TraneメーカーTUD2D120B9V5VBの使用説明書/サービス説明書
ページ先へ移動 of 26
UPFLO W/HORIZONT AL 2-ST A GE, V ARIABLE SPEED GAS-FIRED FURNA CE PUB. NO . 22-1650-13 XV 80 MODELS TUD2B060A9V3VB , TUD2B080A9V3VB TUD2C080A9V4VB , TUD2C080B9V4VB TUD2B100A9V3VB , TUD2C100A9V5VB TUD2.
2 22-1650-13 General Features © 2011 T rane NA TURAL GAS MODELS Central Heating furnace designs are cer- tified by the American Gas Association f or both natural and L.P . gas. Limit setting and rating data were estab lished and approv ed under standar t rating condi- tions using American National Standards Instirute standards.
3 22-1650-13 Featur e Summar y Featur es and Benefits Standard Equipment Optional Equipment General Data TUD2B060A9V3VB TUD2B080A9V3VB TUD2C080A9V4VB TUD2C080B9V4VB TUD2B100A9V3VB TUD2C100A9V5VB TUD2.
4 22-1650-13 XV80 ST AND ARD EQUIPMENT • Upow/Horizontaland • P owersupply115/1/60 • 2-stagegasvalv e • 2-speedventer • V ar iab lespeedblower.
5 22-1650-13 XV80 OPTIONAL EQUIPMENT Thermostat, Mechanical 2-Stage Heating/1-Stage Cooling ........................................................................................ T A YST A T241 [ ] Thermostat, Mechanical Heating Only With F an Switch .
6 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 MODEL TYPE RA TINGS 2 1st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 3 2nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3 T emp . rise (Min.-Max.) °F . BLO WER DRIVE Diameter - Width (In.) No .
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 7 MODEL TYPE RA TINGS 2 1st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 3 2nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3 T emp . rise (Min.-Max.) °F . BLO WER DRIVE Diameter - Width (In.) No .
8 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 MODEL TYPE RA TINGS 2 1st Stage Input BTUH 1st Stage Capacity BTUH (ICS) 3 2nd Stage Input BTUH 2nd Stage Capacity BTUH (ICS) 3 T emp . rise (Min.-Max.) °F . BLO WER DRIVE Diameter - Width (In.) No .
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 9 *UD2B060A9V3VB FURNA CE COOLING AIRFLO W (CFM) AND POWER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER OUTDOOR UNIT SIZE (T ONS) AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW1 SW2 SW3 SW4 0.
10 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 *UD2B080A9V3VB FURNA CE COOLING AIRFLO W (CFM) AND POWER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER OUTDOOR UNIT SIZE (T ONS) AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW 1 SW 2 SW 3 SW 4 0.
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 11 *UD2C080A9V4VB FURNA CE HEA TING AIRFLOW (CFM) AND PO WER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW 7 SW 8 0.1 0.3 0.5 0.
12 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 *UD2C080B9V4VB FURNA CE HEA TING AIRFLOW (CFM) AND PO WER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW 7 SW 8 0.1 0.3 0.5 0.
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 13 *UD2B100A9V3VB FURNA CE HEA TING AIRFLO W (CFM) AND POWER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW 7 SW 8 0.1 0.3 0.5 0.
14 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 *UD2C100A9V5VB FURNA CE HEA TING AIRFLO W (CFM) AND POWER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW 7 SW 8 0.1 0.3 0.5 0.
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 15 *UD2C100B9V5VB FURNA CE HEA TING AIRFLO W (CFM) AND POWER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW 7 SW 8 0.1 0.3 0.5 0.
16 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 *UD2D120A9V5VB FURNA CE HEA TING AIRFLOW (CFM) AND PO WER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW7 SW8 0.1 0.3 0.5 0.
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 17 *UD2D120B9V5VB FURNA CE HEA TING AIRFLOW (CFM) AND PO WER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE S4-3 S4-4 0.1 0.3 0.5 0.
18 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 *UD2D140A9V5VB FURNA CE HEA TING AIRFLO W (CFM) AND POWER (W A TTS) VS. EXTERNAL ST A TIC PRESSURE WITH FIL TER AIRFLOW SETTING DIP SWITCH SETTING EXTERNAL ST A TIC PRESSURE SW 7 SW 8 0.1 0.3 0.5 0.
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 19 PRODUCT D A T A WIRING DIA GRAM F rom Dwg. D344249P02.
20 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 PRODUCT D A T A SCHEMA TIC DIA GRAMS F rom Dwg. D344249P02.
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 21 PRODUCT D A T A FIELD WIRING DIA GRAM FOR SINGLE ST A GE HEA TING ONL Y F rom Dwg. 21B341127 Rev . 0 F rom Dwg. 21B341126 Rev . 0 FIELD WIRING DIA GRAM FOR TW O ST A GE HEA TING TO 115 V 1 PH., 60 HZ.
22 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 PRODUCT D A T A FIELD WIRING DIA GRAM FOR SINGLE ST A GE HEA TING WITH SINGLE ST A GE COOLING (OUTDOOR SECTION WITHOUT TRANSFORMER) F rom Dwg.
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 23 PRODUCT D A T A FIELD WIRING DIA GRAM FOR TWO ST A GE HEA TING WITH TW O ST A GE COOLING (OUTDOOR SECTION WITHOUT TRANSFORMER) F rom Dwg.
24 DA T A SUBJECT T O CHANGE WITHOUT NOTICE 22-1650-13 PRODUCT D A T A TUD-9V OUTLINE DRA WING (ALL DIMENSIONS ARE IN INCHES) F rom Dwg. C341699 MODEL A B C D *UD2B060A9V3V** *UD2B080A9V3V** *UD2B100A.
22-1650-13 DA T A SUBJECT TO CHANGE WITHOUT NOTICE 25.
Since the manufacturer has a policy of contin uous product and product data improvement, it reserves the right to change the design and specifications without notice.
デバイスTrane TUD2D120B9V5VBの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Trane TUD2D120B9V5VBをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTrane TUD2D120B9V5VBの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Trane TUD2D120B9V5VBの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Trane TUD2D120B9V5VBで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Trane TUD2D120B9V5VBを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTrane TUD2D120B9V5VBの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Trane TUD2D120B9V5VBに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTrane TUD2D120B9V5VBデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。