R600 IP/ZW

Technical documentation Water heater & swimming pool boilers Technische Dokumentation Brauchwasser- und Schwimmbadkessel Technische documentatie Tapwater- en zwembadketel Documentation technique Chaudière ECS et piscine Documentazione tecnica Caldaia per acqua calda e piscina

Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 1
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 2
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 3
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 4
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 5
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 6
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 7
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 8
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 9
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 10
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 11
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 12
Elco R600 IP-ZW — R600 IP/ZW diagram (page 1)
図 13

DOC1066

Page 2 of the Elco R600 IP-ZW user manual — R600 IP/ZW
2ページ · クリックして拡大
2ページ

R600 IP/ZW

Technical documentation Water heater & swimming pool boilers

Page 3 of the Elco R600 IP-ZW user manual — Technical documentation Water heater & swimming pool boilers
3ページ · クリックして拡大
3ページ
R601R602R603R604R605R606R607 Nominal heat output at 80-60ºC max/min*kW142.1/23.3190.1/39.5237.2/39.5285.2/39.5380.2/76.6475.3/76.6539.0/76.6 Nominal heat output at 75-60ºC max/min*kW142.2/23.5190.3/39.5237.4/39.5285.5/39.5380.6/76.6475.8/76.6539.6/76.6 Nominal heat output at 40/30ºC max/min*kW150.7/26.7201.6/45.2251.4/45.1302.3/45.2403.1/87.7503.9/87.7571.5/87.7 Nominal heat input Hi max/min*kW145.0/24.5194.0/41.5242.0/41.5291.0/41.5388.0/80.5485.0/80.5550.0/80.5 Efficiency at 80/60ºC%98.0 Efficiency at 40/30ºC%103.9 Annual efficiency (NNG 75/60ºC)%106.8 Annual efficiency (NNG 40/30ºC)%110.4 Standstill losses (T = 70ºC) water%0.210.180.170.160.150.140.13 Max. condensate flowl/h11151922303742 Gas consumption H-gas max/min (10,9 kWh/m3)m3/h13.3/2.317.8/3.822.2/3.826.7/3.835.6/7.444.5/7.450.5/7.4 Gas consumption L-gas max/min (8,34 kWh/m3)m3/h17.4/2.923.2/5.029.0/5.034.9/5.046.5/9.758.2/9.766.0/9.7 Gas consumption LL-gas max/min (8,34 kWh/m3)m3/h17.4/2.923.2/5.829.0/5.834.9/5.846.5/11.258.2/11.266.0/11.2 Gas consumption LPG max/min (12,8 kWh/kg)kg/h11.3/1.915.2/3.218.9/3.222.7/3.230.3/6.337.9/6.343.0/6.3 Gas pressure H-gasmbar20 Gas pressure L/LL-gasmbar25 Gas pressure LPGmbar30/50 Maximum gas pressurembar100 Fluegas temperature at 80/60ºC max/minºC78/61 Fluegas temperature at 40/30ºC max/minºC56/30 Fluegas quantity max/min*m3/h238/40318/69397/69477/69636/134795/134901/134 CO level natural gas max/min 2%10.2/9.4 CO level LPG max/min 2%11.9/10.0 NOx level max/minmg/kWh35/15 CO level max/minmg/kWh14/8 Max. permissible flue resistance max/minPa160/10160/10200/10200/10200/10250/10250/10 Water volumel27313561687582 Water pressure max/minbar8/1 Electrical connectionV230/400 FrequencyHz50 Mains connection fuseA10 IP class-IP20 Power consumption boiler max/min (excl. pump)W158/43200/35230/35260/35470/61650/61770/61 Power consumption DHW pump (optional)W24534047047072011501550 Power consumption DHW bypass pumpW245245245245380460530 Power consumption swimming pool pump (optional)W55090015001100220030003000 Weight (empty)kg295345400465535590650 Noise level at 1 meter distancedB(A)59 Ionisation current minimumµA6 PH value condensate-3.2 CE certification code-CE-0063BS3840 Water connections-R2"DN65 PN16 Gas connection-R3/4"R1"R1.1/2" Flue gas connectionmm150200250 Air intake connection (for room sealed use)mm130150200 Condensate connectionmm22

* min load on gasses H/L/LPG. For type R602-R607 on LL-gas min value is 15% higher.

Page 4 of the Elco R600 IP-ZW user manual — 5 (D1)
4ページ · クリックして拡大
4ページ
Elco R600 IP-ZW — 7 (D2) diagram (page 4)
図 14

7 (D2)

B3 B2

B

Elco R600 IP-ZW — 7 (D2) diagram (page 4)
図 15
Elco R600 IP-ZW — 7 (D2) diagram (page 4)
図 16
Elco R600 IP-ZW — 7 (D2) diagram (page 4)
図 17

5 (D1)

2 (G)

3 (W1)

H

H2

4 (W2)

B4

DimensionsR601R602R603R604R605R606R607 L mm1105126014701220143515851735 L2 mm127.5127.5137.5137.5187.5187.5187.5 H mm1480148015001500150015001500 H2 mm1120113011301150124512451245 B mm670670670770770770770 B2 mm225235235235260260260 B3 mm260260260310310310310 B4 mm130130130245245245245 D1 mm130150150150200200200 D2 mm150150200200250250250 W1 R” / DNR2”R2”R2”DN65 PN16 W2 R” / DNR2”R2”R2”DN65 PN16 G RR3/4”R1”R1”R1”R1 1/2”
Elco R600 IP-ZW — 5 (D1) diagram (page 4)
図 18
Elco R600 IP-ZW — 5 (D1) diagram (page 4)
図 19

1 Electrical connections 2 Gas supply 3 Water supply 4 Water return 5 Air intake 6 Boiler water drain valve 1/2” 7 Flue gas outlet 8 Condensate drain flexible hose 25mm diam.

413 490

Page 5 of the Elco R600 IP-ZW user manual — 5 (D1)
5ページ · クリックして拡大
5ページ
Elco R600 IP-ZW — 7 (D2) diagram (page 5)
図 20

7 (D2)

B3 B2

B

Elco R600 IP-ZW — 7 (D2) diagram (page 5)
図 21
Elco R600 IP-ZW — 7 (D2) diagram (page 5)
図 22
Elco R600 IP-ZW — 7 (D2) diagram (page 5)
図 23

5 (D1)

2 (G)

3 (W1)

H

H2

4 (W2)

B4

DimensionsR601R602R603R604R605R606R607 L mm1105126014701220143515851735 L2 mm127.5127.5137.5137.5187.5187.5187.5 L3 mm425425425390390510510 H mm1480148015001500150015001500 H2 mm1120113011301150124512451245 B mm670670670770770770770 B2 mm225235235235260260260 B3 mm260260260310310310310 B4 mm130130130245245245245 D1 mm130150150150200200200 D2 mm150150200200250250250 W1 R” / DNR2”R2”R2”DN65 PN16 W2 R” / DNR2”R2”R2”DN65 PN16 G RR3/4”R1”R1”R1”R1 1/2”
Elco R600 IP-ZW — 5 (D1) diagram (page 5)
図 24
Elco R600 IP-ZW — 5 (D1) diagram (page 5)
図 25

1 Electrical connections 2 Gas supply 3 Water supply 4 Water return 5 Air intake 6 Boiler water drain valve 1/2” 7 Flue gas outlet 8 Condensate drain flexible hose 25mm diam. 9 Bypass pump

413 490

Page 6 of the Elco R600 IP-ZW user manual — 7 (D2)
6ページ · クリックして拡大
6ページ

General This document is meant to be used in addition to the R600 heating boiler documentation, in case of having a R600 water heater or swimming pool version. This document only contains the differences in construction and application to the heating boiler version. General information on the boiler (transport, commissioning, maintenance, etc.) can be found in the heating boiler documentation. Technical description The R600 water heater and swimming pool boilers are applicable for direct heating of sanitary hot water or swimming pool water without using a hydraulic separation (f.e. plate heat exchanger) in the system. This special version of the R600 boiler series is mainly identical to the heating boiler version, except for the manifolds on the heat exchanger. These are made from stainless steel instead of cast iron, assuring the hydraulic side of the boiler being fully made of stainless steel and allowing the boiler to be flushed with the sanitary hot water or swimming pool water directly.

Elco R600 IP-ZW — 7 (D2) diagram (page 6)
図 26
Elco R600 IP-ZW — 7 (D2) diagram (page 6)
図 27
Elco R600 IP-ZW — 7 (D2) diagram (page 6)
図 28
Page 7 of the Elco R600 IP-ZW user manual — 7 (D2)
7ページ · クリックして拡大
7ページ

Water quality Water heater As a water heater is constantly flushed with fresh water, there are restrictions to the maximum flow temperature related to the hardness of the water. The following table indicates the maximum flow temperatures for different water hardness values. Not respecting these values can lead to damage of the heat exchanger.

Maximum flow temperature related to water hardness Water hardnessMax. setpoint (P1)Temp. limiter settingHigh limit setting [ºdH][ºf][ºC][ºC][ºC] 0 - 50 - 99097100 5 - 159 - 27859295 15 - 2027 - 36808790 20 - 2836 - 50606770
Elco R600 IP-ZW — 7 (D2) diagram (page 7)
図 29
Hot water tapping volumes (cold water = 10ºC) Outputflow @50ºCflow @60ºCflow @65ºCflow @70ºCflow @80ºCflow @90ºC [kW][l/min][l/min][l/min][l/min][l/min][l/min] R60114251.140.837.134.029.225.5 R60219068.354.749.745.539.034.2 R60323785.268.262.056.848.742.6 R604285102.582.074.568.358.651.2 R605380136.6109.399.491.178.168.3 R606475170.8136.6124.2113.997.685.4 R607539193.8155.0141.0129.2110.796.9
Elco R600 IP-ZW — 7 (D2) diagram (page 7)
図 30
Page 8 of the Elco R600 IP-ZW user manual — 7 (D2)
8ページ · クリックして拡大
8ページ

Hydraulic connection Water heater The R600 water heater must be installed in such a way, that a minimum water flow rate of 30% of the nominal flow rate can be assured at all times when the burner is switched on. The R600 water heater can increase the water temperature by maximum 17K at once. This means that the water has to cycle through the boiler several times when f.e. cold water of 10ºC has to be heated up to 60ºC (3 times). This is normally done by installing the R600 water heater in combination with a buffer tank. The flow rate from the tank to the water heater and back can then be secured by the (primary) water heater pump. The table below shows the nominal water flow data at a ∆T of 17K, plus the pump data of the (optional) pump kit for each type of water heater.

Water flow data water heater ∆TNominal flow rateBoiler resistancePump typeVoltageCurve settingPump headResidual pump head [K][m3/h][kPa][-][V][-][kPa][kPa] R601177.214UPS 32-80B2303 -34 -20 - R6029.525UPS 32-120FB2303 261 3036 5 R60312.039UPS 40-120FB2303 264 4825 9 R60414.421UPS 40-120FB2303 250 3029 9 R60519.237UPS 50-120FB4003 264 4727 10 R60624.058UPS 65-120FB4003 -76 -18 - R60727.276UPS 65-180FB4003 -104 -28 -
Elco R600 IP-ZW — 7 (D2) diagram (page 8)
図 31
Page 9 of the Elco R600 IP-ZW user manual — Q2
9ページ · クリックして拡大
9ページ

Bypass water heater When a higher temperature increase than 17K should be achieved directly within one step, this can be done by using a water heater with internal bypass. The built-in bypass pump secures a minimum flow rate through the water heater. When using a water heater with bypass, the internal pump will not transport the hot water from the water heater to the system. Therefore a system pump should be selected, based on the desired ∆T. Below you’ll find a schematic drawing of the situation, plus two tables with all the necessary information for the selection of the system pump. Please be aware that for the calculation method an additional resistance of 10 kPa for the system piping is included.

Q1+Q2

R1

P1

Q1

P1 = bypass pump P2 = system pump

Q2

R2

P2

Elco R600 IP-ZW — Q2 diagram (page 9)
図 32
Bypass pump data R601R602R603R604R605R606R607 Pump type[-]UPS 32-80BUPS 32-120FBUPS 40-120FBUPS 50-120FB Voltage[V]230230230230230230400 ∆T = 40KCurve setting[-]2233111 ∆T = 50K2333222 ∆T = 55K2333222 ∆T = 60K2333322 ∆T = 70K2333332 ∆T = 80K2333332
System pump design data R601R602R603R604R605R606R607 ∆T = 40KFlow rate[m3/h]3.14.15.16.18.210.211.6 Required pump head[kPa]35.528.957.350.742.349.060.6 ∆T = 50KFlow rate[m3/h]2.43.24.14.96.58.29.2 Required pump head[kPa]30.358.550.844.440.856.364.6 ∆T = 55KFlow rate[m3/h]2.22.93.74.45.97.48.4 Required pump head[kPa]27.356.448.741.434.753.061.4 ∆T = 60KFlow rate[m3/h]2.02.73.44.15.46.87.7 Required pump head[kPa]26.255.446.639.358.647.969.1 ∆T = 70KFlow rate[m3/h]1.72.32.93.54.75.86.6 Required pump head[kPa]24.252.344.435.251.461.666.8 ∆T = 80KFlow rate[m3/h]1.52.02.63.14.15.15.8 Required pump head[kPa]22.150.240.330.245.353.565.6
Page 10 of the Elco R600 IP-ZW user manual — Q1+Q2
10ページ · クリックして拡大
10ページ

Swimming pool boiler The R600 swimming pool boiler should be installed in parallel with the main water flow, going back from the filtering installation to the swimming pool. The swimming pool boiler can increase the water temperature by maximum 15K at once. As a swimming pool installation is an open system, with hardly any static pressure, it’s necessary to create a pressure of at least 0,5 bar in the boiler by installing a regulation valve in the flow connection of the boiler. The table below shows the nominal water flow data at a ∆T of 15K, plus the pump data of the (optional) pump kit for each type of swimming pool boiler.

Water flow data swimming pool boiler ∆TNominal flow rateBoiler resistanceReq. static pressurePump typeVoltagePump headResidual pump head [K][m3/h][kPa][kPa][-][V][kPa][kPa] R601158.11850COM350/052309022 R60210.83250COM350/0923011028 R60313.65050COM350/1523014545 R60416.32750COM350/1123010225 R60521.74850CO500/2240014042 R60627.27550CO500/3040016136 R60730.89850CO500/304001513
Elco R600 IP-ZW — Q1+Q2 diagram (page 10)
図 33
Page 11 of the Elco R600 IP-ZW user manual — Q1+Q2
11ページ · クリックして拡大
11ページ

System examples The following examples are only meant to give an indication of the possibilities available with the R600 water heater and swimming pool boilers. These examples can not be used in a project without any further analysis of the project situation by an authorized company. System 1: water heater with buffer tank (1) Water heater connected to a buffer tank, with the cold water feed connected to the return connection of the buffer tank. This is the most common way to connect a water heater. Having the cold water feed on the return connection of the tank results in less start/stop sequences of the water heater and creates a stable temperature control in a normal hot water installation. System 2: water heater with buffer tank (2) Water heater connected to a buffer tank, with the cold water feed connected to the return connection of the water heater. This system is only applicable when there’s a constant hot water demand of hot water, peak loads can cause a high number of start and stop sequences.

Elco R600 IP-ZW — Q1+Q2 diagram (page 11)
図 34
Elco R600 IP-ZW — Q1+Q2 diagram (page 11)
図 35
Page 12 of the Elco R600 IP-ZW user manual — Q1+Q2
12ページ · クリックして拡大
12ページ

System 3: water heater with big buffer tank When having temporary peak demand, it’s useful to have a big buffer tank (or multiple smaller tanks in series) in combination with a small water heater capacity. The capacity of the water heater is determined by the maximum loading time of the buffer tank. System 4: water heater cascade When having a constant high demand of hot water, it’s useful to install a high capacity water heater (or even a cascade of multiple water heaters) in combination with a small buffer tank. The Buffer tank is only covering the starting delay of the boilers, after that the boilers completely cover the hot water demand constantly.

Elco R600 IP-ZW — Q1+Q2 diagram (page 12)
図 36
Elco R600 IP-ZW — Q1+Q2 diagram (page 12)
図 37
Page 13 of the Elco R600 IP-ZW user manual — Q1+Q2
13ページ · クリックして拡大
13ページ

System 5: bypass water heater This system is mainly used in industrial processes with a constant demand of hot water. The bypass water heater can be used without a buffer tank, as the internal bypass covers the minimum flow rate through the water heater. The Bypass water heater can heat up the hot water with higher ∆T than the R600 standard water heater (∆T =17K). The chapter “Hydraulic connection” describes the flow rates with the different ∆T values. System 6: bypass water heater with buffer tank This system is mainly used in industrial processes, where there is a requirement for direct increase of the water temperature with more than 17K, without having a constant demand. Without the buffer tank the bypass water heater would generate many starts and stops and have a restive regulation.

Elco R600 IP-ZW — Q1+Q2 diagram (page 13)
図 38
Elco R600 IP-ZW — Q1+Q2 diagram (page 13)
図 39
Page 14 of the Elco R600 IP-ZW user manual — Q1+Q2
14ページ · クリックして拡大
14ページ

System 7: swimming pool boiler The swimming pool boiler is installed in parallel with the swimming pool circulation loop, after the filtering installation. The swimming pool boiler only heats up a partial flow, which is mixed in the main loop to the swimming pool. System 8: swimming pool boiler cascade In this situation the swimming pool boilers are connected in parallel to the circulation loop as well. It’s important to connect the boilers in such a way, that both boilers are flushed with an equal water flow rate. This can be done with a regulation valve or by connecting the boilers in reversed return.

Elco R600 IP-ZW — Q1+Q2 diagram (page 14)
図 40
Elco R600 IP-ZW — Q1+Q2 diagram (page 14)
図 41
Page 15 of the Elco R600 IP-ZW user manual — Q1+Q2
15ページ · クリックして拡大
15ページ

Accessories For the R600 water heater and swimming pool boilers the following accessories are available: Water heater: - Accessory kit with pump and stainless steel flanges, safety valve and manometer.

Connection sizes components R601 R602 R603 R604 R605 R606 R607 Safety valve Rp 1.1/4" Manometer R 1/4” Pump G2” DN32 DN40 DN40 DN50 DN65 DN65 Flanges - 1.1/4” 1.1/2” 1.1/2” 2” 2.1/2" 2.1/2” Bypass water heater: - Accessory kit with safety valve and manometer.

Connection sizes components R601 R602 R603 R604 R605 R606 R607 Safety valve Rp 1.1/4" Manometer R 1/4” Swimming pool boiler: - Accessory kit with pump, safety valve and manometer.

Connection sizes components R601 R602 R603 R604 R605 R606 R607 Safety valve Rp 1.1/4" Rp 1.1/2" Manometer R 1/4” Pump in Rp 1.1/2” Rp 2” Pump out Rp 1.1/4” Rp 1.1/2” Consult your supplier for more information on the available accessories.

Page 16 of the Elco R600 IP-ZW user manual — R600 IP/ZW
16ページ · クリックして拡大
16ページ

R600 IP/ZW

Technische Dokumentation Brauchwasserund Schwimmbadkessel

Elco R600 IP-ZWについて質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Elco R600 IP-ZWに関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

Elco R600 IP-ZW 取扱説明書(PDF)

72 ページ·666 KB·ボイラー・給湯器·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…