Bryantメーカー556Aの使用説明書/サービス説明書
ページ先へ移動 of 12
NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration,.
can be no deviation. Consult the Application Guideline and Service Manual — Air Conditioners and Heat Pumps Using Pu- ron ® Refrigerant to obtain required unit changes for specific applications and for R-22 retrofit. I. CHECK EQUIPMENT AND JOB SITE A.
INSTALLING TXV IN PLACE OF PISTON 1. Pump system down to 2 psig and recover refrigerant. 2. Remove hex nut from piston body. Use backup wrench on fan coils. 3. Remove and discard factory-installed piston. Be sure teflon seal is in place. 4. Reinstall hex nut.
VII. MAKE PIPING CONNECTIONS WARNING: Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves. CAUTION: Do not leave system open to atmosphere any longer than minimum required for installation.
2. Braze filter drier between connector tube and liquid tube to indoor coil. Flow arrow must point towards indoor coil. C. REFRIGERANT TUBING Connect vapor tube to fitting on outdoor unit vapor service valves. Connect liquid tube to filter drier. (See Fig.
NOTE: Install branch circuit disconnect of adequate size per NEC to handle unit starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC. A. ROUTE GROUND AND POWER WIRES Remove access panel to gain access to unit wiring.
To calculate additional charge requried for a 25-ft line set: 25 ft - 15 ft = 10 ft X 0.6 oz/f t=6o zo f additional charge. B. COOLING ONLY PROCEDURE UNITS WITH COOLING MODE PURON ® TXV Units installed with cooling mode TXV require charging by the subcooling method.
TABLE 3 — REQUIRED LIQUID-LINE TEMPERATURE ( ° F) LIQUID PRESSURE AT SERVICE VALVE (PSIG) REQUIRED SUBCOOLING TEMPERATURE ( ° F) 8 1 01 21 41 61 8 189 58 56 54 52 50 48 195 60 58 56 54 52 50 202 6.
TABLE 5 — REQUIRED SUCTION-LINE TEMPERATURE SUPERHEAT TEMP ( ° F) SUCTION PRESSURE AT SERVICE PORT (PSIG) 107.8 112.2 116.8 121.2 126.0 130.8 138.8 140.
PURON ®— QUICK REFERENCE GUIDE • Puron ® refrigerant operates at 50-70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with Puron ® . • Puron ® refrigerant cylinders are rose colored.
24 VAC HOT 24 VAC COM R C G W/W1 Y/Y2 R C C BRYANT NON-PROGRAMMABLE THERMOSTAT MODEL AC SINGLE-STAGE FURNACE AIR CONDITIONER SEE NOTE 2 Y G W HEAT STAGE 1 COOL STAGE 1 INDOOR FAN A97359 24 VAC HOT R G.
24 VAC HOT R C W/W1 Y/Y2 G R DH W2 W1 Y/Y2 BRYANT NON-PROGRAMMABLE THERMOSTAT MODEL AC FK4C FAN COIL AIR CONDITIONER C INDOOR FAN HEAT STAGE 1 COOL STAGE 1 24 VAC COM Y1 C SEE NOTE 2 G O J2 JUMPER J1 .
デバイスBryant 556Aの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bryant 556Aをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBryant 556Aの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bryant 556Aの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bryant 556Aで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bryant 556Aを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBryant 556Aの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bryant 556Aに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBryant 556Aデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。