D500-0 7-00 1 I56-432-1 1R DH500ACDC Intelligent Air Duct Smoke Detector Housing INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .
D500-0 7-00 2 I56-432-1 1R The DH500A CDCs ar e built to operate on 120/240 V A C or 24 V A C/DC. T wo form-C (SPD T) relay contacts are av ail- able for control purposes. T wo LEDs on each detector latch on to pro vide a local alarm indication. R emote alarm indi- cation is made possible b y using the auxiliary alarm output (see Figur e 5).
D500-0 7-00 3 I56-432-1 1R Exception: Where it is physically impossible to locate the detector accordingly , the detector can be positioned closer than six duct widths , but as far as possible from the open- ing, bend, or deflection plates. Step 3. Mount Duct Housing R emov e the duct housing cover .
A. Installation for Ducts Less Than 8 Feet Wide 1. If the inlet tube is longer than the width of the air duct, drill a 3/4-inch hole in the duct directly opposite the hole alr eady cut for the inlet tube. If the inlet tube is shorter than the width of the air duct, install the end cap into the inlet tube as shown in Figure 3.
av ailable at most plumbing supply houses, may be used. This flange/connector mounting technique makes the initial installation easier because a 1- inch to 1-1/4-inch hole may be drilled where the flange/connector will be used. It is easier to push the inlet tube through the lar ger hole .
ALARM SIGNAL (+) AUX POWER (–) 2 6 (+) (–) DUCT DETECTOR DH500ACDC PA400 (OPTIONAL) AUDIBLE ALERT ALARM SIGNAL (+) AUX POWER (–) 2 6 (+) (–) DUCT DETECTOR DH500ACDC RA400Z (OPTIONAL) REMOTE (L.
Step 7. Per form Detector Check 7.1 Air Flow 1. T o verify sufficient sampling of ducted air , use a manom- eter to measure the differential pr essure created from air flo w acr oss the sampling tubes. The pr essure should measure no less than 0.0 1 inches of w ater and no greater than 1.
Step 8. Install the Cover Install the cover using the four scre ws . Be certain filters are installed as specified in Step 6. Make sure that the cover fits into the base gr oove and that all gaskets ar e in their proper positions. Tighten the four cov er scre ws to 1 0 in-lbs .
1. T urn off power to the system. 2. R emove and inspect sampling tube filter s. 3. If filters ar e heavily coated with dirt, r eplace them with new filter s. If they ar e not heavily coated, use a vacuum cleaner or compressed air nozzle to remo ve dust, then install the filters .
A ccessories P art No. R emote LED RA400ZA Piezo Alert Sounder P A400 R eplacement Filter s F36-05-00 Magnet M02-04-00 End Plug F or Sampling T ube P48-2 1-00 Installation Kit (P arts bag) A2650-0 1 I.
Sy stem Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and ser- vice for a period of three y ears fr om date of manufactur e. S ystem Sensor makes no other e xpress warr anty for this air duct smok e detector .
D500-0 7-00 12 I56-432-1 1R © 200 1 S ystem Sensor DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model:______________________ Number: __________________.
デバイスSystem Sensor DH500ACDCの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
System Sensor DH500ACDCをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSystem Sensor DH500ACDCの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。System Sensor DH500ACDCの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。System Sensor DH500ACDCで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
System Sensor DH500ACDCを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSystem Sensor DH500ACDCの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、System Sensor DH500ACDCに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSystem Sensor DH500ACDCデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。