P ac k ag ed Cooling with Electr ic Heat Roof t op Units Pr ecedent ™ 3 - 1 0 T ons — 60 Hz R T -PR C0 05-EN March 2003.
R T -PRC0 05-EN © 2003 American Standard Inc. All rights reserved Intr oduction Precedent TM . . . The same T rane quality ... with added f le xibility .
3 RT -PRC005-EN Intr oduction F eatur es and Benefits Application Considerations Selection Pr ocedure Model Number Description Gener al Data P erfor mance D ata Cooling Performance Fan Performance Hea.
4 RT -PRC005-EN F eatures and Benef its Unit Cabinet The compact cabinet with rounded corners tak es up less room and is less costly to ship. The beveled and ribbed top is not only aesthetically pleasing, it is designed to prevent w ater from pooling.
5 RT -PRC0 05-EN F eatures and Benef its Standardized Components • Components are placed in the same location on all P recedent™ units. Familiariz e your self with one Precedent and you are familiar with every Precedent.
6 RT -PRC0 05-EN F eatures and Benef its F act ory -installed Options Economizer Equipped with either dry bulb, reference or comparative enthalpy sensing, this feature provides free cooling as the outdoor temperature and/or humidity decreases. Economizers, correctly installed, of fer a valuable energy savings.
7 RT -PRC0 05-EN F eatures and Benef its VariTrac ™ Va r i Tr a c When T rane’s c hangeover V A V System for light commercial applications is coupled with P recedent, it provides the latest in tec hnological advances for comfor t management systems and can allow thermostat control in every zone served by V ariT rac.
8 RT -PRC0 05-EN Application of this product should be within the cataloged airflow and cooling considerations. Lo w Ambient Cooling The Precedent™ line features, with ReliaT el™ microprocessor controls, low ambient cooling down to 0F . With electromec hanical controls, Precedent features low ambient cooling to 40F .
9 RT -PRC0 05-EN Cooling Capacity Step 1 Calculate the building’s total and sensible cooling loads at design conditions. Use the T rane calculation methods or any other standard accepted method.
10 RT -PRC0 05-EN Model Number Description DIGIT 1 - Unit Function T = DX Cooling DIGIT 2 - Efficiency S = Standard Efficiency H = High Efficiency DIGIT 3 - Airflow C = Conv er tible DIGITS 4,5,6 - No.
11 RT -PRC0 05-EN General Data (3 - 5 T on) Standard Ef f icienc y T able GD - 1 — General D ata 3 T on Conver tible Units 4 T on Conver tible Units 5 T on Conve rtible Units TSC036A1, A3, A4, AW TS.
12 RT -PRC0 05-EN General Data (6 - 1 0 T on) Standard Ef f icienc y T able GD - 2 — General D ata 6 To n 7 ½ To n 8 ½ To n 1 0 To n Conver tible Units Conver tible Units Conver tible Units Conver.
13 RT -PRC0 05-EN General Data (3 - 5 T on) High Ef f icienc y T able GD - 3 — General D ata 3 To n 4 To n 5 T o n Convertible Units Convertible Units Convertible Units THC036A1,A3,A4,AW THC048A1,A3,A4,AW TH C 060A1 THC060A3,A4,AW Cooling Performance 1 Gros s Coo ling Capa city 38,000 49,800 62,100 62,400 SEER / EER 2 12.
14 RT -PRC0 05-EN General Data (6 - 1 0 T on) High Ef f icienc y T able GD - 4 — General D ata 6 To n 7 ½ To n 8 ½ To n 1 0 To n Conver tible Units Convertible Units Conver tible Units Conver tible Units THC072A3, A4, AW THC092A3, A4, AW THC102A3, A4.
15 RT -PRC0 05-EN P erformance Data (3, 4 T on) Standard Ef ficiency T able PD-2 — Gross Cooling Capacities (MBH) 4 T on Single Phase TSC048A1 Ambient T emperature (F) 85 95 1 05 1 15 Enter.
16 RT -PRC0 05-EN (4, 5 T on) Standard Ef ficiency P erformance Data T able PD-3 — Gross Cooling Capacities (MBH) 4 T on Three Phase TSC048A3, A4, A W Ambient T emperature (F) 85 95 10 5 1 15 Enter.
17 RT -PRC0 05-EN P erformance Data (6, 7½ T on) Standard Ef ficiency T able PD-5 — Gross Cooling Capacities (MBH) 6 T on Three Phase TSC072A3, A4, A W, AK Ambient T emperature (F) 85 95 10 5 1 15 Enter.
18 RT -PRC0 05-EN P erformance Data (7½, 8½ T on) Standard Ef ficiency T able PD-8 — Gross Cooling Capacities (MBH) 8 ½ T on Three Phase TSC1 02A3, A4, A W , AK Ambient T emperature (F) 85 95 10 5 1 15 Enter.
19 RT -PRC0 05-EN P erformance Data (1 0 T on) Standard Ef ficiency T able PD-9 — Gross Cooling Capacities (MBH) 1 0 T on Thr ee Phase TSC120A3, A4, A W, AK Ambient T emperature (F) 85 95 10 5 1 15 Enter.
20 RT -PRC0 05-EN P erformance Data (3, 4 T on) High Ef f icienc y T able PD-1 1 — Gross Cooling Capacities (MBH) 4 T on THC048A1, A3, A4, A W Ambient T emperature (F) 85 95 10 5 1 15 Enter.
21 RT -PRC0 05-EN P erformance Data (5 T on) High Ef f icienc y T able PD-12 — Gross Cooling Capacities (MBH) 5 T on Single Phase THC060A1 Ambient T emperature (F) 85 95 10 5 1 15 Enter.
22 RT -PRC0 05-EN P erformance Data (5 T on) High Ef f icienc y T able PD-14 — Gross Cooling Capacities (MBH) 5T on THC060A3, A4, A W – Dehumidification Option Ambient T emperature (F) 85 95 1 05 1 15 Enter.
23 RT -PRC0 05-EN (6, 7½ T on) High Ef f icienc y P erformance Data T able PD-15 — Gross Cooling Capacities (MBH) 6T on Thr ee Phase THC072A3, A4, A W Ambient T emperature (F) 85 95 10 5 1 15 Enter.
24 RT -PRC0 05-EN P erformance Data (8½, 1 0 T on) High Ef f icienc y T able PD-1 7 — Gr oss Cooling Capacities (MBH) 8 ½ T on Three Phase THC1 02A3, A4, A W Ambient T emperature (F) 85 95 1 05 1 15 Enter.
25 RT -PRC0 05-EN P erformance Data (1 0 T on) High Ef f icienc y T able PD-19 — Gross Cooling Capacities (MBH) 1 0T on THC120A3, A4, A W – Dehumidification Option Ambient T emperature (F) 85 95 10 5 1 15 Enter.
26 RT -PRC0 05-EN P erf ormance Data (3, 4, 5 T on) Standard Ef f icienc y T able PD-20 — Dir ect Drive Ev aporator F an Perfo rmance 3, 4 and 5 T on TSC036A, TSC048A, TSC060A External Static Pressure (Inc hes of W ater) & Motor Power (Bhp) 1 Standard Motor Ov er si ze d Mo t or Unit High Speed Low Speed High Speed Low Speed T on s Model No.
27 RT -PRC0 05-EN (3 T on) Standard Ef f icienc y T able PD-21 — Belt Dr ive Ev aporator F an Perf or mance — 3 T on — TSC036A3,A4,A W — Downflo w Airflow External Static Pressure (Inc hes of W ater) .
28 RT -PRC0 05-EN (4 T on) Standard Ef f icienc y P erf ormance Data T able PD-23 — Belt Dr ive Ev aporator F an Perf ormance — 4 T on — TSC048A3,A4,A W — Do wnflow Airflow External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .
29 RT -PRC0 05-EN (5 T on) Standard Ef f icienc y P erformance Data T able PD-25 — Belt Dr ive Ev aporator F an Perfor mance — 5 T on — TSC060A3,A4,A W — Do wnflow Airflo w External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .
30 RT -PRC0 05-EN P erformance Data (6 T on) Standard Ef ficiency Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions.
31 RT -PRC0 05-EN (6 T on) Standard Ef f icienc y P erformance Data T able PD-29 — Belt Dr ive Evapora tor F an Perfor mance — 6-T on — TSC072,AK — Downflo w Airflo w External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .70 .80 .
32 RT -PRC0 05-EN (7½ T on) Standard Ef f icienc y P erf ormance Data T able PD-31 — Belt Dr ive Ev aporator F an P erfor mance — 7 ½ -T on — TSC090,092A3,A4,A W ,AK — Downflo w Airflo w External Static P ressure (Inc hes of Water) .1 0 .20 .
33 RT -PRC0 05-EN (8½ T on) Standard Ef f icienc y P erformance Data T able PD-33 — Belt Dr ive Ev aporator F an Perfor mance — 8 ½ -T on — TSC1 02A3,A4,A W , AK — Do wnflowAirflow External Static P ressure (Inc hes of Water) .1 0 .20 .30 .40 .
34 RT -PRC0 05-EN (1 0 T on) Standard Ef f icienc y P erf ormance Data T able PD-36 — Belt Dr ive Evaporat or F an P erformance — 1 0-T on — TSC120A3,A4,A W,AK — Hor izontal Airflow External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .
35 RT -PRC0 05-EN P erformance Data (3, 4, 5 T on) High Ef f icienc y T able PD-37 — Dir ect Drive Ev aporator F an Perfor mance — 3, 4, and 5 T on — THC036A, THC048A, THC060A External Static Pr.
36 RT -PRC0 05-EN P erf ormance Data (3 T on) High Ef f icienc y T able PD-38 — Belt Dr ive Ev aporator F an Perf or mance — 3 T on — THC036A3,A4,A W — Downflo w Airflow External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .70 .
37 RT -PRC0 05-EN P erformance Data (4 T on) High Ef f icienc y T able PD-40 — Belt Dr ive Ev aporator F an Perf ormance — 4 T on — THC048A3,A4,A W — Downflo w Airflow External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .70 .
38 RT -PRC0 05-EN P erf ormance Data (5 T on) High Ef f icienc y T able PD-42 — Belt Dr ive Evapor ator F an P erfor mance — 5 T on — THC060A3,A4,A W — Downflo w Airflow External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .70 .
39 RT -PRC0 05-EN T able PD-44 — Belt Dr ive Ev aporator F an Perf or mance — 5 T on — THC060A3,A4,A W — Hor izontal Airflow External Static Pressure (Inc hes of W ater) .
40 RT -PRC0 05-EN (6 T on) High Ef f icienc y P erformance Data T able PD-47 — Belt Dr ive Ev aporat or Fan Perf o r mance — 6 T on — THC072A3,A4,A W — Hor izontal Airflow External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .
41 RT -PRC0 05-EN (7½ T on) High Ef f iciency P erformance Data T able PD-48 — Belt Dr ive Evaporat or Fan P erformance — 7 ½ -T on — THC092A3,A4,A W — Do wnflo w Airflow External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .
42 RT -PRC0 05-EN (8½ T on) High Ef f icienc y P erf ormance Data T able PD-50 — Belt Dr ive Ev aporator F an P erformance — 8 ½ -T on — THC1 02A3,A4,A W — Downflo w Airflow External Static P ressure (Inc hes of Water) .1 0 .20 .30 .40 .50 .
43 RT -PRC0 05-EN (1 0 T on) High Ef f iciency P erformance Data T able PD-52 — Belt Dr ive Ev aporator F an Perf or mance — 1 0-T on — THC120A3,A4,A W — Do wnflow Airflow External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .
44 RT -PRC0 05-EN (1 0 T on) High Ef f iciency P erformance Data T able PD-54 — Belt Dr ive Evapor ator F an P erfor mance — 1 0-T on — THC120A3,A4,A W — Hor izontal Airflo w External Static Pressure (Inc hes of W ater) .1 0 .20 .30 .40 .50 .60 .
45 RT -PRC0 05-EN P erformance Data # Indicates both Standard and High Efficiency. T able PD-56— Standard Motor & Shea ve/Fan Speed (Rpm) U n i t 6 Tu r n s 5 Tu r n s 4 Tu r n s 3 Tu r n s 2 Tu r n s 1 Tu r n T ons Model No.
46 RT -PRC0 05-EN T able PD-61— Electric Heat er V oltag e Cor rection F actors (Applicable t o A uxiliary Heat Capacity) Nominal Distribution Capacity Voltage Voltage Multiplier 208 0.751 240 230 0.918 240 1 .00 0 380 380 1 .00 0 440 0.840 480 460 0.
47 RT -PRC0 05-EN P erformance Data NOTES: 1. Does not include indoor fan power or heat. 2. Heaters are rated at 240v, 380v, 480v. and 600v. For other than rated voltage, CAP = x rated cap. Rated Voltage Voltage 2 ( ) T able PD-62— A uxiliary Electr ic Heat Capacity Total 2 Stage1 Stage 2 Unit kW MBH No.
48 RT -PRC0 05-EN 3 Ton 4 Ton 5 Ton 1200 CFM 1600 CFM 1 2000 CFM Single Phase Three Phase Single Phase Three Phase Single Phase Three Phase kW Stages T#C036A1 T#C036A3,A4,AW T#C048A1 T#C048A3,A4,AW T#C060A1 T#C060A3,A4,AW TSC060AK 5.0 0 1 13.2 — 9. 9 — 7 .
49 RT -PRC0 05-EN Zone Controls ReliaT el ™ Contr olled Units Zone Sensors are the building occupant’s comfort control devices for Precedent™ units with the Micro control: Manual Changeov er — Heat, Cool or Off System Switc h. Fan Auto or Off S witc h.
50 RT -PRC0 05-EN Electrical Data T able ED-1 — Unit Wir ing — Standard Efficiency Optional Standard Indoor F an Motor Over size Indoor F an Motor Belt Drive Indoor Fan Motor 2 Unit Minimum Maximu.
51 RT -PRC0 05-EN T able ED-2 — Unit Wiring — High Efficiency Optional Standard Indoor Fan Motor Over size Indoor Fan Motor Belt Dri ve Indoor Fan Motor 2 Unit Minimum Maximum Fuse Minimum Maximum Fuse Minimum Maximum Fuse Unit Operating Circuit Size Or Maximum Circuit Size Or Maximum Circuit Siz e or Maximum T ons Model No.
52 RT -PRC0 05-EN Electrical Data (Standard Ef f icienc y) T able ED-3 — Unit Wiring With Electric Heat (Single P o int Connection) — 208/230 V olts — Standard Ef ficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No.
53 RT -PRC0 05-EN T able ED-4 — Unit Wir i ng With Electric Heat (Single P oint Connection) — Standar d Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No.
54 RT -PRC0 05-EN Electrical Data T able ED-5 — Unit Wiring With Electric Heat (Single P o int Connection) — 575 V olts — Standard Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No.
55 RT -PRC0 05-EN Electrical Data (Standard Ef f iciency) T able ED-5 — Unit Wiring With Electric Heat (Single P oint Connection) — Optional Belt Dr ive — Standard Efficiency Optional Belt Drive Indoor Motor To Use Heater Heater Control Max Fuse Size Orr Tons With Model No.
56 RT -PRC0 05-EN Electrical Data (High Ef f icienc y) T able ED-7 — Unit Wir ing With Electr ic Heat (Single P oint Connection) — 208/230 V olts — High Ef ficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No.
57 RT -PRC0 05-EN Electrical Data T able ED-8 — Unit Wir ing With Electric Heat (Single P oint Connection) — 460 V olts — High Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No.
58 RT -PRC0 05-EN Electrical Data T able ED-9 — Unit Wir ing With Electric Heat (Single P oint Connection) — 575 V olts — High Efficiency Standard Indoor Motor Oversize Indoor Motor To Use Heater Heater Control Max Fuse Size Or Max Fuse Size Or Tons With Model No.
59 RT -PRC0 05-EN Electrical Data (High Ef f icienc y) 460 Volts Three Phase BAYHTRR406A 6.0 1 12.1 1 5 3 THC036A4 BAYHTRR412A 12.0 2 21.1 25 BAYHTRR418A 17.4 2 29.3 30 BAYHTRR406A 6.0 1 12.1 1 5 4 THC048A4 BAYHTRR412A 12.0 2 21.1 25 BAYHTRR418A 17.4 2 29.
60 RT -PRC0 05-EN Electrical Data T able ED-1 1 — Electrical Char a cter istics — E v aporat or Fan Mot or — 60 Cycle — Standard and Ov ersized Standard Evaporator Fan Motor Oversized Evaporator Fan Motor Unit Amps Amps T ons Model No. No. V olts Phase HP FLA LRA No.
61 RT -PRC0 05-EN Electrical Data Compressor Motors Condenser Fan Motors Unit Amps 1 Amps Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA TSC036A1 1 208-230 1 3.1 3450 1 7 .2 104.0 1 1 .20 1 .5 2.5 3 TSC036A3 1 208-230 3 3.1 3450 1 1 .
62 RT -PRC0 05-EN T able ED-14 — Electr ical Characteristics — Compr essor Motor And Condenser Motor — 60 Cycle — High Efficiency Compressor Motors Condenser Fan Motors Unit Amps 1 Amps 1 Tons Model No. No. Volts Phase HP 2 RPM RLA LRA No. Phase HP FLA LRA THC036A1 1 208-230 1 2.
63 RT -PRC0 05-EN Jobsite Connections For specific wiring information, see the installation instructions. All wiring except power wires is low voltage. All customer supplied wiring to be copper and must conform to applicable electrical codes (such as NEC or CEC) and local electrical codes.
64 RT -PRC0 05-EN Dimensional Data All dimensions are in inc hes/millimeter s. 5 T ons High Efficiency 3 - 5 T ons Standard Efficiency 3 and 4 T ons High Efficiency (3-5 T ons).
65 RT -PRC0 05-EN Dimensional Data All dimensions are in inc hes/millimeter s. Horiz ontal Airflow Supply/Retur n Downflow Airflow Supply/Ret urn Through the Base Utilities Unit Clearance and Roof Ope.
66 RT -PRC0 05-EN Dimensional Data All dimensions are in inc hes. Downflow Duct Connections — Field Fabr icated (3-5 T ons) 37 1/8” 928 MM.
67 RT -PRC0 05-EN (6-1 0 T ons) Dimensional Data All dimensions are in inc hes. 6 T ons Standard and High Efficiency 7 ½ T ons Standard Efficiency 7 ½ T ons High Efficiency 8 ½ and 1 0 T ons Standa.
68 RT -PRC0 05-EN (6-1 0 T ons) Dimensional Data All dimensions are in inc hes. 6-1 0 T ons — Downflo w Airflow Supply and Return; Through the Base Utilities 6-1 0 T ons — Hor izontal Airflow Supp.
69 RT -PRC0 05-EN (6-1 0 T ons) Dimensional Data All dimensions are in inc hes. 6-1 0 T ons — Roof Curb ALL FLANGES 1 1/4” (31 MM) 6-1 0 T ons — Do wnflow Duct Connections — Field F abr icated.
70 RT -PRC0 05-EN (3-5 T ons Options/ A ccessories) Dimensional Data All dimensions are in inches. Economizer , Manual or Motor ized Fr esh Air Damper See Page 65 for Through the Base Utilities Inform.
71 RT -PRC0 05-EN Dimensional Data All dimensions are in inc hes. 6-1 0 T ons — Economizer and Bar ometric Relief D amper Hoods 6-1 0 T ons — P ow er Exhaust 6-1 0 T ons — S wing Diameter f or H.
72 RT -PRC0 05-EN W eights T able W -1 — Maximum Unit And Cor ner W eights (Lbs) And Center Of Gr avity Dimensions (In.) Unit Maximum Weights (Lbs) Corner Weights (Lbs) 1 Center of Gravity (In.
73 RT -PRC0 05-EN Mec hanical Specif ications General The units shall be conver tible airflow. The operating range shall be between 1 15°F and 0°F in cooling as standard from the factory for units with microprocessor controls. Operating range for units with electromec hanical controls shall be between 1 15°F and 40°F .
74 RT -PRC0 05-EN Mec hanical Specif ications 24-volt electromec hanical control circuit shall include control transformer and contactor pressure lugs for power wiring.
75 RT -PRC0 05-EN Mec hanical Specif ications Supply and/or Retur n Air Smoke Detect or — With this option factory - installed, if smoke is detected, all unit operation will be shut down. Reset will be manual at the unit. Return Air Smok e Detectors require minimum allowable airflow when used with certain models.
T rane A business of American Standard Companies www .trane.com For more information contact your local dealer (distributor), local district office, or e-mail us at comfor t@trane.com T rane has a policy of continuous product and product data improvement and reserves the right to c hange design and specifications without notice.
デバイスTrane RT-PRC005の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Trane RT-PRC005をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTrane RT-PRC005の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Trane RT-PRC005の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Trane RT-PRC005で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Trane RT-PRC005を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTrane RT-PRC005の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Trane RT-PRC005に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTrane RT-PRC005デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。