CONTENTS Page 1. Description, use 1 2. Range 1 3. Overall dimensions 1 4. Preparation - Connection 1 5. General Characteristics 3 6. Compliances and approvals 5 7. Auxilaries and accessories 5

1. DESCRIPTION - USE

3. OVERALL DIMENSIONS

Isolating switch ensuring the breaking and the isolation of electrical circuits.

LEGRAND Isolating Switch (406432) — 1. DESCRIPTION - USE diagram (page 1)
図 3

Fully visible breaking indication.

2. RANGE Polarity and symbols :

1-pole 250V~ 16A 20A 32A 1-pole with indicator light 250V~ 20A 32A 2-poles 400V~ 16A 20A 32A 2-poles with indicator light 250V~ 20A 32A 40A 3-poles 400V~ 20A 32A 4-poles 400V~ 20A 32A

1-pole2-poles3-poles4-poles A (mm)17.817.835.635.6
4. PREPARATION - CONNECTION Mounting : . On symmetrical EN 60.715 rail or DIN 35 rail.
Operating positions. Vertical Horizontal Upside down On the side Power supply:

. For devices without indicator light : Either from the top or the

bottom. . For devices with indicator light : From the top.

87045 LIMOGES Cedex · 1 / 5

Page 2 of the LEGRAND Isolating Switch (406432) user manual — Connection:
2ページ · クリックして拡大
2ページ

4. PREPARATION - CONNECTION (continued) Module maintenance:

4. PREPARATION - CONNECTION (continued)
. Terminal depth14 mm. . Screw head: mixed, slotted and Pozidriv no. 2. . Tightening torques:

. Isolating switches may be replaced in the middle of a row supplied with busbars without disconnecting the other products. This method is available for the 1-pole, 2-poles, 3-poles, 4-poles.

- Min : 1.2 Nm - Recommended : 1.6 to 2 Nm - Max : 2.8 Nm Conductor type: . Copper cable or supply busbar.

LEGRAND Isolating Switch (406432) — 4. PREPARATION - CONNECTION (continued) Module maintenance: diagram (page 2)
図 4 · 4. PREPARATION - CONNECTION (continued) Module maint…

Put the clamp in the unlocking

. Cable cross-section:

Unscrew both upper terminals

Without ferruleWith ferrule Rigid cable1 conductor 1.5 to 16 mm2 2 conductors 1.5 to 6 mm² Flexible cable1 conductor 1.5 to 10 mm2 2 conductors 1.5 to 4 mm21 conductor 1.5 to 10 mm2

Put the clamp in

Recommended tools:

LEGRAND Isolating Switch (406432) — Recommended tools: diagram (page 2)
図 5 · Recommended tools:

. For the terminals:

- Screwdriver with 5.5 mm blade. - Pozidriv no. 2 screwdriver. . For attaching or removing the DIN rail:

- Screwdriver with 5.5 mm blade. - Pozidriv no. 2 screwdriver. Manual actuation of the Isolating switch: . Ergonomic 2-position handle:

Pull the device forward in order to release it from

. "O-OFF": Device open. . "I-ON": Device closed.

Contact status display:

LEGRAND Isolating Switch (406432) — Contact status display: diagram (page 2)
図 6 · Contact status display:

. By marking of the handle:

- "O-OFF" in white on a green background = contacts open. - "I-ON" in white on a red background = contacts closed.

Locking:

Pull the device downward in order

. Padlocks possible in the open and closed positions with padlock support (Cat. No. 4 063 03) and Ø5 mm padlock (Cat. N°. 4 063 13) or Ø6 mm padlock (Cat. N°. 0 227 97).

to release it completely from the prongs of the

Sealing: . Possible in the open or closed positions.

Labelling:

. Circuit identification by way of a label inserted in the label holder situated on the front of the product.

Connection:

LEGRAND Isolating Switch (406432) — Connection: diagram (page 2)
図 7 · Connection:
LEGRAND Isolating Switch (406432) — Connection: diagram (page 2)
図 8 · Connection:
LEGRAND Isolating Switch (406432) — Connection: diagram (page 2)
図 9 · Connection:

. Terminals protected against direct contact IP20, wired device. . Cage terminals, with release and captive screws. . Terminals fitted with shutters preventing a cable being placed under the terminal, with the terminal partly open or closed. . Alignment and spacing of the terminals permitting connection with the other products in the range via prong supply busbars.

Show 7 more labels / short text on this page
position · completely · the unlocking · position · the rail · busbar · 2 / 5
Page 3 of the LEGRAND Isolating Switch (406432) user manual — Rated impulse withstand voltage:
3ページ · クリックして拡大
3ページ

Isolating switch DX 3 -IS

1/2 module per pole, up to 40A

5. GENERAL CHARACTERISTICS Marking on the front side: . By permanent ink pad printing.

5. GENERAL CHARACTERISTICS (continued) Direct current utilization :

. 48V (110V with 2 poles serial cabling).

Without indicator light :

Utilization category:

. AC22 : Mixed load. . A : Frequent operations. . AC23 : Inductive load. Complies with IEC/EN 60947-3. Characteristic not marked on product

LEGRAND Isolating Switch (406432) — Utilization category: diagram (page 3)
図 10 · Utilization category:

Rated operational voltage Utilization category

Degree of pollution:

. 3 in accordance with standard IEC 60664-1. Power dissipated per pole :

LEGRAND Isolating Switch (406432) — Degree of pollution: diagram (page 3)
図 11 · Degree of pollution:
Without indicator lightWith indicator light 16 A20A32A40A20A32A40 A 0,23W0,36W0,92W1,44W0,45W1,01W1,53W

*Rated current with X : Devices tested on fluorescent lamp.

Indicator light (if equiped):

Technology : fluorescent lamp. Shelf life: 50 000 Hours. Color: Orange.

LEGRAND Isolating Switch (406432) — Indicator light (if equiped): diagram (page 3)
図 12 · Indicator light (if equiped):

Marking on the upper panel:. By permanent ink pad printing.

Without indicator light :

Degree or class of protection:

With indicator light:

. Terminals protected against direct contact, Class of protection against solid objects and liquids (wired device): IP20 in accordance with standards IEC 529 – EN 60529 and NF 20-010. . Class II in relation to metallic conductive parts . Class of protection against mechanical impacts IK04 in accordance with standard EN 62262. Plastic materials:

Isolator switch standard Utilization category

Rated operational voltage:

1-pole with or without indicator light and 2 poles with indicator light: . Ue = 250 V ~ 2-poles without indicator light, 3-poles and 4-poles : . Ue = 400 V ~

. Polyamide, PBT and PC Enclosure heat and fire resistance:

Rated frequency:

. Resistance to glow wire tests at 960°C, in accordance with standard IEC 60695-2-10 & 60695-2-11. . Classification V2, in accordance with standard UL94. Higher heating potential:

. 50/60 Hz with standard tolerances.

Short circuit withstand:

. Rated conditional short-circuit current in combination: see coordination table on page 4.

. The heat potential is assessed at:

Following IEC/EN 60947-3 : . Icw = 750 A . Icm = 1500 A Following IEC/EN 60669-2-4 : . Inc =4500 A with fuse of same rated current.

1.29 MJ 2.56 MJ

Closing and opening effort via the handle:

Handle force1-pole2-poles3-poles4-poles To switch Off4N7N10N14N To switch On10N18N29N35N

Insulation voltage:

. Ui = 500 V

Rated impulse withstand voltage:

. Uimp = 6 kV

Show 17 more labels / short text on this page
Electrical diagram · Range · Cat N° · Rated current* · With indicator light · Electrical diagram · Range · Cat N° · Rated current* · Rated operational voltage · Indicator light · Approvals · Isolator switch standard · Approvals · 1-pole and 2-poles · 3-poles and 4-poles · 3 / 5
Page 4 of the LEGRAND Isolating Switch (406432) user manual — 5. GENERAL CHARACTERISTICS (continued) Mechanical endurance:
4ページ · クリックして拡大
4ページ

5. GENERAL CHARACTERISTICS (continued) Mechanical endurance:

. Compliant with standard IEC/EN 60947-3 & IEC/EN 60669-2-4 . 300 000 operations with no load. Electrical endurance:

. Compliant with standard IEC/EN 60947-3 & IEC/EN 60669-2-4 . 30 000 operations with load AC22A. . 1 500 operations with load AC23A. Vibrations and tremors resistance :

. Compliant with appendix Q category F of standard IEC/EN 60947-1. Ambient temperatures:

. Operation: from - 25 °C to + 70 °C. . Storage: from - 40 °C to + 70 °C. Short-circuit behavior in coordination with upstream protection:

. Tests performed according to the protocol of IEC/EN 60669-2-4 : The device remains fully functional and meets the switch tests after suffering two short circuit established in coordination with the DPCC of the following table.

- The first short circuit being set at an angle of 45 °. - The second being provided by the switching on of the isolator switch on the short-circuit.

Rated voltage 400V~Inc (kA) Upstream protection16A20A32A MCBDX³ 4500A/6kA4,54,54,5 DX³ 6000A/10kA4,54,54,5 DX³ 10000A/16kA4,54,54,5 DX³ 25kA4,54,54,5 DX³ 36kA4,54,54,5 DX³ 50kA4,54,54,5 DPX³ 160A 16kA4,54,54,5 DPX³ 160A 25kA4,54,54,5 DPX³ 160A 36kA4,54,54,5 DPX³ 160A 50kA4,54,54,5 DPX³ 250A 25kA4,54,54,5 DPX³ 250A 36kA4,54,54,5 DPX³ 250A 70kA4,54,54,5 Fuse gG / aM20A88 25A88 32A888 40A888 63A888 80A888 100A888 125A666
Rated voltage 250V~Inc (kA) Upstream protection16A20A32A40A MCBDNX³ 4500A/4,5kA4,54,54,54,5 DX³ 4500A/6kA6666 DX³ 6000A/10kA7777 DX³ 10000A/16kA7777 DX³ 25kA7777 DX³ 36kA7777 DX³ 50kA7777 DPX³ 160A 16kA7777 DPX³ 160A 25kA7777 DPX³ 160A 36kA7777 DPX³ 160A 50kA7777 DPX³ 250A 25kA7777 DPX³ 250A 36kA7777 DPX³ 250A 70kA7777 Fuse gG / aM20A1010 25A1010 32A101010 40A10101010 63A10101010 80A10101010 100A10101010 125A10101010

4 / 5

Page 5 of the LEGRAND Isolating Switch (406432) user manual — Installation software:
5ページ · クリックして拡大
5ページ

5. GENERAL CHARACTERISTICS (continued) Packaged volume:

PackagingVolume (dm³) 1-polePer 101.6 2-polesPer 101.6 3-polesPer 51.6 4-polesPer 51.6

Average unit weight:

1-pole65 g 2-poles81 g 3-poles145 g 4-poles160 g

6. COMPLIANCE AND APPROVALS In accordance with standards:

. IEC/EN 60947-3.

. IEC/EN 60669-2-4.

Usage in special conditions:

. Compliant with appendix Q category F of standard IEC/EN 60947-1. Respect for the environment – Compliance with European Union Directives:

. Compliance with Directive 2002/95/EC of 27/01/03 known as "RoHS" which provides for a restriction on the use of dangerous substances such as lead, mercury, cadmium, hexavalent chromium and polybrominated biphenyl (PBB) and polybrominated diphenyl ether (PBDE) brominated flame retardants from 1st July 2006. . Compliance with the Directive 91/338/EEC of 18/06/91 and decree 94-647 of 27/07/04. Plastic materials:

. Halogen free plastic materials. . Labelling of parts compliant with ISO 11469 and ISO 1043.

Packaging:

. Design and manufacture of packaging compliant with decree 98-638 of 20/07/98 and Directive 94/62/EC.

Approvals obtained:

. See list of approvals available.

7. AUXILIARIES AND ACCESSORIES Wiring accessories: . Supply busbar used on 1 pole and 2 poles:

- HX3 1-pole universal supply busbar (Cat N°: 4 049 26, 4 049 37). - HX3 4-poles supply busbar «screw» (Cat N°: 4 052 10). - HX3 4-poles supply busbar « head of group » (Cat N°: 4 052 00, 4 052 01, 4 052 02). . HX³ connection module plug-in system set (Cat N°: 4 052 23). . Connection terminals (Cat N°: 4 049 05, 4 052 08). . Sealable screwcover (Cat N°: 4 063 04).

Signalling auxiliaries :

. Auxiliary contact (0.5 module, Cat N°: 4 062 58). . Double Auxiliary contact (1 module, Cat N°: 4 062 66).

Installation software:

. XL PRO3.

5 / 5

LEGRAND Isolating Switch (406432)について質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
LEGRAND Isolating Switch (406432)に関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

LEGRAND Isolating Switch (406432) 取扱説明書(PDF)

5 ページ·153 KB·スイッチ·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…