1 VFR-400 • 5403548 • REV D • 10/07 Manual #5403548 Rev D 10/07 VFR-400 Installation, Operation, and Instruction Manual Releasing Panel for Sprinkler Systems All speci fi cations subject to revision.
2 VFR-400 • 5403548 • REV D • 10/07 Operating Instructions Form ................................................................................................................................................................ 4 Design Guidelines .
3 VFR-400 • 5403548 • REV D • 10/07 Notes:.
4 VFR-400 • 5403548 • REV D • 10/07 This is the safety alert system. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
5 VFR-400 • 5403548 • REV D • 10/07 Design Guidelines People trained in the design of special hazard systems shall determine the selection and placement of the initiating devices and noti fi cation appliances connected to the VFR-400. This responsible party shall also be familiar with the premises being protected.
6 VFR-400 • 5403548 • REV D • 10/07 · T welve Standard Programs for water based systems or custom program capability · Releasing Zones can be set up for either normal or cross zoning operation · All circuits inherently power limited per NEC 760 and UL 864 Section 14.
7 VFR-400 • 5403548 • REV D • 10/07 LCD A 2 line 32 character alpha-numeric liquid crystal display shows the condition, status and circuit for all Alarm, Supervisory and Trouble conditions: COND.
8 VFR-400 • 5403548 • REV D • 10/07 • Normal standby current - approximately 4.0 mA • Standby voltage - 25VDC maximum, 13.4 minimum • Maximum short circuit current - approximately 36mA • Maximum Impedance for Alarm - 1400 ohms • Normal supervisory current - approximately 4mA • Low current trouble activation - approximately 3.
9 VFR-400 • 5403548 • REV D • 10/07 Service Use NFP A 13 - Automatic Sprinkler NFP A 15 - W ater Spray Fixed System NFP A 16 - Foam W ater Sprinkler and Foam W ater Spray NFP A 72 - National Fir.
10 VFR-400 • 5403548 • REV D • 10/07 Low Air Alarm 1) Operation of supervisory relay contacts and local buzzer . 2) Activation of the noti fi cation appliance circuit(s) or releasing circuit(s) which are mapped to the initiating device circuit(s).
11 VFR-400 • 5403548 • REV D • 10/07 Ground Fault A short between any circuit and earth ground will result in the following: 1) Activation of trouble relay contacts, trouble LED in a fl ashing mode, and local buzzer . 2) Operation of any output circuits which have been described as TROUBLE BELL.
12 VFR-400 • 5403548 • REV D • 10/07 T o Silence A Signaling Appliance Press the SIGNAL SILENCE button. All silencable outputs will de-activate. A trouble condition will be created and the amber Alarm Silenced LED will light. Notes: 1) Alarms initiated from zones that are in the water fl ow mode cannot be silenced.
13 VFR-400 • 5403548 • REV D • 10/07 have activated. Pressing the SIGNAL SILENCE button changes the fl ashing Red Zone LED to steady on and the fl ashing Red Output LED mapped to that zone off unless the output is programmed as RELEASE. In addition, the Y ellow ALARM/ SILENCE LED will light.
14 VFR-400 • 5403548 • REV D • 10/07 } ZONE 1 ZONE 2 ZONE 3 ZONE 4 OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 AC POWER POWER TBL SYSTEM TBL SUP TBL GROUND FA U LT SUPER VISORY 1 SUPER VISORY 2 COMMON A.
15 VFR-400 • 5403548 • REV D • 10/07 Date/Time SELECT T o change the time, press the SELECT button. FUNCTION T o exit to the next function, press the bottom button. If the middle button is pushed, the date and time will appear in the display window: The date is shown at the top and the time at the bottom of the display window .
16 VFR-400 • 5403548 • REV D • 10/07 After entering the correct password, a display similar to the following will appear: Zone Disabled/Enabled This display allows the user to ENABLE or DISABLE Initiating zones. This display window shows that initiating ZONE #1 is enabled.
17 VFR-400 • 5403548 • REV D • 10/07 One Man W alktest This display allows the user to select system mode NORMAL or ONE MAN W ALKTEST by pressing the SELECT button to toggle back and forth from NORMAL to ONE MAN W ALKTEST . When the desired mode is displayed, press the SET button.
18 VFR-400 • 5403548 • REV D • 10/07 Outputs Alarm 24VDC Bells, Horns, Strobes, to indicate an alarm condition. Release Solenoid V alve, Squib, Releasing Mechanism Supervisory 24VDC Bells, Horns, Strobes, to indicate a supervisory condition. T rouble 24VDC Bells, Horns, Strobes, to indicate a trouble condition.
19 VFR-400 • 5403548 • REV D • 10/07 This page intentionally left blank..
20 VFR-400 • 5403548 • REV D • 10/07 PROGRAM #1 For One Sprinkler System V iking Sprinkler System T ypes 2 Release Zones, W ater fl ow Zone, & Manual Release Zone 1. Single Interlocked Preaction System with Electric Release 2. Deluge System with Electric Release 3.
21 VFR-400 • 5403548 • REV D • 10/07 N L H OT - B L A C K N EUTR A L-W H I TE EA RT HG R O U N D- G R E E N OU T PU T 1 B A T + ASS Y D I OD E EO L RED BLACK NO C O M NC NC N O N O N O CO M C O M C O M BLACK RED 5 .
22 VFR-400 • 5403548 • REV D • 10/07 PROGRAM #2 For T wo Sprinkler Systems Operating Independantly From Each Other V iking Sprinkler System T ypes 2 Split Release Zones and 2 W ater fl ow Zones 1. Single Interlocked Preaction System with Electric Release 2.
23 VFR-400 • 5403548 • REV D • 10/07 N L H OT - B L A C K N EUTR A L-W H I T E EA RT H GROUND - G R EEN O U T PU T 1 B A T + ASS Y D I OD E EO L RED BLACK NO CO M NC NC NO N O NO CO M C O M C O M BLACK RED 5 .
24 VFR-400 • 5403548 • REV D • 10/07 PROGRAM #3 For One Sprinkler System V iking Sprinkler System T ypes 2 Cross Release zones, W ater fl ow zone, and Manual Release zone 1.
25 VFR-400 • 5403548 • REV D • 10/07 NL H OT - B L A C K NEUTRAL - WH ITE E AR T H GR O UND - G R E E N O U T P U T 1 B AT+ ASS Y D I OD E EO L RED BLACK N O C OM NC NC N O N O N O C OM C O M C O M BLACK RED 5 .
26 VFR-400 • 5403548 • REV D • 10/07 NOTES: 1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #2 (Release Solenoid) and output #3 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
27 VFR-400 • 5403548 • REV D • 10/07 NL H OT - B L A C K NEUTRAL - WH ITE EA RT H GROUND - G R EEN O U T P U T 1 B AT+ ASS Y D I OD E EO L RED BLACK N O C OM NC NC N O N O N O C O M C O M C O M BLACK RED 5 .
28 VFR-400 • 5403548 • REV D • 10/07 NOTES: 1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #2 (Release Solenoid) and output #3 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
29 VFR-400 • 5403548 • REV D • 10/07 NL H OT - B L A C K NEUTRAL - WH ITE E AR T H GR O UND - G R E E N O U T P U T 1 B AT+ ASS Y D I OD E EO L RED BLACK N O C OM NC NC N O N O N O C O M C O M C O M BLACK RED 5 .
30 VFR-400 • 5403548 • REV D • 10/07 NOTES: 1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (N/O Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
31 VFR-400 • 5403548 • REV D • 10/07 NL H OT - B L A C K NEUTRA L -W H I T E E AR T H GR O UND - G R E E N O U T PU T 1 B AT+ ASS Y D I OD E EO L RED BLACK N O C OM NC NC N O N O N O C O M C O M CO M BLACK RED 5 .
32 VFR-400 • 5403548 • REV D • 10/07 XX = Cross-Zoned PROGRAM #7 For One Sprinkler System V iking Sprinkler System T ypes 2 Cross Release Zones and Manual Release Zone 1.
33 VFR-400 • 5403548 • REV D • 10/07 N L H O T - B L A CK N E U TR A L-W H I T E E A R T H G R O U N D - G R E E N O U T P UT 1 B A T + A SS Y D I O D E EO L RED BLACK N O C O M N C N C NO N O N O C O M C O M C O M BLACK RED 5 . 1K E O L R BLACK RED E O L R 5 .
34 VFR-400 • 5403548 • REV D • 10/07 PROGRAM #8 For One Sprinkler System V iking Sprinkler System T ypes 1 Release Zone and Manual Release 1. FIRECYCLE III Deluge Multicycle System OUTPUTS (Indi.
35 VFR-400 • 5403548 • REV D • 10/07 N L HOT - B L ACK N EUTR A L-W H I T E E AR T H GR O UND - G R E E N O U T P UT 1 B A T + ASS Y D I OD E EO L RED BLACK N O C OM NC NC NO N O NO CO M C O M C O M BLACK RED 5 .
36 VFR-400 • 5403548 • REV D • 10/07 PROGRAM #9 For One Sprinkler System V iking Sprinkler System T ypes 1 Release Zone and Manual Release Zone 1.
37 VFR-400 • 5403548 • REV D • 10/07 N L H OT - B L A C K N EUTR A L-W H I T E E AR T H GR O UND - G R E E N O U T P UT 1 B AT+ ASS Y D I OD E EO L RED BLACK N O C OM NC NC NO N O NO CO M C O M CO M BLACK RED 5 .
38 VFR-400 • 5403548 • REV D • 10/07 NOTES: 1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
39 VFR-400 • 5403548 • REV D • 10/07 N L H O T - B L A CK N E U TR A L-W H I T E EA R T HG R O U N D-G R E E N OU T PU T 1 B A T + A SS Y D I O D E EO L RED BLACK N O C O M N C N C NO N O N O C O M CO M C O M BLACK RED 5 . 1K E O L R BLACK RED E O L R 5 .
40 VFR-400 • 5403548 • REV D • 10/07 XX = Cross-Zoned NOTES: 1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
41 VFR-400 • 5403548 • REV D • 10/07 N L H O T-B L A C K N E U TR A L-W H I T E EA R T HG R O U N D-G R E E N OU T PU T 1 B A T + A SS Y D I O D E EO L RED BLACK NO CO M N C N C NO N O N O C O M C O M C O M BLACK RED 5 . 1K E O L R BLACK RED E O L R 5 .
42 VFR-400 • 5403548 • REV D • 10/07 XX = Cross-Zoned NOTES: 1. Connect EOL Diode assembly IN SERIES as shown with Solenoid on output #3 (Release Solenoid) and output #4 (Release Solenoid). Black wire to positive terminal on panel and Red wire through Solenoid to negative terminal on panel.
43 VFR-400 • 5403548 • REV D • 10/07 N L H O T-B L A C K N E U TR A L-W H IT E EA R T HG R O U N D-G R E E N OUT P UT 1 B A T + A SS Y D I O DE EO L RED BLACK N O C O M N C N C NO N O N O C O M C O M C O M BLACK RED 5 . 1K E O L R BLACK RED E O L R 5 .
44 VFR-400 • 5403548 • REV D • 10/07 +- - - + + - +- +- +- +- + +-+-+- +- S +- +- CUSTOM PROGRAM ZONES SUP 1 SUP 2 #1 #2 #3 #4 OUTPUTS #1 #2 #3 #4.
45 VFR-400 • 5403548 • REV D • 10/07 SET Press the SET button to set the description displayed into the panels program SELECT Press the SELECT button to scroll between water or chemical based modes FUNCTION Press the bottom button to skip to the next function Initiating Zone Description This allows the user to describe the initiating zones.
46 VFR-400 • 5403548 • REV D • 10/07 Soak Timer Description This allows the user to select the amount of time the release circuit on output #3 will stay activated after the Firecycle zone restores to normal. The available times are 30, 60, 90 seconds, 2-20 minutes in 1 minute incriments, or continous.
47 VFR-400 • 5403548 • REV D • 10/07 After selecting all four outputs or pressing FUNCTION, the following will be displayed if any outputs have been described as RELEASING: Where “<A>” is the number of the releasing circuit output. Normal/Cross-Zoning Each releasing circuit can be set up for the normal or cross zoned operation.
48 VFR-400 • 5403548 • REV D • 10/07 Custom Message T o change the banner message, press the SELECT button. If you don’ t want to change the banner message press the bottom button. SET SELECT Press the SELECT button to change banner message. FUNCTION Press the bottom button to skip to the next function.
49 VFR-400 • 5403548 • REV D • 10/07 Custom Program (#0 only) • Describe Initiating Zones 1 - 4 Alarm Zones Supervisory Zones Detection Supervisory W ater fl ow T amper Linear Heat Detection .
50 VFR-400 • 5403548 • REV D • 10/07 Wir e Checkout: W ith all initiating devices and noti fi cation appliances installed and with the EOLR’ s in place, check the wires with an ohmmeter . Meter readings outside of the following will prevent normal operation.
51 VFR-400 • 5403548 • REV D • 10/07 Battery Size Requirements And Maintenance Charging V oltage: 27VDC Nominal Maximum Charging Current: .5A These panels require a 24 volt sealed lead acid battery for proper operation. 24 hours of standby power is required for Local Systems and Central Station (NFP A-72).
52 VFR-400 • 5403548 • REV D • 10/07 T ABLE 2 SECONDAR Y POWER SUPPL Y REQUIREMENTS Service Use Standby Time Alarm Time NFP A 72 • Central Station (PPU) 24 hrs. 5 mins. • Local 24 hrs. 5 mins. FMRC 101 1 and 1012, Deluge and Pre-action Systems 90 hrs.
53 VFR-400 • 5403548 • REV D • 10/07 T ypical Firecycle Wiring T ypical 2 W ire Detector Connection Drawing Base wiring for Potter models IS-24 Ionization Detectors and PS-24 Photoelectric Detectors.
54 VFR-400 • 5403548 • REV D • 10/07 VFR-400 Connection Drawing For additional information see text in this manual Identi fi er A.
55 VFR-400 • 5403548 • REV D • 10/07 2-Wir e Smoke Detector And Synchronization Module Compatibility Data System Sensor (Brk) (Max. No. Of Detectors Per Zone Is 20) Det. Model Identi fi er Base Model Identi fi er 1400* A N/A N/A 2400* A N/A N/A 2400TH* A N/A N/A 2W -B A N/A N/A 2WT -B A N/A N/A 2WTR-B A N/A N/A Detection Systems (Max.
56 VFR-400 • 5403548 • REV D • 10/07 Automatic W ater Control V alves Compatibility Data V iking: 13215 Normally open 1 1591 Normally closed 1 1601 Normally closed 1 1602 Normally closed, explos.
57 VFR-400 • 5403548 • REV D • 10/07 NEC Section 760-54. Installation of Conductors and Equipment. (a) Separation from Electric Light, Power , Class 1, and NPLF A Circuit Conductors. (1) In Cables, Compartments, Enclosures, Outlet Boxes, or Raceways.
58 VFR-400 • 5403548 • REV D • 10/07 ** Or other UL864 9th Edition listed stand alone DACT connected as shown and installed in the same room within 20 feet of the VFR-400 and with interconnecting wiring in conduit. See PFC-7500 Manual 8910225 for programming information.
デバイスViking VFR-400の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Viking VFR-400をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはViking VFR-400の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Viking VFR-400の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Viking VFR-400で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Viking VFR-400を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はViking VFR-400の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Viking VFR-400に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちViking VFR-400デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。