Cancels: II 580F-36-3 II 580F-36-4 1/15/04 IMPORT ANT — READ BEFORE INST ALLING 1. Read an d become fam iliar w ith these install ation instruc tions b efore inst alling this uni t (Fig . 1A and 1B). 2. Be su re th e ins talla tion co nform s to a ll appl icab le lo- cal and natio nal codes.
— 2 — Fig. 1A — Base Unit Di m ensions — 580F0 36-072.
— 3 — Fig. 1B — Base Unit Di m ensions — 580F073.
— 4 — B. Slab Mount ( Hori z ontal Units Only ) Provide a leve l concrete sla b that extend s a minimum of 6 in. beyond unit c abi ne t. I nsta ll a grav el apr on in f ron t of con dens er coil air in let to pre vent grass and folia ge from obs tructing ai rflow .
— 5 — Fig. 3 — Roof Curb ROOF CURB ACCES SO R Y A UNIT SI Z E CRRFCURB001A01 1 ′ -2 ″ [356] 580F 036-073 CRRFCURB002A01 2 ′ -0 ″ [610] NO TES: 1. Roof curb accessory is shipped dis assembled. 2. Insulat ed panels. 3. Dimensions in [ ] are in millimeters.
— 6 — Do no t insta ll unit in an in door l ocation. Do not locat e unit air in lets near e xhaust vents or other sour ces of contami- nated air . Be sure that unit is installed such that snow will not block the comb ustion i nt ake or fl u e outlet .
— 7 — NO TES: 1. Dimensions in ( ) are in millimeters. 2. Hook riggi ng shackles thro ugh holes in base rail , as shown in detai l “A. ” Holes i n base rails ar e centered a round t he unit center of gravity . Use wooden top skid when r igging to prevent rigg ing straps from dam aging unit.
— 8 — Ta b l e 1 — P h ysical D ata LEGEND *Evaporator coi l fin mater ial/cond enser coi l fin mater ial. Cont act your local rep- resentati ve for details abou t coate d fins.
— 9 — Ta b l e 1 — P h ysical D ata ( cont ) LEGEND *Evaporator coi l fin mater ial/cond enser coi l fin mater ial. Cont act your local rep- resentati ve for details abou t coate d fins. †Weight of 14- in. roo f curb. **Singl e phase/th ree-phase.
— 10 — VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS A. Field P ower Supply All units except 208/230-v units are facto ry wired for the voltag e shown on th e namepl ate. If the 208/ 230-v u nit is to be connected to a 208-v power supply , the transformer must be rew ired by movi ng the black wire w ith th e 1 / 4 -in.
— 11 — RACEW A Y LOW V OL T AGE CONNECTIONS INTEGRA TED GAS UNIT CONTROLLER (IGC) HOLE IN END P ANEL (HIDDEN) LEGEND Fig. 9 — P owe r Wiring Connections C— Contactor COMP — Compr essor IFC — Indoor-F an Contactor NEC — National Electr ical Code TB — T erminal Block Fig.
— 12 — T able 2A — Electrical Data ( Wit h out Co n venie nce Out let ) LEGEND *Used to determi ne minim um disconnect per N EC. †Fuse or HA CR circuit bre aker.
— 13 — T a ble 2 B — Ele ctr ical Data ( Wit h Con venience Outl et ) LEGEND *Used to determi ne minim um disconnect per N EC. †Fuse or HA CR circuit bre aker.
— 14 — VIII. STEP 8 — ADJUST F A CTO R Y-INST ALLED O PTIONS A. Manual Outdoor -Air Da m pe r The outdo or-air hood and s creen are attached to the basep a n at the bottom of the unit for shipping . Assembly: 1. Deter mine qu antity o f ventilat ion req uired for build- ing .
— 15 — B. Optional EconoMi$er+ See F ig. 16 for Econo Mi$e r + compon ent loc ations . NO TE: Th ese in structi ons ar e for the factory- inst alled optiona l EconoMi$ er+ onl y . Refe r to the acce ssory Econ oMi$e r+ insta llatio n instruc tions when field ins talling an Econ oMi$er + access ory .
— 16 — (FIELD-SUPPLIED) B TOP P ANEL INDOOR COIL ACCESS P ANEL 19 1/16 ” SCREW HOOD DIVIDER LEFT HOOD SIDE 33 3/8 ” 17 1/4 ” DIVIDER BAROMETRIC RELIEF CLEANABLE ALUMINUM FIL TER FIL TER HOOD FIL TER CLIP OUTSIDE AIR Fig. 21 — F ilter Installation LEGEND NO TES: 1.
— 17 — C. EconoMi$er+ Control Mode Dete rmine the Eco noMi$er+ co ntrol mode befor e install ing sensor s and accessorie s . Diffe rent sensors are r equired for different contr ol modes, and a number of accessories are avai la ble . Refer to T a bl es 3 and 4.
— 18 — T able 3 — EconoMi$er+ Sensor Usage NO TES: 1. CO 2 Sensors (Optional, 5-P in sensor wiring p lug CRE + PLUG001A00 required for install ation.). 33ZCSENCO2 — Ro om sensor (adjustable). Aspirator box is required f or duct mounting of the s ensor .
— 19 — The user ca n read the va lue of the s ensor using the Rea d mode, describ ed in the EconoMi$er+ Controller section. Mount the return air te mperature sensor on the EconoM i$er+, through pre -punched h oles. See Fig . 27. The return air temperature (RAT) sensor is provided with a 2-wire, 42-in.
— 20 — T able 5 — Outdoor Air , Return Air , and Supply Air T e m per atur e Se nsors ( CRTEMPSN001A00 or HH79N Z 03 9 ) — 10K T h er m istor Curve T able 6 — Outdoor Air , Return Air , and .
— 21 — Fig. 29 — Ent h alpy C h a ngeover Se ttings 20 18 16 14 12 10 8 6 4 01 0 2 0 3 0 40 50 60 70 80 90 100 RH (%) CURRENT (mA) 10 20 30 40 50 60 70 80 90 5.6 7.2 8.8 10.4 12.0 13.6 15.2 16.8 18.4 HUMIDITY IN % RH CURRENT IN mA RH — Relativ e Humidity Fig.
— 22 — L. Indoor Air Hu m id ity Senso r F or di fferent ial enthalpy sensing , the Ec onoM i$er+ contro l- ler uses the stan dard outdo or air temper ature se nsor , the outdoo r air hu midity se nsor , and the op tion al indoor air humidity s ensor , an opti onal re turn air t emperat ure se nsor (RAT ).
— 23 — minimum position (c onfigur ation item number 15), unless the remote potenti om ete r is used to override it. F or the demand venti lation control lo g ic, the user configures the lower and upper a ctuator position to establish the base ventila tion rate (I AQMIN_ SP) and the de sign ventilat ion rate (ECONOMIN_SP) for full occupancy .
— 24 — IX. STEP 9 — ADJUST EV APORA TOR-F AN SPEED Adjust evapor ator -fan rp m to meet j obsit e condi tions. T able 8 shows fan r pm at moto r pull ey set t i ngs . T able 9 shows motor performance. Refer to T ables 10-33 to determine fan spee d settings.
— 25 — Ta b l e 8 — F a n R p m at Motor Pulley Settings * *App roxi mate fan rpm sho wn. †Indica tes alter nate motor and dr ive package. **I ndic ate s high- stat ic mot or and driv e pack age . ††Indi cates standard mo tor and dr ive package.
— 26 — T a b l e1 1—F a nP e r f o r m ance 580F036 — V ertical Disc h ar ge Units, Alternate Motor ( Belt Drive )* LEGEND *Motor driv e range: 685 to 1045 rpm. All other r pms require a field- supplied drive . NO TES: 1. Boldface in dicates field-supp lied drive is req uired.
— 27 — T a b l e1 4—F a nP e r f o r m ance 580F048 — V ertical Disc h ar g e Units, Alternate Motor ( Belt Drive )* LEGEND *Motor driv e range: 770 to 1175 rpm. All other r pms require a field- supplied drive . NO TES: 1. Boldface in dicates field-supp lied drive is req uired.
— 28 — T a b l e1 6—F a nP e r f o r m anc e 580F 060 — V er t ical Di sc h arge Units, Stand ard Motor LEGEND See page 36 f or general f an perfo rmance notes. Ta b l e 1 7 — F a n P e r f o r m ance 580F0 60 — Single-P h a se, V er tical Disc h arge Unit, Alternate Motor ( Belt Drive )* LEGEND *Motor driv e range: 878 to 1192 rpm.
— 29 — T a b l e1 8—F a nP e r f o r m ance 580F060 — T h re e-P h ase, V er tical Disc h arge Unit s, Alternate Motor ( Belt Drive )* LEGEND *Motor driv e range: 878 to 1192 rpm. All other r pms require a field- supplied drive . NO TES: 1. Boldface in dicates field-supp lied drive is req uired.
— 30 — T able 2 0 — Fan Perfor m ance 5 80F072,07 3 — V er tical Dis c h ar ge Units, Standa rd Moto r ( Belt Drive )* LEGEND *Motor driv e ra nge: 1070 to 1460 rpm. All other rpms require a field- supplied dri ve. NO TES: 1. Boldface in dicates field-supp lied drive is req uired.
— 31 — T a b l e2 2—F a nP e r f o r m ance 580 F036 — Hori z on tal Disc h ar ge Units, Standard Mo tor LEGEND See page 36 f or general f an perf ormance notes . T a b l e2 3—F a nP e r f o r m anc e 580F036 — Hori z onta l Disc h arge Units, Alternate Motor ( Belt Drive )* LEGEND *Motor driv e range: 685 to 1045 rpm.
— 32 — T a b l e2 5—F a nP e r f o r m ance 580F04 8 — Hori z on tal Disc h ar ge Units, Standard Mo tor LEGEND See page 36 f or general f an perfo rmance notes. T a b l e2 6—F a nP e r f o r m anc e 580F048 — Hori z onta l Disc h arge Units, Alternate Motor ( Belt Drive )* LEGEND *Motor driv e range: 770 to 1175 rpm.
— 33 — T a b l e2 7— F a nP e r f o r m ance 580F 048 — Hori z ont al Disc h arge Units, Hig h -Static Motor ( Belt Drive )* LEGEND *Motor driv e ra nge: 1075 to 1455 rpm. All other rpms require a field- supplied dri ve. NO TES: 1. Boldface in dicates field-supp lied drive is req uired.
— 34 — T a b l e2 9—F a nP e r f o r m ance 580F06 0 — Single-P h as e , Hori z onta l Dis c h arge Un its, Alternate Motor ( Belt Drive )* LEGEND *Motor driv e range: 875 to 1192 rpm. All other r pms require a field- supplied drive . NO TES: 1.
— 35 — T a b l e3 1— F a nP e r f o r m ance 580F 060 — Hori z ont al Disc h arge Units, Hig h -Static Motor ( Belt Drive )* LEGEND *Motor driv e ra nge: 1300 to 1685 rpm. All other rpms require a field- supplied dri ve. NO TES: 1. Boldface in dicates field-supp lied drive is req uired.
— 36 — T able 3 3 — Fan P erfor m ance 580F 072,073 — Hori z ontal Dis c h arge U nits, H ig h -Static Motor ( Belt Drive )* LEGEND *Motor driv e ra nge: 1300 to 1685 rpm. All other rpms require a field- supplied dri ve. NO TES: 1. Boldface in dicates field-supp lied drive is req uired.
— 37 — PRE-ST ART -UP Procee d as follows to in spect and pr epare the unit for initial start -up : 1. Remo ve all access pane ls . 2. Read and foll ow instructions on all W ARNING , CA UTION , and INFORMA TION la bels attached to , or shipped with, the unit.
— 38 — The suc tion a nd disch a rge pre ssure l evels should no w move to their normal start-up levels. NO TE: When the comp ressor is rotating in the wrong di rec- tion, the un it makes an el evated lev el of n oise and do es not pro vide co oling.
— 39 — XII. SAFETY RELIEF A soft solder joint at the su c tion ser vice Sc hrader port pro- vides pressure relief un de r abnormal temperature and pres- sure co nditions (i.e ., fire in bui lding). XIII. VENTILA TION ( CONTINUOUS F AN ) Set fan and syste m selecto r switches at ON and OFF posi- tions, respecti vely .
— 40 — T able 35 — EconoMi$er+ Inputs and Outputs *If there are 3 stages the n there can only be 1 stag e of power e xh aust. †If there are 4 stag es then no power exhaust stages are dire ctly controlled . INPUT NAME TYPE U SE INPUT / OUTPUT RANGE CONVERSION RANGE CONVERSION RESOLUTION CONNECTION PIN NO .
— 41 — T a b l e3 6—S t a r t - U pM o d eS e q uence LED — Light-E mitting D iode T able 37 — Configuration V ariab les ( Read and Set up Mod es ) LEGEND NO TE: The accessibility of these cha nnels will be as follows: READ MODE — All channels will be access ible .
— 42 — After advanc ing throug h all the config uration vari ables in the Read mode, the control ler will then a dvance through t he status of the I/O channels.
— 43 — 6. V erify the conf igurati on point by pushing bu tton #1. The red LED should flash twice to indicate point 2, and th en the gr een LEDs w ill flas h the cu rrent setting. NO TE: Si nce the o ccupied minimum positio n MUST be 1 greater than the IAQ minimum position (i tem 15), the I AQ minimu m position must be cha nged first.
— 44 — IMPORT ANT : There is no way to reset/re store th e factor y defa ult c onfig urati ons; use ca utio n when makin g chan ges to any set po int or op eratio nal vari able. The EconoM i$er+ c ontrol accepts an occupie d/unoccupie d switch input.
— 45 — Compre ssor L ockout T emp erat ure Set the Compres sor Lockout T emp erature. The Compresso r Loc kout T emperatur e (CM P_LOC K) is u sed to preven t com- pressor from r unning at low ambie nt conditi o ns whe n an Econ oMi$e r+ can easily sa tisfy t he lo ad.
— 46 — while th e unit is in coo ling. When th e thermost at is satis fied, C is deenergized and the compressor and OFM shut off . After a 30-second de lay , the (IFM) shuts o ff . If the thermostat fan sel ector sw itch i s in th e ON posi tion , the eva porator mot or will run continuousl y .
— 47 — As an example, if local codes requir e 10% outdoo r air durin g occu pied condi tions , outdoo r -air temp eratu r e i s 60 F , and retur n-ai r tem p eratu re is 75 F: (60 x 0. 10) + (7 5 x 0.90 ) = 73.5 F Carefully adju st the unocc upied minimum position until the measur ed supply-a i r temp erature ma t ches the calculated valu e.
— 48 — II. LUBRICA TION A. Co m press ors Each compress or is charged wi th the cor rect amount of oil at the factor y . B. Fan Moto r Bearings F an moto r bearings ar e of the perm anently lubr icated type. No furt her lu bricati on is req uired .
— 49 — IX. COMBUSTION-AIR BLO WER Clean perio dically to assure p roper airflow and heating effi- ciency . Inspect blow er whee l ev ery fa ll and p eri odical ly during heating season. F or the first heating seaso n, inspect blower wheel bimonthly to determine proper cle aning frequency .
— 50 — 4 TON UNIT CHARGING CHART 30 40 50 60 70 80 90 100 20 30 40 50 60 70 80 SUCTION LINE TEMPERA TURE (DEG. F) 207 276 345 414 483 552 621 689 - 7 - 1 4 1 01 62 12 7 SUCTION LINE TEMPERA TURE (DEG.
— 51 — 5 TON UNIT CHARGING CHART 30 40 50 60 70 80 90 100 20 30 40 50 60 70 80 SUCTION LINE TEMPERA TURE (DEG. F) 207 276 345 414 483 552 621 689 -7 -1 4 10 16 21 27 SUCTION LINE TEMPERA TURE (DEG.
— 52 — Fig. 46 — Burner T ray Details Fig. 47 — Spark Adjust m ent LO W HEA T 580F036-073 — 74,000 BTUH INP UT 580F036-060 (Low NO x ) — 60,000 BTUH I NPUT MEDIUM AND H IGH HEA T 580F036-0.
— 53 — TROUBLESHOO TING I. ECONOMI$ER+ TR OUBLESHOO TING The Eco noMi$ er+ con trol has built-i n diagno stics . The con- trol can detect and display 10 di fferent diagnostic codes as shown in T able 40.
— 54 — Reset Method This erro r must b e manu ally reset and requ ires a po wer reset. H. E rror Cod e 8 — E 2 T es t Failu re Error Criter ia This error occu rs if internal h ardware detects an E2 failure. Required Acti on Shut the un it of f. Reset Method This erro r must b e manu ally reset and requ ires a po wer reset.
— 55 — T a b l e4 1—L E DE r r o rC o d eS e r v i c eA n a l y s i s IMPORT ANT : Ref er to T able 42 — Heating Service Analysis for addit ional troubl esho otin g anal ysis. LEGEND T able 42 — Heating S ervice Ana lys is SYMPT OM CA USE REMED Y Hardware Failure .
— 56 — T able 43 — Cooling S ervice Ana lysis PRO BLEM CA USE REMED Y Co m pre ssor a nd Con den ser Fan Will Not Sta rt. P ower f ailure. Call pow er compan y . Fuse blo wn or circuit bre aker tripped. Replace fuse or reset circuit brea ker . Defecti ve ther mos tat, cont acto r , t ransfor mer, or control rel a y .
— 57 — Fig. 48 — T ypical Unit Wiring Diag ra m LEGEND OFM — Outdoor (Co ndense r) F an Moto r OLR — Overl oad Rela y P— Plug PL — Plug Assembly Q T— Quad ruple T er minal RS — Rollo.
— 58 — APPENDIX A — ECONOMI$ER+ LABEL Button 1 Button 2 DS1 (Red) DS2 (Y ellow) DS3 (Green) DS4 (Green) Action flash flash flash flash Note 1 Indicators flash in sequence at .
— 59 — APPENDIX A — ECONOMI$ER+ LABEL ( cont ).
— 60 — APPENDIX B — JOB SPECIFIC ECONOMI$ER+ CONFIGURA TION SETTINGS Enter the job speci fic settings in the “Job Setting” column below ..
— 61 — INDEX Access panel s 15 Altitude com pensati on 38 Barometric flow capacity 17 Burner ignition 49 Burner r ack 52 Burn er secti on 52 Burn er sp ark ga p 52 Char ging chart, refrigera nt 50.
Copyright 2004 Bryant Heating & Cooling Systems CA T ALOG NO. 5358- 023 SER VICE TRAINING P ackaged Service Training pr ograms are an excelle nt way to incre ase your know ledge of the equipment d.
.
Copyright 2004 Bryant Heating & Cooling Systems CL-1 CA T ALOG NO. 5358-0 23 CUT A LON G DOTTED L INE CUT ALONG DOTTED LINE ST ART -UP CHECKLIST ( Re m ov e and Use in Job File ) I. PRELIMINAR Y INFORMA TION: MODEL NO.: _____ __ _____ ______ _____ __ ____ _______ ___ SERIAL NO.
デバイスBryant 580fの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bryant 580fをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBryant 580fの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bryant 580fの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bryant 580fで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bryant 580fを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBryant 580fの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bryant 580fに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBryant 580fデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。