YorkメーカーTCGF24 THRU 60の使用説明書/サービス説明書
ページ先へ移動 of 28
TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 14.5 SEER – R-410A MODE LS: TCGF24 THRU 60 (2 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuou s product improvem ent, specifications are subject to change without notice. Visit us on the web at www .york.
413434-LTG-E-0909 2 Johnson Controls Unitary Products All dimensions are in inche s. They are subject to change with- out notice. Certified dimensions will be provi ded upon request.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refrigerant for the co ndenser , the smallest evaporator and 15 feet of interconnecting line tub ing.
413434-LTG-E-0909 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 14.5 SEER AC WITH MA TCGF24S41S1 MA08B 17 FC/MC24B 800 24.8 17.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 5 14.5 SEER AC WITH MV - V ARIABLE SPEED (Continued) TCGF36S41S1 MV12B 17 FC/MC35B 1200 35.0 25.8 15.00 12.50 MV16C 21 FC/MC35C 1200 35.2 26.0 15.75 13.00 MV12B 17 FC/MC36B 1200 34.8 25.4 15.00 12.
413434-LTG-E-0909 6 Johnson Controls Unitary Products — = Not applicable. TCGF30S41S1 AHP36 21 – 1000 29.6 21.4 14.30 12.20 AHX30 17 – 1025 29.6 22 .0 15.25 13.00 AHX36 21 – 1005 30.2 22 .6 16.25 13.00 AHX42 21 – 990 30.6 22.8 16.50 13.25 AHX48 24 – 1090 31.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - Upflow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TE D CFM NET MBH SEER 1 EER TOT AL SE NS . TCGF24S41S1 600 - 1000 14,17 FC/MC/PC24 800 24.
413434-LTG-E-0909 8 Johnson Controls Unitary Products COOLING CAP ACITY - With High Efficiency Motor Fu rnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 14.5 SEER AC WITH V ARIABLE SPEED FURNACES 2 TCGF24S41S1 T*(8,L)X*A12 FC/MC/PC24A 14 775 25.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 9 TCGF24S41S1 (L*9C/T*9V)*B12 FC/MC/PC35B 17 815 24.0 17.0 15.75 13.25 L*(8,L)C*A12 FC/MC/PC36A 14 805 24.0 17.0 16.00 13.50 L*(8,L)C*B12 FC/MC/PC36B 17 765 24.0 16.7 15.75 13.50 (L*9C/T*9V)*B12 FC/MC/PC36B 17 815 24.
413434-LTG-E-0909 10 Johnson Controls Unitary Products TCGF30S41S1 T*9X*C16 FC/MC/PC48C 21 1075 30.8 23.4 16.00 13.25 T*9X*C20 FC/MC/PC48C 21 745 29.0 20.2 16.00 13.25 T*9X*D20 FC/MC/PC48D 24 780 29.2 20.6 16.00 13.25 T*(8,L)X*A12 UC30A 14 1035 29.4 21.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 11 TCGF36S41S1 T*(8,L)X*B12 FC/MC/PC35B 17 1290 34.6 25.8 15.25 12.75 T*(8,L)X*C16 FC/MC/PC35C 21 1 105 34.0 24.4 15.50 12.75 T*(8,L)X*C20 FC/MC/PC35C 21 1225 34.4 25.4 15.50 12.75 T*9X*B12 FC/MC/PC35B 17 1265 34.
413434-LTG-E-0909 12 Johnson Controls Unitary Products TCGF36S41S1 L*(8,L)C*C20 FC/MC/PC43C 21 1 190 35.0 25.6 15.75 13.00 (L*9C/T*9V)*C16 FC/MC/PC43C 21 1240 34.8 25.6 15.25 12.75 (L*9C/T*9V)*C20 FC/MC/PC43C 21 1200 35.0 25.6 15.50 13.00 L*(8,L)C*C16 FC/MC/PC48C 21 1210 35.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 13 TCGF42S41S1 T*9X*D20 HD4 8 24 1460 47.5 27.4 14.75 12.50 T*(8,L)X*C16 UC48C 21 1400 40.0 29.8 14.90 12.65 T*(8,L)X*C20 UC48C 21 1515 40.5 30.8 14.90 12.65 T*9X*C16 UC48C 21 1425 39.5 29.6 14.50 12.
413434-LTG-E-0909 14 Johnson Controls Unitary Products TCGF48S41S1 T*(8,L)X*C16 FC/MC/PC48C 21 1600 47.0 33.8 14.50 12.25 T*(8,L)X*C20 FC/MC/PC48C 21 1660 47.5 33.8 14.75 12.50 T*9X*C16 FC/MC/PC48C 21 1565 47.0 33 .8 14.50 12.25 T*9X*C20 FC/MC/PC48C 21 1615 47.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 15 TCGF48S41S1 (L*9C/T*9V)*C16 HD60 21 1590 47.0 33.4 14.75 12.50 (L*9C/T*9V)*C20 HD60 21 1655 47.0 33.4 14.75 12.50 (L*9C/T*9V)*D20 HD60 24 1615 47.0 33.4 14.75 12.50 TCGF60S41S1 T*(8,L)X*C 20 FC/PC60C 21 1605 55.
413434-LTG-E-0909 16 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. Off Cycle Timer Delay - Provides a 5-minute off cycle to pre- vent rapid recycling of the compressor . Hard St a rt Kit - Required when using TXV indoor coil.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
413434-LTG-E-0909 18 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC24A 1.04 1.07 0.92 T*(8,L)X*B12 FC/MC/PC24B 1.05 1.10 0.92 T*9X*B12 FC/MC/PC24B 1.04 1.07 0.92 T*(8,L)X*A12 FC/MC/PC30A 1.04 1.07 0.92 T*(8,L)X*B12 FC/MC/PC30B 1.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 19 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
413434-LTG-E-0909 20 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*A12 FC/MC/PC30A 1.00 1.01 0.94 T*(8,L)X*B12 FC/MC/PC30B 0.99 0.98 0.91 T*9X*B12 FC/MC/PC30B 1.00 1.02 0.94 T*(8,L)X*A12 FC/MC/PC32A 0.99 0.98 0.95 T*(8,L)X*B12 FC/MC/PC35B 1.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 21 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
413434-LTG-E-0909 22 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*B12 FC/MC/PC35B 1.01 1.03 0.95 T*(8,L)X*C16 FC/MC/PC35C 0.99 0.97 0.91 T*(8,L)X*C20 FC/MC/PC35C 1.00 1.01 0.92 T*9X*B12 FC/MC/PC35B 0.99 1.00 0.95 T*9X*C16 FC/ MC/PC35C 1.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
413434-LTG-E-0909 24 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*B12 FC/MC/PC43B 0.99 0.98 0.94 T*(8,L)X*C16 FC/MC/PC43C 1.02 1.03 0.95 T*(8,L)X*C20 FC/MC/PC43C 1.01 1.02 0.94 T*9X*B12 FC/MC/PC43B 0.97 0.94 0.94 T*9X*C16 FC/ MC/PC43C 1.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 25 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
413434-LTG-E-0909 26 Johnson Controls Unitary Products Furnaces Coils T .C. S.C. KW T*(8,L)X*C16 FC/MC/PC48C 1.01 1.02 0.96 T*(8,L)X*C20 FC/MC/PC48C 1.01 1.02 0.95 T*9X*C16 FC/ MC/PC48C 1.01 1.02 0.96 T*9X*C20 FC/ MC/PC48C 1.01 1.02 0.95 T*9X*D20 FC/ MC/PC48D 1.
413434-LTG-E-0 909 Johnson Controls Unitary Pro ducts 27 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between .
Subject to change without notice. Publishe d in U.S.A. 413434-LTG-E-0909 Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 413434-LTG-D-0509 Johnson Controls Unit ary Produc.
デバイスYork TCGF24 THRU 60の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York TCGF24 THRU 60をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork TCGF24 THRU 60の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York TCGF24 THRU 60の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York TCGF24 THRU 60で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York TCGF24 THRU 60を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork TCGF24 THRU 60の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York TCGF24 THRU 60に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork TCGF24 THRU 60デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。