OUTDOOR SPLIT -SYSTEM AIR CONDITIONER MODELS: 10, 1 2, 13 AND 14 SEER 1 PHASE - 1.5 TO 5 T O NS 035-13606-003 Rev. A (202) T ABLE OF CONTENTS GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . 2 INSPECTION . . . . . . . . . . . . . . . . . . .
035-13606-003 Rev. A (202) 2 Unitary Products Group GENERAL INFORMA TION These outdoor units are designed to be connected to a matching UPG indoor coil with sweat connection lines. The se units are factory charged with refrigerant for a matching indoor coil plus 15 feet of fie ld supplied line.
035-13606-003 Rev. A (202) Unitary Products Group 3 A minimum clearance of 18 inches is required for service at the control panel and compre ssor compartments access. A 10 inch clearance is required for the air inlet to the outdoor coil around the pe rimeter of the uni t.
035-13606-003 Rev. A (202) 4 Unitary Products Group INST ALLA TION OUTDOOR U NIT After the site has been select ed, a solid base pad that will not shift or settle should be provided. Th e base pad should not come in contact with the foundat ion or side of the structur e because sound may be tran smitted to the residence.
035-13606-003 Rev. A (202) Unitary Products Group 5 RE-ASSEMBLING , BRAZING AND CLEANING OF JOINT CONNECTIONS Remove the Schrader V alv e cores from the service valves. Remove the plugs from the service valve fiel d tubing connec- tions. Clean the jo ints to be brazed.
035-13606-003 Rev. A (202) 6 Unitary Products Group REFRIGERANT V AL VE OPERA TION All models in this series have brass service va lves. These valves are not back seating. Opening or closing valve does not close service port. Service ports have Schrader valves for gauge connections.
035-13606-003 Rev. A (202) Unitary Products Group 7 LOW VOL T AGE Control wiring may vary depending upon the type of thermo- stat and furnace being connected. Low voltage wiring diagrams can be found with the furnace or air conditioning blower package installation instructions.
035-13606-003 Rev. A (202) 8 Unitary Products Group E SYSTEM CHARGE The factory charge in the outdoor unit includes enough charge for the unit a nd a most sold matched evaporator . Some indoor coil matches may requi re some additional charge. See T abular Data sheet provided in unit literature packet.
035-13606-003 Rev. A (202) Unitary Products Group 9 T able 3: SUPERHEA T V ALUE INDOOR WB ° F 1 OUTDOOR DB ° F 55 60 65 70 75 80 85 90 95 100 105 1 10 1 15 50 9 7 52 12 10 6 54 14 12 10 7 56 17 15 1.
035-13606-003 Rev. A (202) 10 Unitary Products Group 3. Measure and record the suction pressure at the su ction service valve port. 4. Using T a ble 4, note the superheat value corresponding to the intersecti on of the indoor wet b ulb and the outdoor dry bulb.
035-13606-003 Rev. A (202) Unitary Products Group 11 SER VICE RECORDS.
Subject to change without notice. Printe d in U.S.A. 035-13606-003 Rev. A (202) Copyright © by Y ork International Corp. 2002. All rights reserved. Supersedes: 035-13606-002, 550.
デバイスYork 13 AND 14 SEERの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York 13 AND 14 SEERをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork 13 AND 14 SEERの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York 13 AND 14 SEERの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York 13 AND 14 SEERで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York 13 AND 14 SEERを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork 13 AND 14 SEERの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York 13 AND 14 SEERに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork 13 AND 14 SEERデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。