Installation, Oper ation, and Maint enance Sept ember 2006 PT A C-S VX0 1C-EN PTEE070/PTHE070 (7 ,00 0 Bt uh) PTEE090/PTHE 090 (9,00 0 Bt uh) PTEE1 20/PTHE1 20 (1 2,00 0 Bt uh) PTEE1 50/PTHE1 50 (1 5,.
2 PT AC-S VX01C-EN T able of Con tents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Model Number Descr ipti on . . . . . . . . . . . . . . . . . . . . . . . . . 3 Gener al Infor mation . . . . . . . . . . . . . . . . . . . . . .
PT AC-S VX0 1C-EN 3 *All heat pump units must have electric heat. Digit 8—Main P ow er Supply 1 = 230-208V/60Hz/1phase 2 = 265V/60Hz/1phase 4 = 1 15V/60Hz/1phase (Hydronic Only) Digit 9 —Electric .
Gener al Infor m ation © 20 05 American Standard Inc. All rights reserved PT AC-S VX01C-EN NO TICE: W ar nings and Cautions appear in appr opr iate sections thr oughout this manual. Read these carefully . WA R N I N G Indicat es a pot entially hazar dous situati on which, if not a void ed, could r esult in death or ser ious injury .
PT AC-S VX0 1C-EN 5 General Information Refr iger ant Handling Pr ocedur es WA R N I N G Contains Refr iger ant! Syst em contains oil and r efri ger ant under high pr essure. Reco ver ref ri ger an t to re l ie ve p res s ure be fo re opening the syst em.
6 PT AC-S VX01C-EN Pre-Installation Pr e-Installation Consider ations Before beginning installati on, make the followin g considerations: 1 . V erify the w all opening is in the cor rect location and the cor rect siz e.
PT AC-S VX0 1C-EN 7 Pre-Installation Receiving and Handling Shipping P ack age The c hassis and the cabinet front ship in one car ton . Accessories ship separate. Receiving Chec klist Complete the following c hec klist immediately after receiving unit shipmen t to detec t possible shipping damage.
8 PT AC-S VX01C-EN Unit Dimensions Figur e 4. Unit with w all sleeve and subbase accessory Figure 5. W all Sleeve Unit Dimensions.
PT AC-S VX0 1C-EN 9 Unit Dimensions Figur e 6. T o p view of the h ydr onic kit Figur e 7 . Hydr onic kit fr ont view Figur e 8. Hy dronic kit sid e view PTAC Wall Sleeve Air discharge Unit controls c.
10 PT AC-S VX01C-EN Installation WA R N I N G Live Ele ctr ical Components! Dur ing installation, tes ting, servicing and tr oubleshooting of th is pro duct, it may be necessary t o wor k with live electr ical comp onents.
PT AC-S VX0 1C-EN 11 Installation T able 3. Electr ic heat cap acity and electr ica l data, models PTEE and PTHE (i) Nominal heating Building circuit requi rement Voltage (ii) Electric heater Size (kW) # of stages Btu/h at 230/208V Btu/h at 265V Total watts (iii) Unit total amps Minimum ampacity (iv) Maximum protection (v) Plug 230/208 2.
12 PT AC-S VX01C-EN Installation Installation Pr ocedure WA R N I N G Hazar dous V oltage w/ Capacitors! Disconnect all ele ctr ic pow er , including r emote discon nects befor e servicing. F ollo w proper lo ck out/ tagout pr ocedures t o ensure the pow er cannot be inadv ertently energiz ed.
PT AC-S VX0 1C-EN 13 Installation 2. Grasping the top and bottom flanges of the rear closure pa nel as shown in Figure 1 2 , the entire panel is pulled out d iagonally from one side.
14 PT AC-S VX01C-EN Installation 1. All units required either a p ower cord or hard wire kit to power th e unit 2. The Hydronic chas sis "W" ships with no e lectric heat 3. All Hydronic Chassis "W" un its required a p ower cord 4. All 265volt Hydronic chass is "W" required subbase, fuse s and socket.
PT AC-S VX0 1C-EN 15 Installation Note : If using a third par ty thermostat to control the unit, the thermostat must have a clearly m arked OFF state or position. Note : It is important to make sure that the control board’ s fuse is functioning. The specs for the control board fuse are: 5x20mm, 250V , 3 15mA, fast acting.
16 PT AC-S VX01C-EN Installation Notes: EN = Enabled - operations based on other logic Notes: N/C = No change from prior st ate Step 8. Configur e the display module set tings Indoor T emperat ur e setpoint The indoor temperature set p oint but tons tell the unit ho w warm or cool the occupan t w ants the room .
PT AC-S VX0 1C-EN 17 Installation Step 9. Pr ogrammable Set tings The controller has a total of six (7) parameters that are user - configurable: 1 . V ent Door Configurati on 2. Indoor F an Cycle configuration 3. T empera ture S etpoint Limiting configuration 4.
18 PT AC-S VX01C-EN Installation 1 . V entilation Door Function The power do or works based upo n control logic fun ctions. When the unit is on, the vent door will op en to allow fresh air to be cond itioned before entering the room. When the unit is off , the door cl oses to prevent unconditioned air from entering the room.
PT AC-S VX0 1C-EN 19 Installation Ener gy Manag e ment Sy ste m Occupanc y States The controller is designed to handle two possible occupancy s tates: • occupied • occupied standby When the Energ y Management System input is present, it is possible for the controller to switc h between the two occupancy states.
20 PT AC-S VX01C-EN Installation T able 14. PTEE manual t est sequence Step Indoor Fan High Indoor Fan Low Remote Fan Outdoor Fan Condensate Pump Com p Reversing Valve Aux.
PT AC-S VX0 1C-EN 21 Sequence of Operation A ut omatic 3-minut e Compr essor Lock out After the compressor cycles of f, it will not restart fo r three minutes. This feature prevents the compressor from shor t cycling and extends the overall life. A ut omatic 2nd Stag e Electr ic Heat (PTHE only) If the room temperature falls to 2.
22 PT AC-S VX01C-EN Operation Notes: 1. Connectio n to R enables input fu nctions W , Y , GL, GH, O,VT , and/or EN. 2. Connect 24VAC, 3V A maximum Remote F an Control R elay to RF and C Remot e F an Operation PT ACs can operate a remote fan to provide conditi oned air to additional rooms or areas that are not well ventilated.
PT AC-S VX0 1C-EN 23 Operation Notes: Certified in accordance with the Uni t ary Air -Conditioner Equipment Certification Progr am, which is based on ARI Standard 31 0/38 0.
24 PT AC-S VX01C-EN Operation Notes: Certified in accordance with the Uni t ary Air -Conditioner Equipment Certification Progr am, which is based on ARI Standard 31 0/38 0.
PT AC-S VX0 1C-EN 25 Operation T able 19. Cooling temperat u r e change - air conditioners Room air dry bulb Room air wet bulb PTEE0701 PTEE0702 PTEE 0901 PTEE0902 PTEE1201 PTEE1202 PTEE1501 PTEE1502 .
26 PT AC-S VX01C-EN Operation Notes: Shaded area is rating ampere 75 70 12 16 13 16 11 15 10 14 65 18 22 18 21 16 20 16 19 60 24 28 23 26 21 25 21 24 55 31 34 29 31 26 30 26 29 70 65 12 15 12 15 10 13 9 13 60 17 20 16 18 14 17 13 17 55 22 24 20 22 18 21 18 21 T able 21 .
PT AC-S VX0 1C-EN 27 Operation Notes: Shaded area is rating wattage T able 23. Heating total wat tage input — heat pumps Outside air dry-bulb Room air dry-bulb PTHE 0701 PTHE 0702 PTHE 0901 PTHE 090.
28 PT AC-S VX01C-EN Operation T able 25. Unit accessory model numbers Description Part Number Architectural Grilles ARCHITECTURAL ALU MINUM GRILLE BA YAAGL001 ARCHITECTURAL ALU MINUM GRILLE -DARK BRON.
PT AC-S VX0 1C-EN 29 Operation T able 26. Hydronic heat options Kit Description HH y d r o n i c Coil Type WW a t e r C o i l SS t e a m C o i l Accessory Type KK i t Power Voltage 01 208-230 VAC 02 2.
30 PT AC-S VX01C-EN Mainte nance Pr ocedur es P erform the follow ing maintenance procedures to e nsure proper unit operation. W ARNING Live Electr ical Components! Dur ing installation, t esting, servicing and troubleshooting of this product, it may be necessary to w or k with liv e electr ical components .
PT AC-S VX0 1C-EN 31 Maintenance 5. Reinstall the filter by reat ta c hing the hook to the bottom of the vent door and repl acing the two screws, slide the c hassis bac k into the wall sleeve, secure it in place with six screws and reinstall the front cabinet.
32 PT AC-S VX01C-EN Maintenance Leak T esting Refrigerant leaks are best detected with a halide or electronic leak detector . WA R N I N G Use of Pr essure Regulat or – V alves – Gaug es! Alwa ys use pressur e regulat ors, v a lv es, and gauges t o control drum and line pressur es when pressur e testing equipment.
PT AC-S VX0 1C-EN 33 Maintenance Figur e 22. Refrig eration sealed system — heat pump (air conditio ning model Figur e 23. Refrig eration sealed system — Heat pump (heat pump model) Ev acuation CA UTION F an Motor Ov er heat! Never te st operation without the unit in t he w all sleeve.
34 PT AC-S VX01C-EN Maintenance 4. Start the vacuum pump and open the shut-off valve to the high vacuum g auge manifold only . Af ter the compound gauge (low side) has dropped to approximately 29 inc hes of vacuum, op en the valve to the vacuum thermocouple gauge.
PT AC-S VX0 1C-EN 35 Maintenance Cooling P erfor mance T est Ther mometers The followin g precautions ar e necessary in observing the thermometer readings in the cooling performance test. 1 . Use two accurately calibrated refrigeration type thermomete rs or a thermocouple potentiometer .
36 PT AC-S VX01C-EN Maintenance 3. Locate the readin gs listed in the Operation section of this manual. Y ou will note that these readings fall within the vo ltag e, wa tts and amp draw minimu m and maximum ranges listed. Therefore, the unit heating performance would be considered normal.
PT AC-S VX0 1C-EN 37 Maintenance Resistance T est 1 . With no power , remove the leads from the compre ssor terminals. 2. T ouc h the leads of an ohmmeter to terminals C-S, star t windings and C-R, run wi nding. If either winding does not test continuous, replace the compressor .
38 PT AC-S VX01C-EN Maintenance T able 27 . Ther mistor indoor coil resistance x (C°) Rmin (k Ω ) Rnom (k Ω ) Rmax (k Ω ) -40.0 327.60 37 342.7771 358.6311 -39.0 306.47 13 320.4512 335.0471 -38.0 286.84 64 299.7818 313.1748 -37.0 268.61 17 380.
PT AC-S VX0 1C-EN 39 Maintenance WA R N I N G Hazar dous V oltage! Disconnect all ele ctr ic pow er , including r emote discon nects befor e servicing. F ollo w proper lo ck out/ tagout pr ocedures t o ensure the pow e r can not be inadvertently energiz ed.
40 PT AC-S VX01C-EN Maintenance Removing the Outdoor Coil and Outdoor Air Ther mistors 1 . Remove the c hassis from the wall. 2. Remove the front cabinet. 3. Remo ve the control box co ver . 4. Disconnect the outdoor coil/air thermistor wiri ng from th e control board.
PT AC-S VX0 1C-EN 41 Diagnostics The controller i s equipped to display a diagnostic code thro ugh the interface module ; if the display is not present (Class 2 cont rol), there is no method to retrieve the diagnostic codes from the unit.
42 PT AC-S VX01C-EN Troubleshooting T able 31 . Compr essor ou tput does not energiz e Probable cause Explanation Random restart timer All controller outp uts remain off until the time r expires. Selected mode OFF When off is selected at the display to the controller , the unit controls all outputs off .
PT AC-S VX0 1C-EN 43 Troubleshooting T able 34. Reversing v alve output does not energize Random restart timer Explanation Power up control wait All controller outp uts remain off until th e timer expires. S e l e c t e d m o d e O F F, F A N ONL Y Reversing v alve held in current state because compressor use is not allowe d.
44 PT AC-S VX01C-EN Troubleshooting T able 37 . Con densat e pump does not en er gize Probable cause Explanation Random restart timer All controller outp uts remain off until the timer expires. Selected mode OFF When off is selected at the display to the controller , the unit co ntrols all outputs off .
PT AC-S VX0 1C-EN 45 Figure 29. 230/20 8V wir i ng diagram (07 models) GR YL OR BK HI L N L H N BR YL LO HI N RD RD YL RD BK 1 2 3 4 5 6 7 8 3.0KW 1 2 3 4 5 6 7 8 8 7 65 4 3 2 1 2.
46 PT AC-S VX01C-EN Wiring Dia gram Figure 3 0. 230/208V Wiring di agr am (0 9, 12, 15 models) GR YL OR BK HI L N L H N BR YL LO HI N RD RD YL RD BK 87 65 4 3 2 1 5.0KW 1 2 3 4 5 6 7 8 3.0KW 1 2 3 4 5 6 7 8 8 7 65 4 3 2 1 2.0KW 6543 2 1 BL RD BK WH YL/GR 1.
PT AC-S VX0 1C-EN 47 Wiring Dia gram Figur e 31 . 265V Wiring diagr am (07 models) GR OR YL OR BK HI L N L H N BR YL LO HI N RD RD YL RD BK 1 2 3 4 5 6 7 8 3.
48 PT AC-S VX01C-EN Wiring Dia gram Figure 32. 265V Wiring diagram (09, 12, 15) GR OR YL OR BK HI L N L H N BR YL LO HI N RD RD YL RD BK 87 65 4 3 2 1 5.0KW 1 2 3 4 5 6 7 8 3.0KW 1 2 3 4 5 6 7 8 8 7 65 4 3 2 1 2.0KW 6543 2 1 BL RD BK WH YL/GR 1.0KW 2.
PT AC-S VX0 1C-EN 49 Wiring Dia gram Figur e 33. Energ y manage ment syst em Figure 3 4. 3rd par ty class 2 ther mostat wir ing Figur e 35. Remote display wir in g R W YG H G L O VT EN RW Y G H G L O .
50 PT AC-S VX01C-EN F ull 1st Y ear W ar ranty T rane will repair or replace any par t whic h proves to be defective due to workmanship or material s, free of c harge.
.
Literature Orde r Number PT AC-SVX0 1C-EN Date 09/06 Supersedes PT AC-SVX0 1B-EN Stoc king Location W ebb/Maso n The manufacturer has a policy of continuous product and product data improvement and reserves the right to c hange design and specification s without notice.
デバイスTrane PTAC-SVX01C-ENの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Trane PTAC-SVX01C-ENをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTrane PTAC-SVX01C-ENの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Trane PTAC-SVX01C-ENの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Trane PTAC-SVX01C-ENで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Trane PTAC-SVX01C-ENを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTrane PTAC-SVX01C-ENの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Trane PTAC-SVX01C-ENに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTrane PTAC-SVX01C-ENデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。