D400-13-00 1 I56-555-09R DH400ACDCP Air Duct Smoke Detector INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .
[3] Contents Of The Duct Detector Kit 1. Complete housing base and cov er assembly 2. T wo #1 0 sheet metal mounting scre ws 3. T wo sampling tube filter s 4. One test magnet 5. Drilling template 6. T wo 5/16 O-rings 7. T wo rubber tube bushing seals 8.
feet per minute . Be sur e to check engineering specifications to ensure that the air velocity in the duct falls within these parameter s . If necessary , use a velocity meter to check the air velocity in the duct. [5.2] Drill The Mounting Holes R emo ve the paper backing from the mounting template supplied.
[5.4.1] Installation For Ducts Less Than 8 Feet Wide 1. If the tube is longer than the width of the air duct, drill a 3/4-inch hole in the duct directly opposite the hole already cut for the inlet tube. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4.
Install the inlet tube as follow s: 1. Drill a 3/4-inch hole in the duct directly opposite the hole already drilled for the inlet tube . 2. Slide the inlet tube with the flange into the centermost housing bushing. Position the tube so that the arr ow s point into the air flow .
24V 120 VAC 220/240 VAC 1 2 1 2 13 14 AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 16 17 18 19 20 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.
24V 120 VAC 220/240 VAC 1 2 12 13 14 AVAILABLE POWER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC. 15 16 17 18 19 20 N.C. C. N.O. N.O. C. N.C. ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.
[5.6] Install The Filters T o install the sampling tube filters , simply push the filter adapter into the exhaust tube, and push the filter onto the adapter tube on the left, as shown in Figure 9. Install the other filter ov er the end of the inlet sampling tube .
[6.1] Smoke Entr y T ests [6.1.1] Air Flow T o verify sufficient sampling of ducted air , use a manometer to measure the differ ential pressure created from air flow across the sampling tubes . The pr essure should measure no less than 0.0 1 inches of water and no greater than 1.
the R T S45 1/R T S45 1KEY manual. The DH400A CDCP duct detector can be reset by the R T S45 1/R T S45 1KEY . If a sys- tem control panel is used, the panel itself may also requir e resetting. T o install the R T S45 1/R T S45 1KEY , connect the device as shown in Figur e 8; wir e runs must be limited to 25 ohms or less per interconnecting wire .
3. V acuum the photo chamber . Use clean compr essed air to blow it clean. 4. R eplace the screen by aligning the arro w on top with the field test port on the detector . Press the screen into place . It should fit tightly on the chamber . 5. R eplace the detector co v er and rotate it clockwise to lock it in place .
[8] Model DH400ACDCP Air Duct Smoke Detector Specifications Description HV A C air duct mounted ionization or photoelectronic smoke detector for separately power ed sy stems or stand alone sys- tems. A uxiliary alarm relay contacts pr ovide fan contactor shutdo wn to pr e vent HV A C circulation of smoke .
Electrical Specifications P o wer supply v oltage: 20-29 VDC 24 V A C 5 0-60-Hz 120 V A C 50-60 Hz 220/240 V A C 50-60 Hz Input capacitance: 27 0 µ F max. 27 0 µ F max. N/A N/A R eset v oltage: 3.0 VDC min. 2.0 V A C min. 1 0 V A C min. 20 V A C min.
NOTES D400-13-00 14 I56-555-09R.
NOTES D400-13-00 15 I56-555-09R.
D400-13-00 16 I56-555-09R © Sy stem Sensor 1997 DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model: ______________________ Number: ___________________.
デバイスSystem Sensor DH400ACDCPの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
System Sensor DH400ACDCPをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSystem Sensor DH400ACDCPの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。System Sensor DH400ACDCPの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。System Sensor DH400ACDCPで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
System Sensor DH400ACDCPを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSystem Sensor DH400ACDCPの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、System Sensor DH400ACDCPに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSystem Sensor DH400ACDCPデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。