LD1 1555 INST ALLA TION, OPERA TION, & MAINTENANCE F AN COIL AIR CONDITIONERS NEW RELEASE Form 1 15.20-NOM6 (1 106) ***** W ARNING TO INST ALLER, SERVICE PERSONNEL AND OWNER ***** Altering the pro.
JOHNSON CONTROLS 2 FORM 1 15.20-NOM6 (1 106) T ABLE OF CONTENTS FIG. 2 – PHYSICAL DIMENSIONS (INCHES) Reference Documents: • Parts List, Fan Coil Air Conditioners Form 1 15.20-RP2 (Latest) These documents can be ordered through Publications Dept. or downloaded @ http://intranet.
3 JOHNSON CONTROLS FORM 1 15.20-NOM6 (1 106) INST ALLA TION RECEIVING Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspect ion of all carton s shoul d be ma de imme diatel y .
JOHNSON CONTROLS 4 FORM 1 15.20-NOM6 (1 106) INST ALLA TION 2 . Frame around the perimeter of the unit as required for securing the drywall. See T able 1 below for drywall openings.
5 JOHNSON CONTROLS FORM 1 15.20-NOM6 (1 106) INST ALLA TION DUCTWORK Ductwork recommendations are as follows: • Insulate to prevent condensation during cooling. • Size to the unit openings are generally ac cept abl e bu t ar e de ter mine d by the eng ine erin g drawings.
JOHNSON CONTROLS 6 FORM 1 15.20-NOM6 (1 106) T able 2 - ELECTRICAL DA T A UNIT MODEL KW TOT AL AMPS MIN. CIR. AMP ACITY MAX.OVERCURRENT PROTECTION 240V 208V 240V 208V 240V 208V 240V 208V 4CWE 0 0 0.0 1.1 N/A N/A N/A N/A N/A 1 1 0.8 5.3 4.7 7 6 15 15 2 2 1.
7 JOHNSON CONTROLS FORM 1 15.20-NOM6 (1 106) PIPING All piping connections are 5/8" OD copper tubing (see Fig.4). The supply and return piping must be adequately sized to meet the design water flow requirements as spec ified for the speci fic insta llatio n .
JOHNSON CONTROLS 8 FORM 1 15.20-NOM6 (1 106) Drain Piping Con dens ate drai n lin es mu st be inst alle d wit h ade quat e slope away from the unit to assure positive drainage.
9 JOHNSON CONTROLS FORM 1 15.20-NOM6 (1 106) SEQUENCE OF OPERA TION YCW With a Chilled W ater Coil The unit will respond to a cooling command from the thermostat by powering a water control valve open. The fan will operate at the speed selected at the thermostat.
JOHNSON CONTROLS 10 FORM 1 15.20-NOM6 (1 106) MAINTENANCE MOTOR The blower motor should be cleaned annually and if it has oiling ports, it should be oiled with a good grade of SAE 20 oil. Normally a few drops of oil in each bearing is sufficient. COIL The coil must be kept clean by any of the following methods.
1 1 JOHNSON CONTROLS FORM 1 15.20-NOM6 (1 106) This Page Intentionally Left Blank.
T ele. 800-861-1001 www .Y ork.com P .O. Box 1592, Y ork, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA T ele. 800-861-1001 P .O. Box 1592, Y ork, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA T ele.
デバイスYork LD11555の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York LD11555をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork LD11555の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York LD11555の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York LD11555で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York LD11555を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork LD11555の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York LD11555に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork LD11555デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。