D1 00-67-00 1 I56-1 148-04 DH100 Air Duct Smoke Detector INSTALLATION AND MAINTENANCE INSTRUCTIONS A Division of Pittwa y 3825 Ohio A venue, St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 630-377-6.
holes as indicated on the template . Insert the two jack nut receptacles . Drive a #1 0 machine screw into the jacknut to flare the r etainer and then back the screw out to use for de- tector mounting. [5.2.1] Sampling Tube Installation for Ducts Less Than 1 1 / 2 Feet Wide (see Figur e 2) 1.
[5.3] Secure The Detector Housing T o The Duct Slide the foam gaskets o ver the tube bushings as shown in Figure 3. Use the tw o machine screw s to screw the detector housing to the duct. CA UTION: Do not o vertighten the scr ews . Figure 3. Installation of foam gaskets over sampling tube bushings: A78-2045-00 [5.
W ARNING In no case should more than 2 air inlet holes be cut off the tube . There must be a minimum of 1 0 holes in the tube ex- posed to the air stream. [5.4.2] Installation For Ducts More Than 8 Feet W ide NO TE: T o install inlet tubes in ducts more than 8 feet wide , work must be performed inside the air duct.
F or signal wiring, (the wiring betw een interconnected de- tectors or fr om detectors to auxiliary devices), it is usually recommended that single conductor wir e be no smaller than 18 gauge . The duct smoke detector terminals accom- modate wire sizes up to 12 gauge .
D1 00-67-00 6 I56-1 148-04 SUPERVISORY SWITCH 76 4 (+) IN (+) OUT (+) (+) 5 8 (–) (–) IN (–) OUT 1ST DETECTOR IN LOOP DH100 (–) RA400Z (OPTIONAL) REMOTE ALARM LED 2.8 VDC NOM. IN ALARM SUPERVISORY SWITCH 76 4 (+) IN (+) OUT (+) (+) 5 8 (–) (–) IN (–) OUT LAST DETECTOR IN LOOP DH100 (–) RA400Z (OPTIONAL) REMOTE ALARM LED 2.
D1 00-67-00 7 I56-1 148-04 [6.2.2] Alarm T ests [6.2.2.1] M02-04-00 Magnet T est 1. Place the painted surface of the magnet onto the TEST locator on the bottom of the housing (Figur e 9). 2. The red alarm LEDs on the detector should latch on, as should any accessories (i.
[9] Model DH100 Air Duct Smoke Detector Specifications T emperature: 32 ° to 13 1 ° F0 ° to 55 ° C Humidity: 1 0% to 93% R.H. noncondensing Air V elocity: 500 to 4000 ft./min. 2.5 to 20.3 m/sec . Dimensions: 14.38 ″ L x 5.5 ″ W x 2.75 ″ D 36.
デバイスSystem Sensor I56-1148-04の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
System Sensor I56-1148-04をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはSystem Sensor I56-1148-04の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。System Sensor I56-1148-04の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。System Sensor I56-1148-04で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
System Sensor I56-1148-04を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はSystem Sensor I56-1148-04の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、System Sensor I56-1148-04に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちSystem Sensor I56-1148-04デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。