WSHP-DS-6 March 2000 Water Source Heat Pump Water-to-Water Model WPWD WSHP-DS-6.
2 Introduction The WPWD product is a heating and cooling hydronic fluid water-to- water heat pump capable of pro- ducing water temperature up to 130 F or temperatures down to 25 F. This extended operating range offers great opportunities in commercial, residential and indus- trial applications.
3 Introduction 2 Features and Benefits 4 Model Number Description 7 General Data 8 Application Considerations 9 Electrical Data 18 Performance Data 19 Dimensional Data 25 Wiring Diagram 28 Accessory O.
4 General The water source heat pump model WPWD (water-to-water) offers a range of capacities from 2 tons to 6 tons. All units are housed in one standard compact cabinet. Cabinet The cabinet, which allows easy ac- cess for installation and service, is constructed of heavy gauge metal.
5 Controls Features and Benefits Lockout Relay 50 VA Transformer 24 VAC Contactor Compressor Run Capacitor 2 Amp Fuse (for use with desuperheater option) Ground 10 Pole Terminal Strip Low Voltage Ther.
6 Cold water (Supply) Hot water (Supply) Water heater hook-up kit with drain valve from Desuperheater to Desuperheater Desuper-out Isolation Valves (by others) Desuper-in Desuperheater Option The desuperheater option is a heat recovery system packaged within the water-to-water unit.
7 Model Number Description Digits 1 & 2: Product Type WP = Trane Commercial Water Source Heat Pump Digit 3: Product Configuration W = Water-to-Water Digit 4: Development Sequence D Digits 5-7: Unit Nominal Capacity 024 = 24.0 MBh 036 = 36.0 MBh 042 = 42.
8 General Data Table G-1: Physical Data (English) Model: WPWD 024 036 042 048 060 072 Unit Size Width of cabinet (in) 23 23 23 23 23 23 Width of cabinet and connections (in) 24.8 24.8 24.8 24.8 24.8 24.8 Height (in) 24.3 24.3 24.3 24.3 24.3 24.3 Depth (in) 23.
9 Application Considerations Closed Loop System Closed loop systems (both ground source and surface water) provide heat rejection and heat addition to maintain proper water source temperatures. Operating and maintenace cost are low because an auxillary fossil fuel boiler and cooling tower are not required to maintain the loop temperature.
10 Application Considerations Open Loop System Where an existing or proposed well can provide an ample supply of suitable quality water, ground water systems may be very efficient. (See Figure 7) Operation and benefits are similar to those for closed loop systems.
11 Source Side vs. Load Side Application Considerations Source vs. Load The model WPWD water-to-water system contains two water to refrig- erant heat exchangers. The two heat exchangers enable the system to be divided into a source and load separation.
12 Closed Loop Geothermal Application Considerations (Closed) Ground Loop Heat Exchanger Geothermal Space Heating / Cooling T emperature Refrigeration Equipment Hydronic Ice Melting Via Unit a W ater-to-W ater Geothermal Integrated System The Trane ground source heat pump is highly efficient in service station applications.
13 Fresh Air Ventilation Application Considerations Water-Out (source) Water-In (source) Water-Out (load) Water-In (load) Exhaust Air Fresh Air (Closed) Ground Loop Heat Exchanger Geothermal Space Hea.
14 Fresh Air Ventilation Mechanical Application Considerations HOT W A TER COIL EXHAUST AIR OUTSIDE AIR AIR HANDLER AIR HANDLER EXHAUST AIR TO HE A T PU MPS EXHAUST AIR FROM TOILET RMS WPWD AUTOMA TIC.
1 2 3 5 4 6 7 Central Pump Application Ball valves should be installed in the supply and return lines for unit isolation and unit water flow rate balancing (if an auto- matic flow device is not selected).
16 Well Water Systems Application Considerations 7 6 2 3 4 5 Figure 11: Well water installation 1 9 8 S u p p l y O v e r f l o w R e t u r n General A well water application involves an open loop water supply . The water is drawn from an open well or pond into the unit.
17 Earth Coupled Application Ball valves should be installed in the supply and return lines for unit isolation. Flexible hoses may be used to connect the water supply and return lines to the water inlets and outlet s. These hoses reduce possible vibration between the unit and the rigid system.
18 Electrical Data Table E-1: Electrical Data Model: WPWD 024 036 042 048 060 072 Voltage 208-230/60hz/1phase Compressor RLA 11.4 15 18.4 20.4 28 32.1 Compressor LRA 56 73 95 109 169 169 Minimum Circuit Ampacity 16 21 25.8 28.6 39 45 Max Fuse Size 25 30 40 45 60 70 Aux Pump Amps 2.
デバイスTrane WSHP-DS-6の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Trane WSHP-DS-6をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはTrane WSHP-DS-6の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Trane WSHP-DS-6の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Trane WSHP-DS-6で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Trane WSHP-DS-6を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はTrane WSHP-DS-6の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Trane WSHP-DS-6に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちTrane WSHP-DS-6デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。