. MIS-277 W ARNING A minimum of 1/4 inch clearance must be maintained between the supply air duct and combustible materials.
Manual 2100-351 Page 11 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS MIS-548 MIS-549 MIS-948 SEE FIGURE 3 – MOUNTING INSTRUCTIONS SUPPLY AIR OPENING RETURN AIR OPENING RETURN AIR OPENING SUPPLY AIR OPENING BOTTOM MOUNTING BRACKET.
Manual 2100-351 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS MIS-550.
Manual 2100-351 Page 13 WIRING – MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR” type circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current.
Manual 2100-351 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS-1373A.
Manual 2100-351 Page 15 ST ART UP IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dish washing detergent. CRANKCASE HEATERS These units are not provided with crankcase heat. These units utilize scroll compressors which do not require crankcase heat in this application.
Manual 2100-351 Page 16 PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.
Manual 2100-351 Page 17 The suction line temperatures in table above are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle. REMOVAL OF FAN SHROUD 1. Disconnect all power to the unit.
Manual 2100-351 Page 18 TABLE 9 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY Values shown are for units equipped with standard 1 ” throwaway filters or 1 ” washable filters. Derate ESP by .15 for 2 ” pleated filters. S L E D O MP S E - 3 2 0 6 L W Y L N O 5 0 A 0 1 A 9 0 B 4 .
Manual 2100-351 Page 19 TABLE 11 OPTIONAL ACCESSORIES WL6023A. WL6022A WL6023B, WL6022B WL4823A, WL4822A WL4823B, WL4822B t r a P r e b m u Nn o i t p i r c s e D 5 1 - C M Ct i K t r a t SX X A 9 0 -.
デバイスBard WL4823の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bard WL4823をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBard WL4823の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bard WL4823の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bard WL4823で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bard WL4823を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBard WL4823の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bard WL4823に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBard WL4823デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。