
To be sold only with installation instructions.
Contact with electricity can cause electrical fires, personal injury, or death. Shut off power to the circuit before using this product and consult local building codes to determine installation requirements.
1. Wiring must comply with all applicable electrical codes. 2. Turn OFF power before removing or installing connectors. 3. Strip wires ½”. Completely bare conductors. 4. Grip wire firmly and push conductor into open port. Use only one conductor per port. 5. Verify conductor is fully inserted to the back of the connector. 6. Connector is reusable on solid wires of the same wire gage or larger. If reusing connector, cut and re-strip conductors. 7. In order to remove a wire, pull and twist the wire back and forth.
DO NOT RE-USE connector on stranded wire.
COPPER TO COPPER ONLY: Do Not Use on Aluminum wire. Temperature Rating: 105°C (221°F) maximum. 600 volts maximum building wire. 1000 volts in signs and lighting fixtures.
For use on insulation types TFN, TFFN, THHN, XHHW, T90 nylon or equivalent.
774A Listed Wire Connector

Wire Range:
12 to 20 AWG Sol. } REUSABLE 12 to 16 AWG Str. (< 19 strands), 18 AWG Str. (7 strands) } NON-REUSABLE
In order to remove solid conductors pull and twist back and forth. For stranded wire use a new connector
IDEAL INDUSTRIES, INC. Sycamore, IL 60178, U.S.A. 800-435-0705 Customer Assistance www.idealindustries.com ND 6779-1
1/2
この取扱説明書で参照されているリンク(メーカー、サポート、ダウンロード等)。
ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。
最初の質問を投稿しましょう。他のユーザーや当チームが回答します。