Weil-McLainメーカーPLUS LINE PLUS-E017-A/1206の使用説明書/サービス説明書
ページ先へ移動 of 68
P ar t Number PLUS-E017-A/1206 User — Read important user safety information found on pages 2, 18, 19 and 20. Installation and service should only be performed by a qualified serv ice technician.
2 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Hot W ater Can Scald! • W at er heated to temperatur e for clothes washing, dish washing and other sanitizing needs can scald and cause permanent injur y .
P ar t Number PLUS-E017-A/1206 3 Manual • Installation • Start-Up • Usage • Maintenance • Parts Overview This manual contains six sections, A through F. Sections A, E and F apply to ALL GOLD Plus 30, 40, 60 or 80; PLUS 40, 60, or 80; and PLUS 100, 110, or 119 water heater installations, regardless of the boiler used.
4 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Balancing .................................................................................................................... 22 Components required ..............
P ar t Number PLUS-E017-A/1206 5 Manual • Installation • Start-Up • Usage • Maintenance • Parts PLUS 100/110/119 Figure 25 ..................
6 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Codes Installation must co nform with inst ructions in this manual and, where applicable: • local, state, pr ovincial, and national c odes, laws, regulations and ordinances.
P ar t Number PLUS-E017-A/1206 7 Manual • Installation • Start-Up • Usage • Maintenance • Parts Operating restrictions • Maximum d omestic hot wate r temperature ( Use only for special high-temperature operational requirements ): • 160°F for GOLD Plus 30/40/60/80 or Plus 40/60/80.
8 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 T emperature & pressure (T & P) relief v alve Air vent The boiler-side piping must be equipped w ith a diaphr agm- or bladder- ty pe expansion tank, NOT a c losed-ty pe expansion tank.
P ar t Number PLUS-E017-A/1206 9 Manual • Installation • Start-Up • Usage • Maintenance • Parts Figure 2 Piping — OPTION 1 GOLD Plus 30/40/60/80 or Plus 40/60/80 (See Figure 3, page 10, f .
10 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 W ater heater piping continued A2 Figure 3 Piping — OPTION 2 Models 30/40/60/80 or Plus 40/60/80 (Required f o.
P ar t Number PLUS-E017-A/1206 11 Manual • Installation • Start-Up • Usage • Maintenance • Parts Figure 4 Piping — OPTION 1 PLUS 100/110/119 (See Figure 5, page 12, f or OPTION 2, required.
12 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Figure 5 Piping — OPTION 2 PLUS 100/110/119 (Required f or Commonwealth of Massachusetts) Drain v alve PLUS 100/110/119 Option 2 Apply the following and Figure 5 t o water heate rs installed in Massachusetts.
P ar t Number PLUS-E017-A/1206 13 Manual • Installation • Start-Up • Usage • Maintenance • Parts General piping inf ormation • For domestic wate r piping, see pages 8 thr ough 12. • See pages 22–23, for d omestic water recir culation piping.
14 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Domestic water piping • U nion on domestic hot water outlet should be piped at a hig her elevation than domestic water drain valv e. This wil l make draining wate r heater easier .
P ar t Number PLUS-E017-A/1206 15 Manual • Installation • Start-Up • Usage • Maintenance • Parts W ater heater thermostat connection PL US-Line indirect water heaters utilize a snap-set connector for easy w iring between water heater thermostat and boiler co ntrols (also see Section B or D).
16 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 1. Close boiler water drain valv e at boiler water outlet of water heater .
P ar t Number PLUS-E017-A/1206 17 Manual • Installation • Start-Up • Usage • Maintenance • Parts Star t-up chec klist ❏ Long element T&P r elief valve is pr operly installed and dr ain discharge is directed awa y from all persons. ❏ Both inner and outer tanks ar e filled w ith water .
18 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Hot W ater Can Scald! • W ater temperature ov er 125°F can cause severe burns instantly , or death fr om scalds.
P ar t Number PLUS-E017-A/1206 19 Manual • Installation • Start-Up • Usage • Maintenance • Parts Studies hav e indicated that dangerous bacteria, including legionella pneumophila, can form in the potable water distr ibution system if certain minimum water temperatures are not maintained.
20 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 W ater heater maintenance A6 Maintenance schedule – ann ual service technician Annual service by qualified service technician to include: • Any pr ocedures r equired b y local codes.
P ar t Number PLUS-E017-A/1206 21 Manual • Installation • Start-Up • Usage • Maintenance • Parts Filling See Filling the Inner (Domestic Water) Tank , and Filling the Outer (Boiler Water) Tank , on page 16. Draining Drain water heater if it will be shut off and exposed to freezing temperatur es.
22 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 T able 2 Time lag to obtain hot water at fixture f or branch lengths of 10 and 25 f eet (ASPE Domestic W ater Heating Design Manual ) Time in seconds required to get hot water at fixture (from ASPE) Fixture flow r ate (GPM) - 0.
P ar t Number PLUS-E017-A/1206 23 Manual • Installation • Start-Up • Usage • Maintenance • Parts Figure 10 Recirculation connection at water heater Figure 9 Recirculation components Components 1 Cir culato r — Little flo w is req uired to maintain a tempera ture in the piping.
24 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 B Gas-fir ed boiler applications Overview Follow the guidelines in this section to install Gas-fired boilers with PLUS or PLUS indirect water heaters. Install the domestic water piping and water heater following the guidelines of Section A.
P ar t Number PLUS-E017-A/1206 25 Manual • Installation • Start-Up • Usage • Maintenance • Parts Install system water piping (space heating) Figure 11 Expansion tank piping B1 Gas System water piping methods All pip ing met hods sho wn in this manua l use primary/sec onda ry c onn ection to the boiler loop .
26 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Install system water piping (space heating) (continued) Figure 12 Zone valv e z oning plus optional water heater piping Zoning with zone valves 1. Connec t boiler to system as shown in Figu re 12 when zone val ve zoning.
P ar t Number PLUS-E017-A/1206 27 Manual • Installation • Start-Up • Usage • Maintenance • Parts Install system water piping (space heating) (continued) Figure 13 Circulator zoning plus optional w ater heater piping Zoning with cir culators 1.
28 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Install boiler -to-water heater piping Combined space heating/water heating applications 1. Figure 14 sho ws r ecommended piping between Gas boiler and PL US water heater .
P ar t Number PLUS-E017-A/1206 29 Manual • Installation • Start-Up • Usage • Maintenance • Parts T able 3 Combined space heating/water heating (see Notes) T able 4 De d i ca te d w at e r - .
30 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 ELECTRICAL SHOCK HAZARD — For yo ur s a fe t y , tu r n o f f el ec t r i ca l power supply at ser vice entrance panel befor e making any electr ical con nections to avo id p ossible elect ric shock hazard.
P ar t Number PLUS-E017-A/1206 31 Manual • Installation • Start-Up • Usage • Maintenance • Parts Wiring a system cir culator 1. For combined systems, to ac tivate a system circu- lator when the Boiler circulator operates, w ire as shown at bottom of Figure 17, pag e 30.
32 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Field wiring — Gas boilers only (continued) Figure 19 Low v oltage field wiring connections Summer/winter switch (item 7) — Install a summer/winter sw itch, if desired, to disable the boiler (space heating) circulato r during non-heating months.
P ar t Number PLUS-E017-A/1206 33 Manual • Installation • Start-Up • Usage • Maintenance • Parts Start-up — Gas boilers only B4 Gas Follow boiler manual 1. Fo llo w all pr oc ed ur es in the Gas bo ile r manu al to start up and verify operation of the boiler .
34 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Start-up — Gas boilers only (continued) B4 Gas [ 3180 ] ( burner on, space heat ing ) Once flame is prov en and stable, the burner turns down to low fire for ap - pro ximately 2 minu tes.
P ar t Number PLUS-E017-A/1206 35 Manual • Installation • Start-Up • Usage • Maintenance • Parts Boiler -side piping (except Gas) This sect ion provides suggested boiler-side and system piping for boiler s other than Gas-fired boilers ( see Se ction B for Gas applications).
36 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Figure 20 GOLD Plus 30/40/60/80 Plus 40/60/80 • Zoning with pumps • Place pumps at beginnings of zones . Placing them at the ends of zones could result in heating idle zones .
P ar t Number PLUS-E017-A/1206 37 Manual • Installation • Start-Up • Usage • Maintenance • Parts Figure 21 GOLD Plus 30/40/60/80 Plus 40/60/80 • Zoning with pumps • Primar y/secondary piping • Place pumps at beginnings of zones . Placing them at the ends of zones could result in heating idle zones .
38 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 1. This drawing is conc eptual only . It shows representativ e piping components and la you t. W eil-McLain does not r epresent that this dra wing meets an y particular mechanical or building codes.
P ar t Number PLUS-E017-A/1206 39 Manual • Installation • Start-Up • Usage • Maintenance • Parts 1. This drawing is conc eptual only . It shows representativ e piping components and la you t. W eil-McLain does not r epresent that this dra wing meets an y particular mechanical or building codes.
40 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Figure 24 Dedicated single boiler with single water heater In residential application ( t y p i c a l l y G O L D P l u s 3 0 / 4 0 / 6 0 / 8 0 or Plus 40/60/80) .
P ar t Number PLUS-E017-A/1206 41 Manual • Installation • Start-Up • Usage • Maintenance • Parts Figure 25 Dedicated single boiler with single water heater In commercial application (typically PLUS 100/110/119).
42 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Figure 26 Multiple water heaters — domestic water piping 1. The drawings on this page are conceptual only . They show representativ e piping components and la y out .
P ar t Number PLUS-E017-A/1206 43 Manual • Installation • Start-Up • Usage • Maintenance • Parts Figure 28 Multiple water heaters and dedicated multiple boiler s — boiler water piping (see legend and details in Figure 26, page 42) 1. This drawing is co nceptua l only .
44 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Installation and start-up of water heaters connected to steam boilers See Figure 29, page 45, for suggested piping schematic. Pipe the domes tic wate r co nne ctio ns t o the wate r hea te r per Section A of this manual.
P ar t Number PLUS-E017-A/1206 45 Manual • Installation • Start-Up • Usage • Maintenance • Parts Figure 29 Steam boiler application Domestic water heating using water pumped from steam boiler • Locate flow/check v alv e as close as possible to w ater heater boiler side connections — to reduce heat loss between cycles.
46 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 w irinG requirements .............................................................................................. 47 Wiring requirements — Circulators ........
P ar t Number PLUS-E017-A/1206 47 Manual • Installation • Start-Up • Usage • Maintenance • Parts Electrical sho ck hazard. Can cause severe personal injury , death or substantial property damage. Disconnect powe r before installing and/or servicing .
48 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
P ar t Number PLUS-E017-A/1206 49 Manual • Installation • Start-Up • Usage • Maintenance • Parts 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
50 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
P ar t Number PLUS-E017-A/1206 51 Manual • Installation • Start-Up • Usage • Maintenance • Parts 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
52 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 Figure 34 T ypical wiring: • Zoning with Weil-McLain zone valve contr oller (WMZV -4 shown) • Domestic priority optional (controller s witch) • Also refer to W eil-McLain Boiler Zone Wiring Guide f or fur ther details.
P ar t Number PLUS-E017-A/1206 53 Manual • Installation • Start-Up • Usage • Maintenance • Parts 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
54 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
P ar t Number PLUS-E017-A/1206 55 Manual • Installation • Start-Up • Usage • Maintenance • Parts 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
56 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
P ar t Number PLUS-E017-A/1206 57 Manual • Installation • Start-Up • Usage • Maintenance • Parts Figure 39 T ypical wiring: • Zoning with zone valves • With domestic priority • PLUS 100/110/119 only • Also refer to W eil-McLain Boiler Zone Wiring Guide f or fur ther details.
58 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
P ar t Number PLUS-E017-A/1206 59 Manual • Installation • Start-Up • Usage • Maintenance • Parts 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
60 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 1. These drawings are conceptual only . They show represe ntative piping co mponents and lay out. W eil-M cLain does not rep resent that the dra wing s meet any par ticular mechanical or building codes.
P ar t Number PLUS-E017-A/1206 61 Manual • Installation • Start-Up • Usage • Maintenance • Parts A. GOLD Plus 30, 40, 60 or 80 Plus 40, 60 or 80 ................................................................................................
62 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 GOLD Plus 30/40/60/80 or PLUS 40/60/80 Series 3 E Replacement parts continued.
P ar t Number PLUS-E017-A/1206 63 Manual • Installation • Start-Up • Usage • Maintenance • Parts Replacement par ts — GOLD Plus 30/40/60/80, Ultra Plus 40/60/80, Series 3 Item Description .
64 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 PLUS 100/110/119 Series 3 E Replacement parts continued.
P ar t Number PLUS-E017-A/1206 65 Manual • Installation • Start-Up • Usage • Maintenance • Parts Replacement par ts — PLUS 100/110 /119 Series 3 Item Description Size Manufacturer W eil-Mc.
66 P ar t Number PLUS-E017-A/1206 PLUS LINE Indir ect-Fired W ater Heaters – Series 3 W ater heater dimensions Dimensions — PLUS-Line indirect water heaters, Series 3 PLUS-Line Indirect-Fired W ater Heaters — Series 3 W ater Heater Model Storage Heati ng surface Head loss on Boiler- side Dimension s Ship.
P ar t Number PLUS-E017-A/1206 67 Manual • Installation • Start-Up • Usage • Maintenance • Parts W ater heater performance ratings Boiler DOE Heating Capacity MBH First Hour Rating Capac ity.
68 P ar t Number PLUS-E017-A/1206 Residenti al & Comme rci al Cast Ir on Boilers R e si d ential W ater W a rranty — Lim ite d Life tim e R e si d ential Steam W arranty — Li m ite d 1.
デバイスWeil-McLain PLUS LINE PLUS-E017-A/1206の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Weil-McLain PLUS LINE PLUS-E017-A/1206をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはWeil-McLain PLUS LINE PLUS-E017-A/1206の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Weil-McLain PLUS LINE PLUS-E017-A/1206の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Weil-McLain PLUS LINE PLUS-E017-A/1206で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Weil-McLain PLUS LINE PLUS-E017-A/1206を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はWeil-McLain PLUS LINE PLUS-E017-A/1206の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Weil-McLain PLUS LINE PLUS-E017-A/1206に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちWeil-McLain PLUS LINE PLUS-E017-A/1206デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。