June 2008 SS-S VX09A -EN Installation Oper ation Maint enance Remot e Split S yst em Units Air Cooled Condensing Units and EVP Chillers Models “V” and Later Design Sequence RA UC-C20 RA UC-C40 RA .
© 20 08 T rane All righ ts reserved SS-SVX09A-EN W ar nings, Cautions and Notices W ar nings, Cautio ns and Notices. Note that warn ings, cautions and notices appear at appropriate interva ls throughout this manual. W arn ings are provide to alert instal ling contractors to potential haza rds that could result in per sonal inju ry or death.
T able of Cont ents SS-SVX09A-EN 3 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Model Number Des cription . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 SS-SVX09A-EN Outside Air Thermost at (5S57 Field Provided) . . . . . . . . . . . . . . . . . . . . . 61 Constant Volume Control (Honeywel l 973) . . . . . . . . . . . . . . . . . . . . . . . . 63 System Pre-Start Procedures . . . . . . . . . . . . .
SS-SVX09A-EN 5 Gener al Inf or mation Model Number Descr iption All T rane products are iden tified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeri c identification code i s provided below.
6 SS-SVX09A-EN Gener al Infor mation Ev apor ator Nameplat e (EVP Chiller Applications Only) The nameplate is lo cated on the same side of the refrigerant connections near the top. T o view the nameplate, remove the tape over the area and spr ead the insulation.
SS-SVX09A-EN 7 Installation Unit Inspection As soon as th e unit ar rives at the job site [ ] V e rify that the nameplate data matc hes the data on th e sales orde r and bill of lading (including electrical data). [ ] V erify that the power supply c omplies with the unit nameplate spec ifications.
8 SS-SVX09A-EN Installation NO TICE T o pr even t inter nal c hiller damage due t o fr eezing, do not install the BPHE c hiller outdoors without adequate fr eeze prot ection. Allow adequate clearance for wate r and refrigerant piping con nections, space to perform service procedures, i.
SS-SVX09A-EN 9 Installation Figure 2. T ypical Installation Clearances f or Single, Multiple or Pit Appl ications.
10 SS-SVX09A-EN Installation Figur e 3. RAU C-C20 Unit Dimensional Data & Recommended Clear ances.
SS-SVX09A-EN 11 Installation Figur e 4. RAU C-C25 Unit Dimensional Data & Recommended Clear ances.
12 SS-SVX09A-EN Installation Figur e 5. RAU C-C30 Unit Dimensional Data & Recommended Clear ances.
SS-SVX09A-EN 13 Installation Figur e 6. RAU C-C40 Unit Dimensional Data & Recommended Clear ances.
14 SS-SVX09A-EN Installation Figur e 7 . RA UC-C50 Unit Dimensional D ata & Recommended Clearances.
SS-SVX09A-EN 15 Installation Figur e 8. RAU C-C60 Unit Dimensional Data & Recommended Clear ances.
16 SS-SVX09A-EN Installation Note: All water connections are V ictaulic. Figure 9. BPHE 20 Ev aporator Chiller Dimensio ns Evaporator mounting brakets and insulation are provided with ChillerBPHE Accessory for field installation - Field provided vinyl tape is required to seal insulation edges after installation .
SS-SVX09A-EN 17 Installation Note: All water connections are V ictaulic. Figure 1 0. BPHE 25 Evapor ator Chiller Dimens ions 7.994 8.084 17.670 6.440 3.331 2.431 23.432 1.130 ID 2.431 2.261 17.720 2.261 3.451 SUCTION LIQUID ENTERING WATE R LEA VING WATE R 2X Ø2.
18 SS-SVX09A-EN Installation Note: All water connections are V ictaulic. Figure 1 1 . BPHE 30 Evapor ator Chiller Dimens ions 17.670 2.431 3.331 23.432 10.
SS-SVX09A-EN 19 Installation Note: All water connections are V ictaulic. Figure 12. BPHE 40 Evapor ator Chiller Dimens ions 3.960 23.780 2.551 30.292 13.533 2.517 2.517 8.500 6.767 6.767 13.533 30.292 2.826 4.235 23.230 1.380 ID X 2 7.720 9.096 SUCTION CIR #1 LIQUID CIR #1 SUCTION CIR #2 LIQUID CIR #2 1.
20 SS-SVX09A-EN Installation Note: All water connections are V ictaulic. Figure 13. BPHE 50 Evapor ator Chiller Dimens ions 3.960 23.780 2.551 30.292 13.533 2.517 2.517 8.500 6.766 6.767 13.533 30.292 2.827 4.235 23.230 1.380 ID X 2 8.872 9.096 SUCTION CIR #1 LIQUID CIR #1 SUCTION CIR #2 LIQUID CIR #2 2.
SS-SVX09A-EN 21 Installation Note: All water connections are V ictaulic. Figure 14. BPHE 60 Evapor ator Chiller Dimens ions 3.960 23.780 2.551 30.292 13.533 2.517 2.517 8.500 6.766 6.767 13.533 30.292 2.826 4.235 23.230 1.380 ID X 2 14.858 SUCTION CIR #1 LIQUID CIR #1 SUCTION CIR #2 LIQUID CIR #2 2.
22 SS-SVX09A-EN Installation T able 1 . T ypical Unit W eig hts & P oint Loading D ata Unit Size Operating Weight Unit Weight on Iso lator @ Mounting Location L o c a t i o n 1 23456 AL CU AL CU A.
SS-SVX09A-EN 23 Installation Rigging WA R N I N G Heavy Objects! Do not use cables (c hains or slings) ex cept as sh o wn. Each of the cables (chai ns or slings) used to lif t the unit must be capable of suppor ting the entir e weight of the unit.
24 SS-SVX09A-EN Installation Unit Isolation T o minimize un it sound and vibratio n transmission, one of the f ollowing installation met hods should be used: 1 . Install the unit directly on an isolated (detac h e d) concrete pad or on isolated concrete fo otings located at eac h unit load point.
SS-SVX09A-EN 25 Installation Spr ing Isolat ors Install the spring isolat ors at eac h unit mounti ng (load) point using the follow ing procedure: 1 . Elevate the unit (one side at a time) to a llow access to the base rail mounting holes. WA R N I N G Heavy Objects! Use solid type bloc ks, i.
26 SS-SVX09A-EN Installation T able 4. T ypical Spr ing Isolator Selection & Location Shipping F ast eners Compr essor Shipping Har dwar e Figure 16 illustrates the location of eac h tiedown bolt and rubber iso lator bolt for the compressor assembly in eac h circuit.
SS-SVX09A-EN 27 Installation Gener al Unit Requirements The c hec klist listed below is a su mmary of the s teps required to successfully inst al l a commercial air cooled condenser . This c hec klist is intended to acquaint the installing personnel with what is required in the installation process.
28 SS-SVX09A-EN Installation WA R N I N G Hazard of Explosion! Never use an open flame t o detect g as leaks. Ex plosive conditions ma y occur . Use a leak test solution or other appr oved methods for leak test ing.
SS-SVX09A-EN 29 Installation WA R N I N G Gr ound Wir e! All field-installed wir ing must be complet ed by qualified personnel. All field -installed wir ing must comply wi th NEC and applicable local codes. F ailur e to f ollow th is instr uction could r esult in death or ser ious injur ies.
30 SS-SVX09A-EN Installation WA R N I N G Gr ound Wir e! All field-installed wir ing must be complet ed by qualified personnel. All field -installed wir ing must comply wi th NEC and applicable local codes. F ailur e to f ollow th is instr uction could r esult in death or ser ious injur ies.
SS-SVX09A-EN 31 Installation Low V oltag e Wir ing (AC & DC) WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing. F ollo w proper lock out/ tagout pr ocedur es to ensur e the po wer can not be inadver tently ener gized.
32 SS-SVX09A-EN Installation Refer to Ta b l e 5 for filter/filter dr ier recommendations. Liquid Line Moist ure In dicator Sight Glass T o ai d in troubleshootin g, install a moisture indicato r sight glass in the liquid lin e near the evaporator , down stre am of the so lenoid valve prior to any branc h takeoffs to the expansion valve.
SS-SVX09A-EN 33 Installation Split Syst em Component Number Definitions (1)Interconnecting Suction Line T ubing (2)Suction Line Filter (3)Shutoff V alves - Manual ball valves (4)Interconnecti ng Liquid Line T ubi ng.
34 SS-SVX09A-EN Installation Refr ig erant Piping Refrigerant piping mu st be properly sized and a p plied. These two factor s have a very significant effect on both system pe rformance and reliability . NO TICE Use T ype “L ” refr ig erant gr ade co pper tubing only .
SS-SVX09A-EN 35 Installation Liquid Line Piping Liquid line siz es are based on their abil ity to provid e a minimum of 5 degrees F (2.7ºC) of sub- cooling at the expansion valve throughout the unit’ s operating system. Increasing the liqui d line size does not increase the availab le sub-cooling.
36 SS-SVX09A-EN Installation Ev apor ator Piping 1 . Install the TXV directly to the unit liquid connectio n. 2. Locate the TXV bu lb midway be tween the 90 degrees bends on top of th e suction line as illustrated in Figure 19 and Figure 20 .
SS-SVX09A-EN 37 Installation Hot Gas Bypass for Commer cial Comf ort-Cooling Applications Hot gas bypass is not recommended for use on RA UC units. Frostat™ is th e preferred method of protecting the evaporator from fr eez e-up. It turns off compressor s wh en the coil frosting is sensed.
38 SS-SVX09A-EN Installation Brazing Pr ocedur es WA R N I N G Hazard of Explosion and Deadly Gases! Never solder , braze or w eld on r efr igerant li nes or an y unit comp on ents th at ar e abov e atmospher ic pressur e or wher e refr ig erant may be present.
SS-SVX09A-EN 39 Installation Leak T esting Pr ocedur e WA R N I N G Hazard of Explosion! Use only dry nitrog en with a pressur e r egulato r for pr essur izing unit. Do not use acetylene, o xyg en or compressed air or mixt ures contai ning them for pr essur e testing.
40 SS-SVX09A-EN Installation 7 . If a leak i s located, use proper pr ocedures to remove the ref rigerant/nitrog en mixture, break the connection and remake as a new joint. R etest for leaks af ter making repairs. 8. Open the liquid line service valve an d the compressor disc harge service valve.
SS-SVX09A-EN 41 Installation Note: Factor to con vert “F eet of W ater” to “Lbs. pe r Sq . Inc h” (PSI): 2.3 F eet of W ater = 1 PSI Fi gu re 2 1.
42 SS-SVX09A-EN Installation Air V e nts V en ts must be installed at hig h points in the piping system to fa cilitate air purgin g during the filling process. W at er Pr essur e Gaug es Install pressure gauge(s) to monit or the entering a nd le aving c hilled w ater pressure.
SS-SVX09A-EN 43 Installation NO TICE F ailure to use ther mal paste could r esult in err atic temperatur e sensing resulting in equipment damage. Fr eez estat A Bulb-well (located in side the remote panel) must be installe d in the leaving water piping as close to the c hiller barrel as possible.
44 SS-SVX09A-EN Installation NO TICE F ailure to use ther mal paste could r esult in err atic temperatur e sensing resulting in equipment damage. Final W ater Piping Connections 1 . All water piping to the system should be fl ushed thoroughly be fore making the final connections .
SS-SVX09A-EN 45 Installation 3. Install the drain plug, (if no drain is used ) or ensure the drain shutoff valve is closed. 4. While filling the c hiller system with sol ution, vent the air from the system at the highes t points.
46 SS-SVX09A-EN Installation Main Unit P ow er Wir ing WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing. F ollo w proper lock out/ tagout pr ocedur es to ensur e the po wer can not be inadver tently ener gized.
SS-SVX09A-EN 47 Installation P o wer Wir e Sizing and Pr ot ection Device Equations T o correctly size the main power wiring for the unit, use the ap propriate calcul ation(s) listed below.
48 SS-SVX09A-EN Installation Calculation #2 Disconnect Switc h Sizing (DSS) DSS = 1 .15 X (L OAD 1 + L O AD 2 + L O AD 4) T abl e 8. Electr ical Se rvice Sizing D ata Model Electrical Charac. Unit Characteristic s Condenser Fan Motor Compressor Motor Allow- able Voltage Range Min.
SS-SVX09A-EN 49 Installation Field Installed Contr ol Wir ing WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing. F ollo w proper lock out/ tagout pr ocedur es to ensur e the po wer can not be inadver tently ener gized.
50 SS-SVX09A-EN Installation liquid line solenoid valve(s). Supply F an Int er lock (Contr ol options utilizing an Air Handler) The normally open evaporator fan interloc k auxili ary contacts and the .
SS-SVX09A-EN 51 Installation Contr ols using 24 V AC WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing. F ollo w proper lock out/ tagout pr ocedur es to ensur e the po wer can not be inadver tently ener gized.
52 SS-SVX09A-EN Installation These com ponents may incl ude: Field installed Disc harge Duct S ensor (6RT1 CV units); Field installed Return Duct S ensor (6RT6 CV units); Field installed Disc harge Ai r Sensor (6R T3 V A V units); Field installed Chilled W ater Sensor (6R T2 EVP units); 1 .
SS-SVX09A-EN 53 Installation No S ystem Contr ol T emperat ur e Control P aramet ers Eac h unit ordered wi th the “No Controls” opti on, requires a field pr ovided and field wired temperature controller . Single re frigerant circuit units require a 2-step control device, and dual refrigerant circuit units requ ire a 4-step control device.
54 SS-SVX09A-EN Installation Refer to Wiring Notes on p. 55 Figur e 25. F ield Connection Diagr am or RA UC -C20 - C60 “ No S ystem Controls” Applications.
SS-SVX09A-EN 55 Installation Field Connection Diagram Not es fo r all S yst em Contr ol Options.
56 SS-SVX09A-EN Installation V ar iable Air V olume Control (Hone yw ell W71 00A) In a variable air v olume system, the desired sp ace temperature is maintained by varying the amount of condi tioned air being delivered to the spa ce.
SS-SVX09A-EN 57 Installation Suction Line Ther mostat Eac h unit ordered with variable air vo lume contro ls (digit 9 in the model number) is ship ped with a suction line thermostat (6S63) that must be field installe d. Locate the thermo stat close to the e xpansion valve bu lb on a slightly flattened portion of the suction line.
58 SS-SVX09A-EN Installation Refer to Wiring Notes on Pa ge p. 55 EVP Chiller Contr ol Eac h unit orde red for EVP Chiller applications ( digit 9 in the model number), is shipped wi th the following c.
SS-SVX09A-EN 59 Installation connection diagra m illustrated in Figure 29 for the intercon necting po ints between the remote panel and the unit’ s control panel. WA R N I N G Gr ound Wir e! All field-installed wir ing must be complet ed by qualified personnel.
60 SS-SVX09A-EN Installation Chilled W ater T emper atur e Sensor (Honeyw ell 6R T2) With the sensor installed in its proper location within the c h illed w ater piping ( Figure 18 ), c onnect shielded cable (Belden 8760 or equivalent) from th e sensor leads to the le ads inside the remote panel.
SS-SVX09A-EN 61 Installation Outside Air Ther mostat (5S57 Field Pr ovided) The setpoint for the outside air thermostat is based upon the wo rking ambient selected when the unit w as ordered. A Zero (“0”) in the 1 1th digi t of the model number ind icates the system is designed for stan dard ambient op eration of 40ºF and above.
62 SS-SVX09A-EN Installation Refer to Wiring Notes on Pa ge p. 55 Figur e 29. Field Connection Diagr am for RA UC-C20 - 60 “EVP Chiller” Applicatio ns.
SS-SVX09A-EN 63 Installation Constant V olume Contr ol (Honeyw ell 973) The descriptions of the following basic input devi ces used with the Honeywell 973 Master Energy Controller (MEC) are to acquaint the operator with their func ti on as they interface with the controller .
64 SS-SVX09A-EN Installation Figure 30. T7067 Electr on ic Zone The r mostat & Q667 Switching Subbase Figure 31 . Q667 S witching Subbase & T7 067 Ther mostat T er minal Identification.
SS-SVX09A-EN 65 Installation Discha rg e Air Sensor (Honeyw ell 6R T1) A disc harge air sensor ships with eac h un it when the constant volume control op tion is ordered. The sensor should be installed in a turbulent free area of the disc harge air duct at a location that will provide accurate su pply air se nsing.
66 SS-SVX09A-EN Installation Refer to Wiring Notes on Pa ge p. 55 Figur e 32. Field Connection Diagr am for RA UC- C20 thr ough 60 “Constant volume ” Applications.
SS-SVX09A-EN 67 Installation Figur e 33. 6RT1 Disc harg e Air Sensor Assembly.
68 SS-SVX09A-EN S yst em Pr e-Star t Pr ocedur es Use the c hec klist provided below in conjunctio n with the “General Unit Requirement” c hec klist” to ensure that the unit is properly installed and read y for operation. Be sure to complete all of the procedures descri bed in this section befo re starting the unit for the fir st time.
SS-SVX09A-EN 69 Sy stem Pr e-Star t Procedur es before filling with water to disp lace any air in the bar rel. Close vent po rts or repl ace the vent plug after purging or filling . [ ] Once the system has been fill ed, inspect the entire c hilled w ate r piping system fo r leaks.
70 SS-SVX09A-EN S ystem Pr e-Star t Pro cedures Note: It is unlawful to release refr igerant into the atmo sphere. When service procedures requir e working with refrigerants, the service tec hnician m ust comply with all Federal, Sta te, and local laws.
SS-SVX09A-EN 71 Sy stem Pr e-Star t Procedur es Dischar g e Air Controller Chec k out (Hone ywell W71 00A) Note: The following chec ko ut procedure must be performe d in its entirety and in the sequence given. WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing.
72 SS-SVX09A-EN S ystem Pr e-Star t Pro cedures 5. Install a jump er across the P and P1 terminal s (remote setpoint inpu t), and an other jumper across terminals 6 and 7 (reset input) if reset is enabled. 6. Disconnect the wires fr om terminals T and T1 (disc harge air sensor).
SS-SVX09A-EN 73 Sy stem Pr e-Star t Procedur es In approximately 5 minut es; me asure the voltage across terminal s R (-) & W (+). The measured voltag e should drop to approximately 0.2 VDC. 20. T urn the control circ uit switc h 1S2, in the unit control panel, and the main po wer disconnect switc h to th e “ OFF” position.
74 SS-SVX09A-EN S ystem Pr e-Star t Pro cedures Dischar g e Air Sensor Check o ut (Hone ywell Sensor) WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing. F ollo w proper lock out/ tagout pr ocedur es to ensur e the po wer can not be inadver tently ener gized.
SS-SVX09A-EN 75 Sy stem Pr e-Star t Procedur es EVP Chiller Contr ol Check out (Hone ywell W71 0 0G) Note: The following chec ko ut procedure must be performe d in its entirety and in the sequence given. WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing.
76 SS-SVX09A-EN S ystem Pr e-Star t Pro cedures 1 0. “Close” the main power disconnec t switc h an d turn the control ci rcuit switc h 1S2, in the unit control panel, “ ON” . WA R N I N G High V oltage is Pr esent at T er min al Block 1TB1 or Unit Disconnect Swi t ch 1 S1.
SS-SVX09A-EN 77 Sy stem Pr e-Star t Procedur es Chilled W ater Sensor Chec k out (Honeyw ell Sensor) WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing. F ollo w proper lock out/ tagout pr ocedur es to ensur e the po wer can not be inadver tently ener gized.
78 SS-SVX09A-EN S ystem Pr e-Star t Pro cedures Mast er Energ y Contr ol Check out WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing. F ollo w proper lock out/ tagout pr ocedur es to ensur e the po wer can not be inadver tently ener gized.
SS-SVX09A-EN 79 Sy stem Pr e-Star t Procedur es 1 0. M easure the voltage ag ain across T e rminals R (-) and W (+). The measured v oltage should now be approximately 0.2 VDC. 1 1 . T urn the control circuit switc h 1S2, in th e unit control pane l, to the “ OFF” position .
80 SS-SVX09A-EN S ystem Pr e-Star t Pro cedures Dischar g e Air Sensor Check out (Hone yw ell 6RT1) WA R N I N G Hazardous V oltag e! Disconnect all electr ic po wer , including r emote d isconnects befor e servicing. F ollo w proper lock out/ tagout pr ocedur es to ensur e the po wer can not be inadver tently ener gized.
SS-SVX09A-EN 81 Sy stem Pr e-Star t Procedur es Figur e 39. 6RT1 Disc harg e Duct Sen sor “T emper atur e vs Res istance ” Curv e Figure 40. W97 3 Mast er En erg y Controller (M EC) 1600 1800 2000.
82 SS-SVX09A-EN S ystem Pr e-Star t Pro cedures V oltage Imbalance Excessive thr ee phase voltage imbalance between phases will cause moto r s to overheat and eventually fail.
SS-SVX09A-EN 83 S yst em Star t-Up Sequence of Oper ation V A V W71 0 0A Disc harg e Air Controller (7U1 1) The disc harge air controller used in V ariable Air V olume applications is a Honeywell W71 0 0A. This microprocessor contro ller is designed to maintain an avera ge disc harge air (D/A) temperatur e by: 1 .
84 SS-SVX09A-EN Syst em Star t-Up Chilled W a ter T emper atur e Control ler (6U1 1) The c hill ed water tem perature controller used with EVP c hiller ap plications is a Honeywell W71 0 0G.
SS-SVX09A-EN 85 Syst em Star t-Up a. Could cause seri ous compressor damage due to ref rigerant floodbac k. b. Remo ves working surface from the evapor ator nor mally used for heat transfer . Systems operating with superheat in excess of 16 degrees: c.
86 SS-SVX09A-EN Syst em Star t-Up Low Ambien t Dampers Low Ambient Dampers are available as a factory inst alled option or can be field-installed. Dampers are used to extend the operation of these units fr om the standard operatio nal temperatures to a minimum of 0ºF without hot g as bypass or 1 0ºF with hot gas bypass.
SS-SVX09A-EN 87 Syst em Star t-Up Low Ambien t Ther mostats In addition to the low ambient dampers on 25, 30 , 50 & 60 T on units, a low am bient thermostat is installed to furt her restrict the airflow across the condenser by cycling the 2B3 co ndenser fan on 25 & 30 T on units plus 2B6 on 50 & 60 T on un its.
88 SS-SVX09A-EN Syst em Star t-Up EVP Chiller Applications Start th e c hilled water circulati ng pump by closing the field pro vided pump disconnect switc h and turn the pump control circuit switc h 5S1 “ On ” . Chec k the flow device to ensure it opens and close properly .
SS-SVX09A-EN 89 Syst em Star t-Up “ Air Ov er” Ev apor ator Application V erify ing Proper Supply F an Rotation 1 . Ensure that the “System” selection switc h at th e remote panel is in the “ Of f” po sition and the “Fan ” selection switc h for the ap prop riate controls application is in th e “ Auto ” position.
90 SS-SVX09A-EN Syst em Star t-Up 3. Plot this value onto the appr opriate component p ressure drop curve that shippe d with the Air Handling eq uipment. Use the data to a ssist in calculating a new fan dri ve if the CFM is not at design specification s.
SS-SVX09A-EN 91 Syst em Star t-Up WA R N I N G Live Electr ical Components! Dur ing instal lation, testing, servicing and tr oublesho oting of this product, it may be necessary to w or k with live electr ical comp onents.
92 SS-SVX09A-EN Syst em Star t-Up 1 1 . After the compressors and co ndenser fans for th e operating circuit have been operati ng for approximately 30 minutes, obse rve the operatin g pressures. Use the appropriate pressure curve in Figure 47 to determine the proper operating pr essures.
SS-SVX09A-EN 93 Syst em Star t-Up 1 4. T urn the 1 15-v olt control circuit switc h 1S2 to the “ OFF” p osition and open the field pro vided or optional factory mou nted disconnect switc h. 15. Af ter shut ting the system o f f, c h ec k the compresso r oi l appearance.
94 SS-SVX09A-EN Syst em Star t-Up Unit Size With HGBP No HGBP With HGBP No HGBP 20-60 45° 40° 10° 0° Note: Mini mum starting amb ients in degrees F and is based on th e unit oper ating at minimum step of unloading and 5 mph wind across conden ser .
SS-SVX09A-EN 95 Syst em Star t-Up Figur e 45. T ypical Compressor Locations Figur e 46. T ypical Compre ss or T er minal Bloc k.
96 SS-SVX09A-EN Syst em Star t-Up Figure 47 . 20 T on Pressure Curv e.
SS-SVX09A-EN 97 Syst em Star t-Up Figure 48. 25 T on Pressur e Curve.
98 SS-SVX09A-EN Syst em Star t-Up Figur e 49. 30T on Pressur e Curve.
SS-SVX09A-EN 99 Syst em Star t-Up Figure 50. 40 T on Pressur e Curve per Circuit.
10 0 SS-SVX09A-EN Syst em Star t-Up Figure 51 . 50 T on Pressur e Curve per Circuit.
SS-SVX09A-EN 101 Syst em Star t-Up Figure 52. 60 T on Pressur e Curve per Circuit.
10 2 SS-SVX09A-EN Syst em Star t-Up Final S ystem Set up After co mpleting the Pre-star t and Star t-up procedur es outlined in the previous sections, perform these final c hec ks before leaving the unit: [ ] T urn the 1 15 v olt control circuit switc h 1S2 “ Of f” .
SS-SVX09A-EN 10 3 Syst em Star t-Up T able 1 8. Sample Maintenance Log Date Current Ambient Temp. (F) Refrigerant Circuit #1 Refrigerant Circuit #2 Compr. Oil level Suct. Press. (Psig) Disch. Press. (Psig) Liquid Press. (Psig) Super- heat (F) Subcool (f) Compr.
10 4 SS-SVX09A-EN Service & Maint enance Compr essor Operational Sounds Because of the scroll compressor d esign, it emits a higher frequency tone (sound ) than a reciprocating compressor . It is designed to accommo date liquids, both o il and refrigerant, without causing compressor damage.
SS-SVX09A-EN 10 5 Service & Maint enance T able 1 9. Compressor Circuit Br eak er Data Voltage Comp RLA LRA Must Must Tons Hold Trip 200 9 41.4 269.0 50.4 58.0 230 9 41.4 251.0 50.4 58.0 460 9 18.1 117.0 22.0 25.3 575 9 14.4 94.0 17.5 20.2 380/415 9 17.
10 6 SS-SVX09A-EN Service & Maint enance Fu se Replacement Data T able 20 lists the re placement fuses for the control circuit, comp ress or s, and condenser fans. Monthly Maint enance Air Handling Equipment Before completing the following c hec ks, turn the system control ci rcuit switc h 1S2 and 5S1 to the "Off" position.
SS-SVX09A-EN 10 7 Service & Maint enance [ ] V erify that all wire te rminal connections are tight. [ ] Generally inspect th e unit for unusual condit ions (e.g., loose access panels , leaking piping connections, etc.) [ ] Make sure that all retainin g screws are reinstalled in the un it access panels once these c hec ks are complete.
10 8 SS-SVX09A-EN Service & Maint enance WA R N I N G Hazardous Pr essures! Coils contain refr ig erant under pr essur e. When cleaning coils, main tain coil clea ning solution temper ature under 150°F t o av oid excessiv e pressur e in the coil.
SS-SVX09A-EN 10 9 W ARRANT Y AND LIABILIT Y CLA USE COMMERCIA L EQUIPMENT RA TED 20 T ONS AND LARGER AND RELA TED A CCESSORIES PRODUCTS CO VERED - This war ranty* is extended by T rane Inc. and a pplie s only to commercial equipment rated 20 T ons and la rger and re late d accessories.
11 0 SS-SVX09A-EN Symbols “EVP” Chiller Units 29 ”No Controls” Units 29 Numerics 115 Volt Control Wiring (All Units) 29 A AC Conductors 51 Access Valves (Ports) 32 Air Handling Equipmen t 106 .
SS-SVX09A-EN 111 Index Supplied) 31 Suction Line Inter connecting Tubing 34 Suction Line Ther mostat 57 Supply Fan Interlock 50 T T7067 Thermostat Terminal Identification 64 Temperatu re Control Param.
www .trane.com For more information, contact your local T rane office or e-mail us at comfort@trane.com Literature Order Number SS-S VX09A-EN Date June 2008 Supersedes RAUC-IOM-1 4 June 2007 T rane has a policy of continuous product and pro duct data improvement and reserves the right to c hange design and specific ations without notice.
デバイスTrane RAUC-C50の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Trane RAUC-C50をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTrane RAUC-C50の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Trane RAUC-C50の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Trane RAUC-C50で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Trane RAUC-C50を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTrane RAUC-C50の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Trane RAUC-C50に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTrane RAUC-C50デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。