47D40-801 Demand Defrost Contr ol INST ALLA TION INSTRUCTIONS The 47D40-801 control is a microprocessor-based demand defrost controller intended f or Rheem heat pump systems. This controller uses basic diff erential temperature means to detect degradation of system perf ormance due to ice build-up on the outdoor coil.
2 SPECIFICA TIONS Electrical Ratings [@ 77 o F (25 o C)]: Rated V oltage ..................................... 24 V A C Rated V oltage Range ............................... 18-30 V AC Max. P ower Consumption @ 24 V AC .................. 4.08 V A Nominal F requency .
3 INST ALLA TION On some units, the Outdoor Ambient T emperature (OA T) and Outdoor Coil T emperature (OCT) sensors ma y be attached permanently to the controller. The 47D40-801 includes replacement OA T and OCT sensors that plug onto the 2- and 3-pin connectors on the controller board.
www .white-rodgers.com www .emersonclimate.com White-Rodgers is a division of Emerson Electric Co. The Emerson logo is a trademark and service mar k of Emerson Electric Co.
デバイスWhite Rodgers 47D40-801の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
White Rodgers 47D40-801をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはWhite Rodgers 47D40-801の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。White Rodgers 47D40-801の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。White Rodgers 47D40-801で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
White Rodgers 47D40-801を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はWhite Rodgers 47D40-801の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、White Rodgers 47D40-801に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちWhite Rodgers 47D40-801デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。