1 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 Owner’ s Manual — Phoenix 200 MAX Installation, Operation & Ser vice Instr uctions Read and Sav e These Instr uctions Phoenix 200 MAX TS-262C The Phoenix 200 MAX is one of the most effective and versatile dr ying devices a vailable.
2 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 1 Specifications P ar t No. 4024920 P ower 110-120 V ac, 7.4 amps; 851 watts W ater 133 pints/day @ AHAM (80°F , 60%) Removal 240 pints/day @ saturation 30 gal/da y maximum @ saturation Refrigerant 1 lbs.
3 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 • The air inlet on top & the side outlet must be at least 1 foot from walls and other obstructions to air flow . • If the humid area is ver y large, dehumidification can be improved b y adding an outlet duct to circulate air to stagnant areas (see Sec.
4 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 2.10 Low Pressure Control If the low side refrigerant pressure drops to 15 PSIG, the low pressure control opens and shuts off the compressor and blower . It is an automatically reset control.
5 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 The mixture of gas and liquid refrigerant enter the accumulator after lea ving the evaporator coil. The accumulator prevents an y liquid refrigerant from reaching the compressor .
6 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 5. Rotate the blower outlet tow ard you as you remove it. Use care to a void hooking wiring , tubing or electrical components. 6. Reassembling with the new blow er in the above procedure reversed.
7 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 If sludge is evident in the discharge line, it will likely be found in the suction line; this indicates the compressor burned out while r unning. Sludge and acid ha ve been pumped throughout the system.
8 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 Figure 3: Electrical schematic of 200 MAX 5 Wiring Diagram.
9 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 Item P ar t No. Qty . Description 1 4022254 1 Accumulator 4021475 1 Air F ilter , Pleated, 2” x 16” x 20” 65% Mer v-1.
10 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 This page intentionally left blank..
11 www .thermastor .com • sales@ther mastor .com T oll-F ree 1-800-533-7533 Phoenix 200 MAX Dehumidifier Limited W ar ranty W arrantor : Therma-Stor LLC PO Box 8680 Madison, WI 53708 T elephone: 1-.
デバイスTherma-Stor Products Group 200 MAXの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Therma-Stor Products Group 200 MAXをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTherma-Stor Products Group 200 MAXの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Therma-Stor Products Group 200 MAXの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Therma-Stor Products Group 200 MAXで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Therma-Stor Products Group 200 MAXを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTherma-Stor Products Group 200 MAXの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Therma-Stor Products Group 200 MAXに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTherma-Stor Products Group 200 MAXデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。