Product Manual 4512 Bluetooth communication enabler

Zone 2 ZONE 2 / DIV 2
TEMPERATURE | I.S. INTERFACES | COMMUNICATION INTERFACES | MULTIFUNCTIONAL | ISOLATION | DISPLAY

Individually outstanding, unrivalled in combination
With our innovative, patented technologies, we make signal conditioning smarter and simpler. Our portfolio is composed of six product areas, where we offer a wide range of analog and digital devices covering over a thousand applications in industrial and factory automation. All our products comply with or surpass the highest industry standards, ensuring reliability in even the harshest of environments and have a 5-year warranty for greater peace of mind.

Our range of temperature transmitters and sensors provides the highest level of signal integrity from the measurement point to your control system. You can convert industrial process temperature signals to analog, bus or digital communications using a highly reliable point-to-point solution with a fast response time, automatic self- calibration, sensor error detection, low drift, and top EMC performance in any environment.

We deliver the safest signals by validating our products against the toughest safety standards. Through our commitment to innovation, we have made pioneering achievements in developing I.S. interfaces with SIL 2 Full Assessment that are both efficient and cost-effective. Our comprehensive range of analog and digital intrinsically safe isolation barriers offers multifunctional inputs and outputs, making PR an easy-to-implement site standard. Our backplanes further simplify large installations and provide seamless integration to standard DCS systems.

We provide inexpensive, easy-to-use, future-ready communication interfaces that can access your PR installed base of products. All the interfaces are detachable, have a built-in display for readout of process values and diagnostics, and can be configured via push-buttons. Product specific functionality includes communication via Modbus and Bluetooth and remote access using our PR Process Supervisor (PPS) application, available for iOS and Android.

Our unique range of single devices covering multiple applications is easily deployable as your site standard. Having one variant that applies to a broad range of applications can reduce your installation time and training, and greatly simplify spare parts management at your facilities. Our devices are designed for long-term signal accuracy, low power consumption, immunity to electrical noise and simple programming.

Our compact, fast, high-quality 6 mm isolators are based on microprocessor technology to provide exceptional performance and EMC-immunity for dedicated applications at a very low total cost of ownership. They can be stacked both vertically and horizontally with no air gap separation between units required.

Our display range is characterized by its flexibility and stability. The devices meet nearly every demand for display readout of process signals, and have universal input and power supply capabilities. They provide a real-time measurement of your process value no matter the industry, and are engineered to provide a user-friendly and reliable relay of information, even in demanding environments.

4512 Contents
Warning 2 Symbol identification 2 Safety instructions 2 Applications 4 Technical characteristics 4 Mounting / installation / programming 4 Mounting on a 4000 / 9000 device 5 Order 6 Electrical specifications 6 4512 - configuration / operating the function keys 8 4512 settings - routing diagram 10 PR Process Supervisor - PPS app 11
App download 11 Connection and configuration 12 Pairing options 13 Time adjustment 13 Process simulation 13 Data logging set-up 13 Analysis of logged data, event logging and export 14 PReset software 15
Time adjustment 15 Detailed analysis of logged data 15 Data logging 17 Event log 17 Import of saved device configuration 18 Document history 19

To avoid the risk of electric shock and fire, the safety instructions of this guide must be observed and the guidelines followed. The specifications must not be exceeded, and the device must only be applied as described in the following. Prior to the commissioning of the device, this installation guide must be examined carefully. Only qualified personnel (technicians) should install this device. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Repair of the device must be done by PR electronics A/S only.
Triangle with an exclamation mark: Read the manual before installation and commissioning of the device in order to avoid incidents that could lead to personal injury or mechanical damage.
The CE mark proves the compliance of the device with the essential requirements of the directives.
Ex devices have been approved according to the ATEX directive for use in connection with installations in explosive areas.
The product meets the requirements of the standards: Factory Mutual Approval Standard Class Number 3611 and CSA C22.2 No. 213-16. FM/CSA Hazardous (Classified) Location Electrical Equipment: Non Incendive / Class I / Division 2 / Groups A,B,C,D.
The device has an internal, non-removable, rechargeable coin cell battery. Do not attempt to open the back cover or remove the battery, as you may damage the device.
Unpack the device without damaging it and check whether the device type corresponds to the one ordered.
The device is manufactured for indoor use. Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock, as well as rain and heavy moisture. If necessary, heating in excess of the stated limits for ambient temperatures should be avoided by way of ventilation. The device may be used in Overvoltage Category II, Pollution Degree 2 at an altitude up to 2000 m. If the equipment is installed within an ultimate enclosure, the inner service temperature of the enclosure corresponds to the ambient temperature of the device. If the device is operated in an ambient temperature between +55ºC and +60ºC, the temperature of the device housing may be higher than +60ºC. The device must therefore be installed so that it is only accessible to service personnel or users that are aware of the reason for restricted access and the required safety measures at an ambient temperature of +55ºC to +60ºC.
Only qualified technicians who are familiar with the technical terms, warnings, and instructions in this installation guide and who are able to follow these should connect the device. Only devices which are undamaged and free of moist and dust may be installed. The device may be installed on and supplied by PR electronics 4000 and 9000 series only.
Receipt and unpacking · Environment · Mounting

Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
PR electronics A/S www.prelectronics.com
ATEX and IECEx installation in Zone 2
KEMA 13ATEX0098 X II 3 G Ex nA IIC T5 Gc IECEx DEK 13.0026 X Ex nA IIC T5 Gc
For safe Ex installation the following must be observed: The device must be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
The devices must be installed in a suitable enclosure providing a degree of protection of at least IP54 according to EN60529, taking into account the environmental conditions under which the equipment will be used.
To prevent ignition of the explosive atmospheres do not separate connectors when energized and an explosive gas mixture is present.
To avoid the risk of explosion due to electrostatic charging of the enclosure, do not handle the units unless the area is known to be safe, or appropriate safety measures are taken to avoid electrostatic discharge.For safe installation the following must be observed
FM installation in Zone 2 / Div. 2
FM, US CL I, Div 2, Gp A, B, C, D T5 CL I, Zn 2, Gp IIC T5 FM, CA CL I, Div 2, Gp A, B, C, D T5
For safe Ex installation the following must be observed: The device must be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area.
CAUTION: To prevent injury, read the manual before use. WARNING – Explosion hazard. Substitution of components may impair suitability for Class I, Division 2. WARNING – Explosion hazard. Do not disconnect while circuit is live unless area is known to be non-hazardous. WARNING – Explosion hazard. Do not disconnect equipment unless power has been switched off or the area is known to be
non-hazardous.
Year of manufacture can be taken from the first two digits in the serial number.
The equipment is intended to be mounted in a vent-free, tool-secured enclosure, meeting the equipment enclosure requirements in accordance with ANSI/ISA-61010-1 and C22.2 No. 1010.1, where applicable.
When disconnected, the device may be cleaned with a cloth moistened with distilled water.
PR electronics A/S offers a 5-year warranty on this product.
To the extent the instructions in this manual are not strictly observed, the customer cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement.
Cleaning · Warranty · Liability

Mounting / installation / programming
Applications · Technical characteristics

PR 4512 is a detachable display that can be mounted on all system 4000/9000 fronts for programming and signal monitoring.

PR 4512 contains a dot matrix LCD display

Line 1 can e.g. show the scaled process value. Line 2 can e.g. show the selected engineering unit. Line 3 can e.g. show the analog output or TAG no. Line 4 shows status for communication and e.g. signal trending.
Icons illustrate - left to right:
Input signal trend up/down
Display communication to host
Logdata present (steady) or logging in progress (blinking)
Relay/-s status

Environmental conditions: Operating temperature -20°C to +60°C Storage temperature -20°C to +85°C Humidity < 95% RH (non-cond.) Protection degree IP20 when installed Installation in pollution degree 2 / overvoltage category II.
Mechanical specifications: Dimensions (HxWxD) 73.2 x 23.3 x 26.5 mm Dimensions (HxWxD) w/ 4000/9000 unit 109 x 23.5 x 131 mm Weight approx 30 g
Common specifications: Supply voltage 6.5...20 V supplied from host 4000 / 9000 device Max. required power 0.15 W
Extended EMC immunity: NAMUR NE 21, A criterion, burst No loss of communication
Internal battery back-up (for real-time clock) 2 years (@ 25°C) Calibrated real-time clock accuracy
Data logging: Memory 100 MB Capacity > 2.75 million data points1 Data retention, without power ~ 10 years
Observed authority requirements:
Directives: EMC 2014/30/EU RED 2014/53/EU ATEX 2014/34/EU RoHS 2011/65/EU
Standards: UL, Standard for Safety UL 61010-1
1 Consult www.prelectronics.com/logpointcalculator for device specific capacity.
Order · Electrical specifications

Bluetooth: Europe, CE 117-37823-1 US, FCC ID QoQBGM111 Canada, IC 5123A-BGM111 Japan, MIC R 209-J00192 Korea, KC MSIP-CRM-BGT, BGM111 China, SRRC, CMIIT-ID 2018DJ6574 Brazil, Anatel 06541-18-11723 Peru, MTC T-251621-2018 Singapore, IMDA N1861-20 Australia, RCM 42 004 182 772 Malaysia, SIRIM QAS RAHY/63M/1020/S(20-4544)
Please find an updated list of countries who have approved the use of 4512 at: www.prelectronics.com/4512-bluetooth-approvals/
Approvals:
Ex/ I.S.: ATEX KEMA 13ATEX0098 X II 3 G Ex nA IIC T5 Gc IECEx DEK 13.0026 X Ex nA IIC T5 Gc c FM us FM18US0268X / FM18CA0129X FM, US CL I, Div 2, Gp A, B, C, D T5 CL I, Zn 2, Grp IIC T5 FM, CA CL I, Div 2, Gp A, B, C, D T5

Documentation for routing diagram.
When using the PR 4512 for configuration of a PR 4000 or PR 9000 device, you will be guided through all parameters and can choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys: 1 will increase the numerical value or choose the next parameter 2 will decrease the numerical value or choose the previous parameter 3 will save the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state 1.0. Pressing and holding 3 will return to the previous menu or return to the default state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0) without saving the changed values or parameters.
For device-specific programming menus, please refer to the user manual for each device, e.g. PR 4116.
The PR 4512 gives access to a number of functions which can be reached by answering “Yes” to the menu point “ADV.SET” (see “4512 settings - routing diagram” on page 10).
Two factor authentication When pairing the PPS device with PR 4512, a physical acknowledgement on the 4512 unit is required to complete pairing (activation of the 3 button). Two factor authentication is disabled by default.
Log functionality By selecting the “LOG.INT” menu item, it is possible to set the log interval in seconds. Valid selections are 1...9999 s. You can also choose to reset the stored log in the menu item “LOG. DEL”. The logging function exits automatically, if the PR 4512 is detached. If the PR 4512 is placed back on the same device, the logging will continue. In the event of a power outage, logging will resume when power is restored.
In general · 4512 functions

Error Scenarios and help texts
Memory The memory available for data logging is 100 MB. When the memory is full, the oldest data will be overwritten.
Backup of device configuration If you want to back-up the 4000/9000 product configuration, remember to save the configuration in the PR 4512 under the menu point “MEM” in the “ADV.SET” menu. The saved configuration can later be imported into PReset (see “Import of saved device configuration” on page 18).
SIL and PR 4512 / PPS As of PR 4512 hardware serial number 211065001, shipped from January 2021, you can engage data logging via the front display while the 9000 device is SIL-enabled (SIL-locked).
There is no support for enabling SIL mode for 9000 series devices from within the PPS application or for accessing a SIL- enabled device for monitoring via the PPS. An attempt to access a SIL-enabled device from the PPS application returns the error code ‘SIL-enabled, access not possible!’.
Bluetooth enable / disable For customers with an IT security policy that prevents Bluetooth devices in production environments, it is possible to disable Bluetooth while still benefitting from the data logging capabilities. This feature has been implemented on PR 4512 devices with serial number from 201556001, shipped from August 2020.

"Monitor" SCROLLING HELPTEXTS: 40.0 0000 (correct) No (No) xxxx [1] Set correct password % ---OK--> > PASSW. ---OK--> ADV.SET ---OK--> XXXX [2] Enter advanced setup menu? 10.4mA [1] [2] (Yes) [x] [3] Enter Language setup ^ o V Enter Password setup v ^ v ^ | v ^ Enter Simulation mode | 9999 YES | Perform Process calibration | 0000 NO | Enter Display setup | | Perform Memory operations | | MEM (MEM) Enter Bluetooth setup | | > SETUP -OK-|--> Enter Log setup | [3] | Enter Rotation setup | (DISP) [4] Enable Two-factor authentication? | v ^ |--> [5] Enable log functionality? | MEM | [6] Select log interval time in sec | DISP (CAL) [7] Warning, new log, confirm overwrite? | CAL |--> [8] Rotate device upside down? | SIM | [9] Delete stored log? | PASS (SIM) [10] Enable Bluetooth? | LANG |-->
| LOG | | ORIEN (PASS)
| |--> | | | (LANG)
| |--> | | *3
| (BLUE) YES YES |--> |--> BT.EN ---OK--> BT.2FA ---OK--> "Monitor" | [10] [4] |
(LOG) YES (YES) NO (YES) 10 (YES) |--> EN.LOG ---OK--> DEL.LOG ---OK--> > LOG.INT ---OK--> "Monitor" | [5] (NO) [7] / [9] (NO) [6] |
Menu is shown only if log is started and no log is present in the device (ORIEN) NO |--> ROT.DEV ---OK--> "Monitor" *3): [8] Menu is shown only if Bluetooth is enabled
v ^ YES

The PR electronics ‘PR Process Supervisor’ - PPS - app enables remote data logging, programming and error diagnostics of PR 4000/9000 devices mounted with the 4512 Bluetooth communication enabler. The app shows live data directly from a smart device. It is designed for technical and maintenance staff as well as plant operators. All that is required to get started is to download the free app, and you have a user friendly interface for monitoring and programming of installed PR devices.
If you have already downloaded the PR electronics PPS app from either the Apple App store (IOS) or Google Play (Android), check for updates that will add the Bluetooth communication options.2
If you will be downloading the PR electronics PPS app for the first time, follow the instructions for IOS below. The Android download process will be similar.


Go to the App store or scan the QR code (the code works for both IOS and Android).

Search for ”PR electronics PPS”, and install the free application.

Tap the newly created PPS icon.
2 Please consult app release notes for latest status of supported devices.
App download




5 When a specific product is selected in the PPS, the display on the corresponding PR 4512 device will flash, indicating that connection has been established.
Connection and configuration

a) Two-factor authentication - BT.2FA (disabled as default): 1. The display on the corresponding PR 4512 device will flash. 2. Confirm that the right device has been selected by pushing the 3 button on the 4512.

b) Fast pairing:
The internal clock in the PR 4512 uses Coordinated Universal Time (UTC). When connecting to a smart device, the clock will automatically show local time. If the internal clock has drifted by > 2 minutes, a warning will appear on the smart device prompting you to adjust the time.
If a process simulation is performed using the PPS app, the device will return to normal operation state when the connection between the PPS app and the 4512 is terminated.
Opening screen for start-up of data logging: 1. Select “Data logging” in the left-hand side.


Analysis of logged data, event logging and export




For a detailed description of the error codes, see the section “Error indications” in the individual 4000/9000 series product manual.
The internal clock in the PR 4512 uses Coordinated Universal Time (UTC). When connecting to PReset, the clock will automatically show local time. If the internal clock has drifted by > 2 minutes, a warning will appear in PReset prompting you to adjust the time.
Detailed analysis of logged data

Use the PR 4590 ConfigMate to transfer logged data in the PR 4512 to PReset for analysis.
Time adjustment





The below example shows the graph for display value. Other options are Relative PV, Output Value and Primary Raw Values.

The below example shows an event log in PReset for a PR 4114. The event log indicates date and time for the occurrence of the event and for when it was cleared.

For a detailed description of the error codes, see the section “Error indications” in the individual 4000/9000 series product manual.
Data logging · Event log

Import of saved device configuration


The following list provides notes concerning revisions of this document.
Rev. ID Date Notes 100 2002 Initial release of the product. 101 2103 Menu structure updated. SIL & Bluetooth functionality updated.

Our trusted red boxes are supported wherever you are
All our devices are backed by expert service and a 5-year warranty. With each product you purchase, you receive personal technical support and guidance, day-to-day delivery, repair without charge within the warranty period and easily accessible documentation.
with a global reach. This means that we are always nearby and know your local markets well. We are committed to your satisfaction and provide PERFORMANCE MADE SMARTER all around the world.
For more information on our warranty program, or to meet with a sales representative in your region, visit prelectronics.com.
We are headquartered in Denmark, and have offices and authorized partners the world over. We are a local business

PR electronics is the leading technology company specialized in making industrial process control safer, more reliable and more efficient. Since 1974, we have been dedicated to perfecting our core competence of innovating high precision technology with low power consumption. This dedication continues to set new standards for products communicating, monitoring and connecting our customers’ process measurement points to their process control systems.
Our innovative, patented technologies are derived from our extensive R&D facilities and from having a great understanding of our customers’ needs and processes. We are guided by principles of simplicity, focus, courage and excellence, enabling some of the world’s greatest companies to achieve PERFORMANCE MADE SMARTER.
よくあるトラブル、考えられる原因、対処法。
| 問題 | 考えられる原因 | 対処法 | |
|---|---|---|---|
| 4512 has been without power until the battery is fully discharged. The RTC now needs to be synchronized. | Connect a smart device to the 4512 and synchronize. The error message will disappear when the synchronization is OK. | p.11 | |
| 4512 has a log in progress and is moved to a new host. | Move the 4512 back to the previous host or press OK. Both actions will remove the error message. The log will still be available in the memory of the 4512, but the device will not continue logging. Use PR 4590 or the PPS app to read out the log, before moving 4512 to a new host. | p.11 | |
| 4512 has a log in progress and the user changes the host configuration. | If the configuration is changed while logging, the log is stopped immediately. A MEM-SAVE is also considered a configuration change, and thus stops data logging. Press OK to acknowledge that the log has been stopped in order to remove the error message. The log will still be available in the memory of the 4512, until a new log is started. Use PR 4590 or the PPS app to read out the log, before starting a new log. | p.11 |