F220 Series Detectors with F220-B6/C/E/R Bases Installation Manual en English manual 4998138694Er7.book Page 1 Thursday, March 1, 2007 8:42 AM.
2 en | Legal F220 Series Dete ctors wit h F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 1L e g a l 1.1 T rademarks CleanMe ® is a registered trademar k of GE Interlogix in the United States and/or other countries.
F220 Series Detect ors with F220-B6/C /E/R Bases G eneral Information | en 3 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 use a can of clean, dry compre ssed air (such as TECHSPRAY ENVI-RO-TECH Duster) which is available at office and alarm supply stores.
4 en | G eneral Information F220 Series Detectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. Four-wire: Compatible with all UL Listed four-wire control panels. Refer to the control pane l manufacturer’s installation instructions for proper end-of-line (EOL) resistor selection.
F220 Series Detect ors with F220-B6/C /E/R Bases G ener al Information | en 5 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 2.1.3 Base Features 5 1 2 4 6 7 9 8 10 12 11 12 12 12 3 11 11 11 13 1. Terminal 1 2. Terminal 2 3.
6 en | G eneral Information F220 Series Detectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 2.2 F220 Series Det e ctors 2.2.1 About F220 Series Detector Heads The F220 Series Detector Heads listed in Table 2.
F220 Series Detect ors with F220-B6/C /E/R Bases G ener al Information | en 7 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 2.2.2 F220 Series Detector Features 2.2.3 F220 Series Heat Detector Heads The F220 Heat Detector Heads can be identified by color coding (refer to Table 2.
8 en | G eneral Information F220 Series Detectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 2.
F220 Series Detect ors with F220-B6/C /E/R Bases G ener al Information | en 9 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.
10 en | Install the Bases F220 Series Det ectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. providing tamper protection. An EOL power supervision module, such as a D275 or an F220-B6E Power Supervision Base and an EOL resistor as specified by the control panel manufacturer, supervises power.
F220 Series Detect ors with F220-B6 /C/E/R Bases Install the Bases | en 11 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 3.2 Wire the Bases 3.2.1 Terminal Connections 3.2.2 EOL Resistors Use the EOL resistors supplied or specified by the control panel manufacturer.
12 en | Install the Bases F220 Series Det ectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 3.2.4 Four-wire Loop Termination One D275 End-of-Line Module (refer to Figure 3.6 on page 17) or F220-B6E Power Superv ision Base (refer to Figure 3.
F220 Series Detect ors with F220-B6 /C/E/R Bases Install the Bases | en 13 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 3.4 Wire F220-B6 T wo-wire Bases The F220-B6 is a 12 VDC or 24 VDC base for two-wire conventional loops.
14 en | Install the Bases F220 Series Det ectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 3.5.1 F220-B6C: The F220-B6C base has a normally open alarm loop relay and auxiliary Form C (NC/C/NO) cont acts.
F220 Series Detect ors with F220-B6 /C/E/R Bases Install the Bases | en 15 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 unnecessary. Use only one F220-B6 E per zone run. It must be the last base on the run. Refer to Figure 3.
16 en | Install the Bases F220 Series Det ectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 3.5.3 F220-B6R: The F220-B6R is the standard base for four-wire configurations. The Alarm Loop Relay (Terminals 1 and 2) is a normally-open relay rated for 0.
F220 Series Detect ors with F220-B6 /C/E/R Bases Install the Bases | en 17 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 3.6 Wire P ower Super vision Modules 3.6.1 Wire F220-B6E Power Supervision Base Refer to Section 3.
18 en | Install the Det ector Heads F220 Se ries Detect ors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 4 Install the Detect or Heads 4.1 Mount the Detect or Heads 4.1.1 Optional Locking Bar Each base has a snap-off locking bar as part of the base molding.
F220 Series Detect ors with F220-B6/C/E/R Bases Install the De tector Heads | en 19 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 4.1.2 Mounting Skirt Align the four alignment keys (refer to Figure 2.1 , Item 11 on page 5 and to Figure 4.
20 en | Install the Det ector Heads F220 Se ries Detect ors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 4.1.3 Detector Head Install: Install the detector head by lini ng up the LED on the detector head (refer to Figure 4.
F220 Series Detect ors with F220-B6/C/E/R Bases Install the De tector Heads | en 21 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 4.2 Set Detector Mode s The F220 Series Smoke Dete ctors feature a unique magnet-operated sensitivity mode and detector test mode.
22 en | Install the Det ector Heads F220 Se ries Detect ors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. 4.3 Set CleanMe F eature The Clean Me feature monitors t he smoke chamber’s sensitivity and sends a trouble signal to the control panel when the sensitivity degrades to a preset level.
F220 Series Detect ors with F220-B6/C/E/R Bases T est the Installation | en 23 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 A unit with CleanMe activated double flashes (two flashes within a half second of each other) every eight seconds.
24 en | T est the Installa tion F220 Seri es Det ectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc. every eight seconds. This veri fies the detector is receiving power and operating properly. 5.
F220 Series Detect ors with F220-B6/C/E/R Bases T est the Installation | en 25 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.01 5.3 T est the Alarm L oop Checkthe voltage across the EOL re sistor of each alarm loop to verify wiring losses do not exceed control panel manufacturer’s specifications.
26 en | T est the Installa tion F220 Seri es Det ectors with F220-B6/C/E/R Bases 4998138694 -04 | 2007.01 In stallation Manual Bosch Security Syst ems, Inc.
F220 Series Detect ors with F220-B6/C/E/R Bases T est the Installation | en 27 Bosch Security Syst ems, Inc. Installa tion Manual 4998138 694 -04 | 2007.
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450-9199 USA Customer Service: (800) 289-0096 Technical Support: (888) 886-6189 www.boschsecurity.
デバイスBosch Appliances F220-B6の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bosch Appliances F220-B6をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBosch Appliances F220-B6の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bosch Appliances F220-B6の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bosch Appliances F220-B6で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bosch Appliances F220-B6を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBosch Appliances F220-B6の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bosch Appliances F220-B6に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBosch Appliances F220-B6デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。