D200-39-00 1 I56-1977-004R 3825 Ohio A venue , St. Charles, Illinois 60 174 800/736-7672, F AX: 630-377-6495 www .s ystemsensor .com Before installing detectors, please thoroughly read the NEMA Guide .
1. Re move the front cov er . 2. Slide the plastic sampling tube into the housing bushing. 3. Align the holes in the bushing with the holes in the sampling tube . Make sure there are 6 exposed holes on the plastic sampling tube . Secure with the #8 self-tapping scr ew into the bottom of the permanent tube (shown in Fig.
D200-39-00 3 I56-1977-004R SCREW HOLES FOR A TT A CHING HOUSING T O DUCT W ORK. Figure 3. Installation of foam gaskets over sampling tube bushings: Figure 5. T ube mounting configurations with var ying air flow dir ection: T able 1. Sampling tubes r ecommended for dif fer ent duct widths: Outside Duct Width Sampling Tube Recommended* 1 to 2 ft.
T wo LEDs on each duct smoke detector may light, if programmed by the sy stem control panel, to pro vide a local, visible indication. Remote LED annunciator capability is a vailable as an option. Each duct smoke detector can only be wired to one remote accessory .
D200-39-00 5 I56-1977-004R [9.1] Smoke Entr y T ests [9.1.1] Air Flow This pro duct is d esigned to operat e o ver an exte nded air speed range of 1 00 to 4000 FPM. T o veri fy sufficient sampling of ducted air , turn the air han- dler on and use a m anometer to measure the differ ential pr essur e betwee n the two sampling tubes.
D200-39-00 6 I56-1977-004R Figure 10. W iring Diagram for DH200RPL Duct Detector with optional RA400Z: 5 7 RA400Z 5 = Alarm Signal 7 = Aux. Po wer (–) DO NOT BREAK T AB ON RA400Z Figure 11. System Wiring Diagram for DH200RPL Duct Smoke Detector with R TS451/RTS451KEY : ALARM SIGNAL AUX.
D200-39-00 7 I56-1977-004R [9.2.2.2] R TS451/R TS451KEY Remote Station T est The R TS45 1/R TS45 1KEY Remote T est Station facilitates test of the alarm capability of the duct smoke detector . These accessories provide the stimulus to initiate an alarm condition at the detector .
Curr ent Requir ements (using no accessories) P ow er supply voltage: 20-3 0 VDC 24 V A C, 50-60 Hz 120 V A C, 50-60Hz 220/240 V A C, 50-60Hz Max. standby current: 26 mA 65 mA RMS 44 mA RMS 25 mA RMS Max. alarm current: 87 mA 182 mA RMS 52 mA RMS 3 0 mA RMS Alarm response time: 3 to 1 0 Sec.
デバイスSystem Sensor DH200RPLの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
System Sensor DH200RPLをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSystem Sensor DH200RPLの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。System Sensor DH200RPLの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。System Sensor DH200RPLで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
System Sensor DH200RPLを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSystem Sensor DH200RPLの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、System Sensor DH200RPLに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSystem Sensor DH200RPLデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。