WINE-MATE Ducted System Installation, Operation & Care Manual VINO4500DS VINO6500DS VINO8500DS V V i i n n o o t t e e m m p p I I n n t t e e r r n n a a t t i i o o n n a a l l C C o o r r p p . . w w w w w w . . w w i i n n e e m m a a t t e e .
- 1 - RE AD A ND SAVE THESE I NSTRUCTIONS TABLE OF CONTENTS Important Safety Info rmation…..........................................2 Feature Description…………………………….……………..3 Cellar Construction.…………………………….
- 2 - Important Safety Information • DO NOT USE A GROUND FAUL T INTERRUPTER (GFI). • A DEDICATED 20 AMP CIRCUIT IS HIGHLY RECOMMENDED..
- 3 - Feature Description • WINE-MATE ducted system VINO4500- 8500DS are designed and used to provide a cold temperature between 50~65 ° F for a properly insulated wine room at a normal environment. • The wine room will maintain hum idity of 50~70% RH even when the environment becomes dry and humid.
- 4 - The dimensions and capacities are specified as follows: MODEL DIMENSION L”xH”xW” Btu/h (55/90 ° F) CFM BOTTLE CA PA CITY (55/75 ° F) REF RI GERA NT ELECTRICAL WEIGHT(lb) VINO- 4500DS 45X.
- 5 - Cellar Construction This is only a guide and shall be c onsidered as minimum requirements. All interior walls and floors shall have a vapor barrier and a minimum of R11 insulation. All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation.
- 6 - Installer’s Instruction Federal law requires that WINE -MATE ducted cooling systems be installed by an EPA certified refrigeration technician. WINE-MATE ducted system is shipped re ady for use only after a certified refrigeration technician has properly inst alled the system.
- 7 - 1. Location • Place the unit in a properly ventilated location. If it is not, heat exhausted by the condensing unit will build up and the cooling syst em will not operate properly. • Leave minimum 5 feet clearance for hot air exhaust and leave minimum 1 foot clearance for the fresh air intake.
- 8 - Temperature Control & Humidity Adjustment 1. Temperature Setting • Set the temperature at 55 ° F for the optimum aging of wine • On initial start-up, the time required to reach the desired temperature will vary, depending on the quantit y of bottles, temperature setting and surrounding temperature.
- 9 - Dip-switch description (See detail in VSTAT instruction) 1, 2 differential: added to the Set Point, es tablishes the temperature threshold, measured by the regulation probe, beyond which the co .
- 10 - If the function is enabled, the compressor is not energized for three minutes after controller power up. The function is also active in hot-gas defrost mode. 5) LED & Display Messages 1. LED off 2. LED on 3. LED blinking 0.5s on/0.5s off 4.
- 11 - 2) Alarm Signals 2.1 Code Description 2.2 Alarm Recovery Probe alarms P1”, start a few seconds afte r the fault in the re lated probe; they automatically stop a few seconds afte r the probe restarts normal operation. Check connections before replacing the probe.
- 12 - 2. The value of the set point will be di splayed and the “°C” or “°F” LED starts blinking; 3. To change the Set value, push the o or n arrows within 10s. 4. To memorize the new set point value, push the SET key again or wait 10s. 4) Humidity Adjustment The parameter Fon is used to adjust the humidity in the wine cabinet.
- 13 - Service Guide 1. Refrigeration Piping and Charge • The subcooling at the condensing unit shall be around 10 ° F. The charge may be complete when there are no more bubbles forming in the sight glass. • The evaporator’s constant pressure expansion valve is set around 38- 40 ° F at factory.
- 14 - k. Low suction pressure and low to normal head p re s sure High superheat and normal to high subcooling l. Low suction pressure and n ormal head pressure High superheat and normal subcoo ling m. Low su ction pressure and high head pressure High superheat and high subcooling n.
- 15 - 4. Electrical Wiring Fig. 4.2 VINO4500DS Electrical Wiring Diagram (VTSTAT) Fig. 4.3 VINO4500DS Elect rical Wiring Diagram (D IGITAL CONTROLLER).
- 16 - Fig. 4.4 VINO6500DS Electrical Wiring Diagram (VTSTAT) Fig. 4.5 VINO6500DS Elect rical Wiring Diagram (D IGITAL CONTROLLER).
- 17 - Fig. 4.6 VINO8500DS Elect rical Wiring Diagram (VTSTAT, UJ6220Z) Fig. 4.7 VINO8500DS Wiring Diagram (DIGITAL CONTROLLER, UJ6220Z).
- 18 - 5. Use of the adjustable low pr essure control (if applicable) Cut out = 5 psig; Cut in = 25 psig; Differential = 20 psig Fig. 4.8 Adjustable Low Pressure Control 6. Condensing Unit Troubleshooting Unit not running a. Incorrect power supply b. Incorrect or loose wiri ngs c.
- 19 - Care Guide In general, always unplug system or di sconnect power while doing care. 1. Coil Cleaning • Clean the condenser coil regularly. Coil may need to be cleaned at least every 6 months. • Unplug the system or disconnect power. • Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty.
- 20 - User’s Troubleshooting This Troubleshooting Chart is not prepared to replace the training required for a professional refrigeration servic e person, not is it comprehensive Troubleshooting Chart Complaint Possible Causes Response 1.Unit not running a.
- 21 - e. Malfunctioning fans f. Improper evaporator or condenser airflow g. Dir ty Condenser h. Iced evaporator i. Refrigeration system restriction j. Sealed system problem k. Undercharge or overcharge intake side e. Check for both evaporator and condenser fans f.
- 22 - Customer Support If you still have problems, please contact us at: Vinotemp International 17631 South Susana Road Rancho Dominguez, CA 90221 Tel: (310) 886-3332 Fax: (310) 886-3310 Email: info@vinotemp.
- 23 - Warranty Thank you for choosing a Vinotemp cooling unit. Please enter the complete model and se rial numbers in the space provided: Model_____________ _________________________ __ _________________ Serial No._________________ ____________________ _________________ Attach your purchase receipt to this owner’s manual.
- 24 - VINOTEMP will, at its discret ion, repair or replace the unit and return it free of charge to the original retail customer. If the unit is found to be in good working order, or beyond the initial twelve month period, it will be returned freight collect.
デバイスVinotemp VINO8500DSの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Vinotemp VINO8500DSをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはVinotemp VINO8500DSの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Vinotemp VINO8500DSの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Vinotemp VINO8500DSで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Vinotemp VINO8500DSを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はVinotemp VINO8500DSの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Vinotemp VINO8500DSに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちVinotemp VINO8500DSデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。