GENERAL The outdoor units are completely piped and wired at the fac- tory and are shipped ready for immediate installation. Only the interconnecting liquid and suction lines, sight glasses, control wiring, and the main power wiring are required to complete the installation.
2 Unitary Products Group 035-16192-001-A-1001 E 1 F B 2 5 8 A PRODUCT NOMENCLATURE PRODUCT GENERATION 1 = First Generation PRODUCT CA TEGOR Y E = S plit-System Heat Pump Outdoor Unit PRODUCT IDENTIFIE.
LIMIT ATIONS These units must be installed in accordance with all national and local safety codes. If no local codes apply , installation must conform with the appropriate national codes. See T able 1 for unit application data. Units are designed to meet National Safety Code S tandards.
CAUTION: LENGTH OF FORKS MUST BE A MINIMUM OF 54" (when lifting from the compressor end of the unit) and a MINIMUM OF 42" (when lifting from the front or rear of the unit). Remove the nesting brackets from the four corners on top of the unit.
Unitary Products Group 5 035-16192-001-A-1001 INDOOR UNIT OUTDOOR UNIT TERMINALS ON HEAT PUMP TH ERMOSTAT 1 1 Control wiring (24-v olt) refe r to elect rical d ata to deter mine th e prope r wire s ize. T ABLE 3 - ELECTRICAL DA T A 1 Maximum fuse or maximum circuit breaker (HACR type per NEC).
6 Unitary Products Group 035-16192-001-A-1001 All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
and/or drafts. Circulation of air to the thermost at should not be blocked by curtains, drapes, furniture, partitions, etc. Some installations may require a locking cover to protect the thermostat from tampering and/or damage.
3. T urn the stem in (or clockwise) between 1/4 and 1/2 turn to open the access port. As soon as some internal pressure is relieved, close the ac- cess port.
4. After the disc has been removed, burnish the external sur - faces and clean the internal surfaces as outlined above. 5. Move the dry nitrogen supply back to the access port on the liquid line service valve.
10 Unitary Products Group 035-16192-001-A-1001 FIG . 5 - EXTENDING THE SERVICE POR TS ALTERNA TE CHARGING METHODS If you are starting a unit when the ambient temperature is higher or lower than those shown in Figures 7 through 15, either of the following methods may be used.
GENERAL During the cooling cycle, when the reversing valve solenoids becomes energized, operation will be the same as any conven - tional air conditioning system.
through the defrost control boards and safety switches to energize relays RY1 and R Y2, which in turn will energize contactors 1M & 3M, starting the compressors. Contactors 2M and 4M are energized through the NO contact s on auxil - iary contactors 1M-AUX and 3M-AUX in order to start the outdoor fan motors.
OPERATION BELOW 0 ° F OUTDOOR TEMPERA - TURE 1. At 0 ° F outdoor temperature, the low temperature compres - sor cutoff thermost at TH1 and TH3 contacts 1 and 3 will open, de-energizing contactor 1M and 3M which shuts down the compressor . Contacts 1 and 2 of thermostat TH1 and TH3 are closed when contacts 1 and 3 are open.
CRANKCASE HEA TER The crankcase heaters must be energized at least 8 hours bef - ore starting the compressor . T o energize the crankcase heat - ers, the main disconnect switch must be closed. During this 8 hour period, the system switch on the room thermostat must be “OFF” to prevent the compressor from starting.
Unitary Products Group 15 035-16192-001-A-1001 150 200 250 300 350 400 50 60 70 80 90 S u c t i o n P r essu re ( p si g ) D i sc h a rg e P ressu re ( p si g ) 115 °F 105 °F 95 °F 85 °F 75 °F OD.
16 Unitary Products Group 035-16192-001-A-1001 FIG . 9 - HEA TING MODE CHARGING CHART A T 4800 CFM - EFB180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 S u c t i o n P ressu re ( p si g ) D i sc h a rg e P ressu re ( p si g ) 80 °F 70 °F 60 °F IDDB FIG .
Unitary Products Group 17 035-16192-001-A-1001 FIG . 1 1 - HEA TING MODE CHARGING CHART A T 6600 CFM - EFB180A 50 100 150 200 250 300 350 400 30 40 50 60 70 80 90 S u c ti o n P ressu re ( p si g ) D i sc h a rg e P ressu re ( p si g ) 80 °F 70 °F 60 °F IDDB FIG .
18 Unitary Products Group 035-16192-001-A-1001 FIG . 13 - HEA TING MODE CHARGING CHART A T 7000 CFM - EFB240A 50 100 150 200 250 300 350 30 40 50 60 70 80 90 S u c t i o n P ressu re ( p si g ) D i sc h a rg e P ressu re ( p si g ) 80 °F 70 °F 60 °F IDDB FIG .
NOTES Unitary Products Group 19 035-16192-001-A-1001.
Unitary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright by Y ork International Corporation 2001.
デバイスYork E1FB180の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York E1FB180をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork E1FB180の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York E1FB180の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York E1FB180で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York E1FB180を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork E1FB180の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York E1FB180に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork E1FB180デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。