TECHNICAL GUIDE LX SERIES SPLIT -SYSTEM AIR CONDITIONERS 13 SEER – R- 410A – 1 PHASE (1.5 THRU 5 NOMINAL TONS) MODELS: YCJD18 THRU 60 Due to continuous pro duct improvement, spec ifications are subject to cha nge with ou t notice. Visit us on the web at www .
840569-YTG-A-0612 2 Johnson Controls Unitary Products All dimensions are in inche s. They are subject to ch ange with- out notice. Certified dimensions will be provi ded upon request.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 3 System Charge for V arious Matched Sy stems Out door Unit YCJD18 S41S1(H)(E) YCJD24 S41S1(H)(E) YCJD30 S41S1(H)(E) YCJD36 S41S1(H)(E) YCJD42 S41S2(H)(E) YCJD48 S41S1(H)(E) YCJD60 S41S1(E) Required Ori fice or TXV 1 , 2 0.
840569-YTG-A-0612 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the out door unit, the smallest matc hed indoor unit, and 15 feet of interconnect i ng lin e tubing.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL WIDTH RA TED CFM NET MBH SEER EER TOT AL SE N S. 13 SEER AC WITH AIR HANDLERS YCJD18S41S1(H)(E) AHE18B 17.
840569-YTG-A-0612 6 Johnson Controls Unitary Products YCJD36S41S1(H)(E) AHE36C 21.0 – 1 190 35.6 25.4 14.25 12 .00 AHE42D 24.5 – 1 180 35.8 25.8 14.50 12 .25 AHP36 21.0 – 1235 35.0 24.8 13.00 1 1.00 AHP42 21.0 – 1255 35.0 24.8 13.00 1 1.00 AHR36B 17.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 7 — = Not applicable. MA Modular Air Handlers use Coil Only Ratings. YCJD48S41S1(H)(E) AHE48D 24.5 – 1600 47.0 34.6 13.75 1 1.50 AHP48 24.5 – 167 5 48.0 34.4 13.00 1 1.00 AHP60 24.5 – 160 0 48.
840569-YTG-A-0612 8 Johnson Controls Unitary Products MA Modular Air Handlers use Coil Only Ratings. PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Rating s. COOLING CAP ACITY - Up flow , Downflow & Horizo nt al Furnaces and Coils (Coil Only Ratings) UNIT MODEL COIL CFM RANGE (MIN.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 9 COOLING CAP ACITY - With High Efficiency Motor Furna ces UNIT MODEL FURNACE COIL MODEL 1 COOLING MODEL WIDTH RA TED CFM NET MBH SEER EER TOT AL SE N S. 13 SEER AC WITH HIGH EFFICIENCY MOTOR FURNACES 2 YCJD18S41S1(H)(E) T*(8,L)V*A12 14.
840569-YTG-A-0612 10 Johnson Controls Unitary Products YCJD24S41S1(H)(E) Y*(8,L)C*A12 14.5 UC36A 805 23.6 16 .6 13.80 1 1.50 Y*(8,L)C*B12 17.5 FC/MC/PC35B 760 24.0 16.8 14.00 12 .00 Y*(8,L)C*B12 17.5 FC/MC/PC36B 765 24.0 17.0 14.00 12 .00 Y*(8,L)C*B12 17.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 11 YCJD36S41S1(H)(E) T*(8,L)V*A12 14.5 FC/MC/PC37A 980 33.8 23.0 13.50 1 1.00 T*(8,L)V*B12 17.5 FC/MC/PC43B 1210 35.2 25.2 13.50 1 1.00 T*(8,L)V*C16 21.0 FC/MC/PC43C 1205 35.6 25.4 14.00 1 1.50 T*(8,L)V*C16 21.
840569-YTG-A-0612 12 Johnson Controls Unitary Products YCJD42S41S2(H)(E) T*(8,L)V*B12 17.5 FC/MC/PC43B 1270 41.0 28.8 13.25 1 1.25 T*(8,L)V*C16 21.0 FC/MC/PC43C 1390 42.0 30 .2 13.50 1 1.50 T*(8,L)V*C16 21.0 FC/MC/PC48C 1330 42.0 29 .8 13.50 1 1.50 T*(8,L)V*C16 21.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 13 YCJD42S41S2(H)(E) T*9(C,V)*C20 21.0 FC64D 1445 42.0 30.8 13.75 1 1.75 T*9(C,V)*C20 21.0 UC48C 1430 42.0 30.2 13.25 1 1.25 T*9(C,V)*C20 21.0 UC60C 1445 41.5 29.8 13.00 1 1.25 T*9(C,V)*D20 24.5 FC/MC/PC48D 1450 42.
840569-YTG-A-0612 14 Johnson Controls Unitary Products YCJD42S41S2(H)(E) Y*(8,L)C*C20 21.0 UC60C 1410 42.0 30.0 13.50 1 1.50 Y*9C*C16 21.0 FC/MC/PC43C 1360 42.0 30 .0 13.25 1 1.25 Y*9C*C16 21.0 FC/MC/PC48C 1395 42.0 30 .4 13.50 1 1.50 Y*9C*C16 21.0 FC/MC/PC48D 1395 42.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 15 PSC furnaces, such as the TG8S, TG LS, and TG9S, use Coil Only Ratings. YCJD48S41S1(H)(E) Y*9C*C20 21.0 FC/MC/PC48C 1655 48.0 34.8 13.20 1 1.00 Y*9C*C20 21.0 FC/PC60C 1655 48.0 35.2 13.10 1 1.00 Y*9C*D20 24.
840569-YTG-A-0612 16 Johnson Controls Unitary Products ACCESSORIES Refer to Price Manual for specific model numbers. Off Cycle Timer Delay - Provides a 5-minute off cycle to pre- vent rapid recycling of the compressor . St art Assist Kit (S1-2SA067*) - Provides in creased starting torque for areas with low voltage.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
840569-YTG-A-0612 18 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 19 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC32A 1.00 1.02 0.96 T*(8,L)V*A12 FC/MC/PC36A 1.00 1.01 0.92 T*(8,L)V*A12 FC/MC/PC37A 1.00 1.02 0.92 T*(8,L)V*A12 UC36A 0.98 0.99 0.94 T*(8,L)V*B12 FC/MC/PC35B 1.
840569-YTG-A-0612 20 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 21 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC32A 1.01 1.04 1.01 T*(8,L)V*A12 FC/MC/PC37A 1.03 1.04 0.98 T*(8,L)V*B12 FC/MC/PC35B 1.02 1.02 0.98 T*(8,L)V*B12 FC/MC/PC43B 1.03 1.05 0.95 T*(8,L)V*C16 FC/MC/PC35 C 1.
840569-YTG-A-0612 22 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 23 Furnaces Coils T .C. S.C. KW T*(8,L)V*A12 FC/MC/PC37A 0.97 0.93 0.97 T*(8,L)V*B12 FC/MC/PC43B 1.01 1.02 1.01 T*(8,L)V*C16 FC/MC/PC43C 1.02 1.02 0.97 T*(8,L)V*C16 FC/MC/PC48C 1.03 1.05 0.94 T*(8,L)V*C16 UC48C 0.
840569-YTG-A-0612 24 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 25 T*(8,L)V*C20 FC/PC60C 1.01 1.01 0.95 T*(8,L)V*C20 FC64D 1.01 1.03 0.93 T*(8,L)V*C20 UC48C 1.01 1.01 0.95 T*(8,L)V*C20 UC60C 1.01 1.01 0.97 T*(8,L)X*B12 FC/MC/PC43B 1.00 0.99 0.96 T*(8,L)X*C16 FC/MC/PC43C 1.
840569-YTG-A-0612 26 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween.
840569-YTG-A-0612 Johnson Controls Unitary Pro ducts 27 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 7.
Subject to change without notice. Published in U .S.A. 840569-YTG-A-0612 Copyright © 2012 by Johnson Controls, Inc. All rights reserved. Supersedes: 561908-YTG-D-0611 Y o rk International Corp.
デバイスYork YCJD18 THRU 60の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
York YCJD18 THRU 60をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはYork YCJD18 THRU 60の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。York YCJD18 THRU 60の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。York YCJD18 THRU 60で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
York YCJD18 THRU 60を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はYork YCJD18 THRU 60の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、York YCJD18 THRU 60に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちYork YCJD18 THRU 60デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。