FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 360101-XT G-A-0108 TECHNICAL GUIDE ® DESCRIPTION These packaged cooling air conditi oners are designed for outdoor installation. Only ut i lity and duct connections are required at the point of installation.
360101-XTG-A-0108 2 Johnson Controls Unitary Products TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 STANDARD FEATURES / BENEFITS . . . . . . . . . . . . . . . . . 1 FIELD-INSTALLED ACCESSORIES . .
360101-XTG-A-0108 Johnson Controls Unitary Products 3 STANDARD FEATURES/BENEFITS (CONT.) UTILITY CONNECTIONS MADE EASY - Electri c al utility knockouts are provided through the bottom as well as the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor.
360101-XTG-A-0108 4 Johnson Controls Unitary Products operation. Independe nt blade desig n insures p roper control and less than 1% leak rate. Includes hood an d me sh bird screen filter integrated into the ho od, dry bulb senso r and relie f damper.
360101-XTG-A-0108 Johnson Controls Unitary Products 5 SEER = Seasonal Energy Efficiency Ratio - the total coolin g output in BTU's during a normal annual usage period for cooling div ided by the total electric power input in watt-hours dur ing the same period.
360101-XTG-A-0108 6 Johnson Controls Unitary Products ALL SENSIBLE CAPACITIES T ABLE 3: COOLING CAP ACITIES - 1 -1/2 T ON (DEB018) TEMPERATURE OF AIR ON OUTDOOR COIL AIR ON INDOOR COIL 450 CFM 525 CFM 600 CFM 675 CFM 750 CFM WB °F WB °F WB °F WB °F WB °F 72 67 62 57 72 67 6 2 57 72 67 62 57 72 67 62 57 72 67 6 2 57 85 °F Net Cap MBH 18.
360101-XTG-A-0108 Johnson Controls Unitary Products 7 ALL SENSIBLE CAPACITIES T ABLE 4: COOLING CAP ACITIES - 2 T ON (DEB024) TEMPERATURE OF AIR ON OUTDOOR COIL AIR ON INDOOR COIL 600 CFM 700 CFM 800 CFM 900 CFM 1,000 CFM WB °F WB °F WB °F WB °F WB °F 72 67 62 57 72 67 6 2 57 72 67 62 57 72 67 62 57 72 67 6 2 57 85 °F Net Cap MBH 25.
360101-XTG-A-0108 8 Johnson Controls Unitary Products ALL SENSIBLE CAPACITIES T ABLE 5: COOLING CAP ACITIES - 2 -1/2 T ON (DEB030) TEMPERATURE OF AIR ON OUTDOOR COIL AIR ON INDOOR COIL 750 CFM 875 CFM 1,000 CFM 1,125 CFM 1,250 CFM WB °F WB °F WB °F WB °F WB °F 72 67 62 57 72 67 6 2 57 72 67 62 57 72 67 62 57 72 67 6 2 57 85 °F Net Cap MBH 32.
360101-XTG-A-0108 Johnson Controls Unitary Products 9 ALL SENSIBLE CAPACITIES T ABLE 6: COOLING CAP ACITIES - 3 T ON (DEB036) TEMPERATURE OF AIR ON OUTDOOR COIL AIR ON INDOOR COIL 900 CFM 1,050 1,200 1,350 1,500 WB °F WB °F WB °F WB °F WB °F 72 67 62 57 72 67 6 2 57 72 67 62 57 72 67 62 57 72 67 6 2 57 85 °F Net Cap MBH 34.
360101-XTG-A-0108 10 Johnson Controls Unitary Products ALL SENSIBLE CAPACITIES T ABLE 7: COOLING CAP ACITIES - 3 -1/2 T ON (DEB042) TEMPERATURE OF AIR ON OUTDOOR COIL AIR ON INDOOR COIL 1,050 CFM 1,225 1,400 1,575 1,750 WB °F WB °F WB °F WB °F WB °F 72 67 62 57 72 67 6 2 57 72 67 62 57 72 67 62 57 72 67 6 2 57 85 °F Net Cap MBH 40.
360101-XTG-A-0108 Johnson Controls Unitary Products 11 ALL SENSIBLE CAPACITIES T ABLE 8: COOLING CAP ACITIES - 4 T ON (DEB048) TEMPERATURE OF AIR ON OUTDOOR COIL AIR ON INDOOR COIL 1200 CFM 1400 CFM 1600 CFM 1800 CFM 2000 CFM WB °F WB °F WB °F WB °F WB °F 72 67 62 57 72 67 6 2 57 72 67 62 57 72 67 62 57 72 67 6 2 57 85 °F Net Cap MBH 49.
360101-XTG-A-0108 12 Johnson Controls Unitary Products ALL SENSIBLE CAPACITIES T ABLE 9: COOLING CAP ACITIES - 5 T ON (DEB060) TEMPERATURE OF AIR ON OUTDOOR COIL AIR ON INDOOR COIL 1200 CFM 1400 CFM 1600 CFM 1800 CFM 2000 CFM WB °F WB °F WB °F WB °F WB °F 72 67 62 57 72 67 6 2 57 72 67 62 57 72 67 62 57 72 67 6 2 57 85 °F Net Cap MBH 65.
360101-XTG-A-0108 Johnson Controls Unitary Products 13 Note: 1. D educt these resistance values from t he available external static pressure show n in the respective Blower Performance T able. 2. The pressure thru the economizer is greater for 100 % outdoor air then for 100% return air.
360101-XTG-A-0108 14 Johnson Controls Unitary Products * KW listed is for 240 volts, use tabl e at top of p age for 208 or 230 volts. T ABLE 12: ELECTRICAL DA T A (BASIC UNIT) Model DEB Volt Voltage Limitations 1 1. Rated in accordance with ARI St andard 110, utilization ran ge “A”.
360101-XTG-A-0108 Johnson Controls Unitary Products 15 FIGURE 3 - UNIT DIMENSIONS HIGH VO L TAGE CONN. “ x " DIA. KNOCKOUT 6 DRAIN “ NPTI CONDENS A TE LOW VO L TAGE CONN.
360101-XTG-A-0108 16 Johnson Controls Unitary Products FIGURE 4 - CENTER OF GRAVITY T ABLE 14: UNIT WEIGHTS Unit Size Shipping Weight Operating Weight Corner Weights Economizer (lbs.
360101-XTG-A-0108 Johnson Controls Unitary Products 17 TYPICAL APPLICATIONS FIGURE 5 - TYPICAL SLAB ON GROUND INSTALLATION FIGURE 6 - TYPICAL ROOF CURB INSTALLATION TO POWER SUPPL Y SUPPL Y AIR DUCT R.
360101-XTG-A-0108 18 Johnson Controls Unitary Products FIGURE 7 - ROOF CURB DIMENSIONS (8 ” Roof curb al so available) FIGURE 8 - ROOF CURB APPLICATION FRONT 1 1 WOOD NAILER 4 INSULA TED P ANELS 22 .
360101-XTG-A-0108 Johnson Controls Unitary Products 19 FIGURE 9 - TYPICAL WIRING DIAGRAM ( 208/230-1-60 POWER SUPPLY) DEB MODEL S 15695BASH0301 SEE DET AIL "A" T2 M1 - 2 DET AIL "A".
360101-XTG-A-0108 20 Johnson Controls Unitary Products MECHANICAL SPECIFICATIONS GENERAL DESCRIPTION Units shall be factory-assembl ed, single packaged, Electric Cooling units, desi gned for outdo or mounted installation .
360101-XTG-A-0108 Johnson Controls Unitary Products 21 4. Unit Controls: a. Unit shall contain a large, l ow voltage Te rmi nal Board for easy connection of fi eld low voltage wiring.
360101-XTG-A-0108 22 Johnson Controls Unitary Products.
360101-XTG-A-0108 Johnson Controls Unitary Products 23.
Subject to change without notice. Print ed in U. S.A. 360101-XTG-A-0108 Copyright © 2008 by Johnson Controls, In c. All rights rese rved. Supersedes: 263146-X TG-A-0206/036-21753-0 01-A-0206 Johnson .
デバイスYork AFFINITY 360101-XTG-A-0108の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York AFFINITY 360101-XTG-A-0108をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork AFFINITY 360101-XTG-A-0108の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York AFFINITY 360101-XTG-A-0108の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York AFFINITY 360101-XTG-A-0108で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York AFFINITY 360101-XTG-A-0108を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork AFFINITY 360101-XTG-A-0108の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York AFFINITY 360101-XTG-A-0108に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork AFFINITY 360101-XTG-A-0108デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。