GENERAL Model D1EB units are factory assembled cooling only air condi- tioners designed for outdoor installation on a rooftop or a slab. Field-installed electric heater accessories are available to provide electric heat combined with electric cooling.
LIMIT ATIONS These units must be installed in accordance with the following national and local safety codes. 1. National Electrical Code ANSI/NFPS No. 70 or Canadian Electrical Code Part 1, C22.1 (latest editions). 2. Local plumbing and waste water codes and other applica - ble local codes.
CLEARANCES All units require certain clearances for proper operation and service. Refer to Figure 3 for the clearances required for com - bustion, construction, servicing and proper unit operation. WARNING: Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet.
POWER AND CONTROL WIRING Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFP A No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.
035-16703-001-A-0202 Unitary Products Group 5 MODEL DEB POWER SUP - PL Y VOL TAGE LIMIT ATIONS 1 COMPRESSOR COND. FA N MOTOR, FLA SUPPL Y AIR BLOWER MOTOR, FLA MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, AMPS 2 MAX. HACR BREAKER SIZE, AMPS UNIT POWER F ACTOR TRANSFORMER SIZE (V A) MIN.
035-16703-001-A-0202 6 Unitary Products Group DEB POWER SUPPL Y COMPRESSOR COND. FA N MOTOR FLA SUPPL Y AIR BLOWER MOTOR, FLA ELECTRIC HEA T ACCESSORY MINIMUM CIRCUIT AMP ACITY MAX. FUSE SIZE, 1 AMPS MAX. HACR 2 BREAKER SIZE MODEL RLA LRA MODEL NO. ST AGE KW TOT AL AMPS 018 208/230-1-60 9.
Checking Supply Air CFM T o check the supply air CFM after the initial balancing has been completed: 1.Remove the two ¼ inch dot plugs in the duct panel. 2.Insert at least 8 inches of ¼ inch tubing into each of these holes for sufficient penetration into the airflow on both sides of the indoor coil.
8 Unitary Products Group 035-16703-001-A-0202 T ABLE 7 - SUPERHEA T CHARGING T ABLE FOR MODEL D1EB024 OUTDOOR TEMPERATURE (F) SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 800 CFM/TON INDOOR WB TEMPERATURE (F) 55 57 59 61 63 65 67 69 71 73 75 65 13.
Unitary Products Group 9 035-16703-001-A-0202 T ABLE 10 - SUPERHEA T CHARGING T ABLE FOR MODEL D1EB042 OUTDOOR TEMPERATURE (F) SUPERHEA T A T COMPRESSOR SUCTION (F), AIRFLOW = 1,400 CFM/TON INDOOR WB TEMPERATURE (F) 55 57 59 61 63 65 67 69 71 73 75 65 20.
10 Unitary Products Group 035-16703-001-A-0202 FIG . 3 - DIMENSIONS AND CLEARANCES CLEARANCES (Minimum) Front 12" Back 0" Left Side (Filter Access) 24" Right Side 24" Below Unit 1 .
Cooling The following sequences of operation are based on using a standard single-stage cooling thermost at. WITH POWER TO UNIT AND THERMOST A T IN COOLING MODE.
12 Unitary Products Group 035-16703-001-A-0202 NORMAL MAINTENANCE WARNING: Prior to any of the following maintenance proce- dures, shut off all power to the unit, to avoid per- sonal injury . Periodic maintenance consists of changing or cleaning filters and general cleaning of the outdoor coil.
Unitary Products Group 13 035-16703-001-A-0202 FIG . 4 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPL Y) POWER SUPPLY POWER SUPPLY 208/230-1-60 208/230-1-60 USE COPPER USE COPPER CONDUCTORS ONLY C.
14 Unitary Products Group 035-16703-001-A-0202 FIG . 5 - TYPICAL WIRING DIAGRAM (230-3-60 POWER SUPPL Y).
Unitary Products Group 15 035-16703-001-A-0202 L2 L1 PO W ER SU PPL Y W / O U T EL EC H EAT 4 6 0 - 3 - 6 0 O R 5 7 5 -3 -6 0 US E CO P PE R CO NDUCT O RS ON L Y GN D LU G PO W ER SU PPL Y W / EL EC H.
16 Unitary Products Group 035-16703-001-A-0202 TYPICAL WIRING DIAGRAM NOTES TYPICAL WIRING DIAGRAM LEGEND HTR 5 ELECTRIC HEA TER (OPT . ACCSSR Y: 20 & 25 KW ELEC HEA T) HTR 4 ELECTRIC HEA TER (OPT .
Unitary Products Group 5005 York Drive, Norman Oklahoma 73069 Subject to change without notice. Printed in U.S.A. Copyright by York International Corporation 2001.
デバイスYork 1-1/2 THRU 5 TON (10 SEER)の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York 1-1/2 THRU 5 TON (10 SEER)をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork 1-1/2 THRU 5 TON (10 SEER)の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York 1-1/2 THRU 5 TON (10 SEER)の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York 1-1/2 THRU 5 TON (10 SEER)で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York 1-1/2 THRU 5 TON (10 SEER)を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork 1-1/2 THRU 5 TON (10 SEER)の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York 1-1/2 THRU 5 TON (10 SEER)に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork 1-1/2 THRU 5 TON (10 SEER)デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。