IMPORT ANT — READ BEFORE INST ALLING 1. Read and become familiar with these installation in- structions before installing this unit (Fig. 1). 2. Be sure the installation conforms to all applicable local and national codes. 3. These instructions contain important information for the proper maintenance and repair of this equipment.
UNIT 581B ST ANDARD UNIT WEIGHT V ARISLIDE™ ECONOMIZER WEIGHT CORNER WEIGHT ‘‘ A’’ CORNER WEIGHT ‘ ‘B’’ CORNER WEIGHT ‘ ‘C’’ CORNER WEIGHT ‘ ‘D’’ Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg 036 530 240 34 15.4 127 57.6 122 55.
INST ALLA TION Unit is shipped in the vertical airflow configuration. See Fig. 1. T o convert to horizontal discharge, remove horizontal duct opening covers. Using the same screws, install covers with insulation-side down (facing outside) on the unit on ver- tical duct openings.
Fig. 4 — Roof Curb Dimensions ROOF CURB ACCESSOR Y ‘‘A ’ ’ UNIT SIZE CRRFCURB001A00 14 9 [356] 581B036-072 CRRFCURB002A00 24 9 [610] NOTES: 1. Roof curb accessory is shipped disassembled. 2. Insulated panels. 3. Dimensions in [ ] are in millimeters.
II. UNIT DUCT CONNECTIONS On vertical units, secure all ducts to roof curb and building structure. Do not connect ductwork to unit. On horizontal units, duct flanges should be attached to horizontal openings and all ductwork should be secured to flanges.
T able 1 — Specifications BASE UNIT 581B 036 048 060 072 NOMINAL CAP ACITY (tons) 3 456 OPERA TING WEIGHT (lb) Unit 530 540 560 615 With Economizer 564 574 594 649 Roof Curb 11 5 11 5 11 5 11 5 COMPRESSOR Scroll Quantity 1 111 Oil (oz) 42 53 50 60 REFRIGERANT TYPE R-22 Operating Charge (lb-oz) 5-8 8-6 10.
IV . FIELD CONNECTIONS A. External T rap Condensate Drain The unit’ s 3 ⁄ 4 -in. condensate drain connections are located at the bottom and side of the unit. Unit discharge connec- tions do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
T able 2 — Maximum Gas Flow Capacity of Pipe in Cubic Ft of Gas Per Hour for Gas Pressures of 0.5 Psig or Less and a Pressure Drop of 0.5 in. wg (Based on a 0.60 Specific Gravity Gas) NOMINAL IRON PIPE SIZE (in.) INTERNAL DIAMETER (in.) LENGTH OF PIPE, FT* 10 20 30 40 50 60 70 80 90 100 125 150 175 200 1 ⁄ 2 .
Liquid Propane Units are shipped for use with natural gas, but may be field- converted for use with liquid propane with accessory LP (liq- uid propane) kit. All LP gas equipment must conform to NFP A safety standards. LP gas pressure at the unit must not be less than 5 in.
3. V oltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see T ables 3A and 3B). On 3-phase units, voltages be- tween phases must be balanced within 2% and the cur- rent within 10%. Use the formula shown in T ables 3A and 3B, Note 2, to determine the percent voltage im- balance.
High-V oltage Connections (Fig. 13) The unit must have a separate electrical service with a field- supplied, waterproof, fused disconnect switch mounted at, or within sight from the unit. Refer to the unit rating plate for maximum fuse/circuit breaker size and minimum circuit amps (ampacity) for wire sizing.
T able 3B — Electrical Data (Units with Electrical Convenience Outlet) UNIT 581B NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM IFM COMBUSTION F AN MOTOR POWER SUPPL Y WITH OUTLET MINIMUM UNIT DISCONNECT SIZE* Min Max RLA LRA FLA FLA FLA MCA MOCP† FLA LRA 036 (3 T ons) 208/230-1-60 187 254 16.
Heat Anticipator Setting The room thermostat heat anticipator must be properly ad- justed to ensure proper heating performance. Set the heat anticipator , using an ammeter to determine the exact re- quired setting. NOTE: For thermostat selection purposes, use .
8. Remove tape from outdoor-air thermostat (OA T). Fas- ten OA T to inside of hood using screws and speed clips provided. See Fig. 23. Make sure OA T terminals are positioned up. 9. Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel.
Save panels and screws. Remove optional economizer so the outdoor-air damper hood package can be re- moved from the filter section. See Fig. 16. 3. Assembly outdoor-air hood top and side plates as shown in Fig. 17. Install seal strips on hoop top and sides.
d. After installation is complete, calculate the mini- mum airflow across the economizer . T o calculate the minimum airflow , the following data is needed: total cfm (cfm 3 ), temperature of the total cfm (T 3 ), temperature of the return air (T 2 ), and tempera- ture of the entering outside air (T 1 ).
PRE-ST ART -UP W ARNING: Failure to observe the following warn- ings could result in serious personal injury: 1. Follow recognized safety practices and wear pro- tective goggles when checking or servicing refrig- erant system.
II. HEA TING SECTION ST ART -UP AND ADJUSTMENTS CAUTION: Complete the required procedures given in the Pre-Start-Up section on this page before starting unit. Do not jumper any safety devices when operating the unit. Ensure that burner orifices are properly aligned.
T able 5 — Rated Gas Inputs at Indicated Manifold Pressures UNIT 581B NUMBER OF ORIFICES GAS SUPPL Y PRESSURE (in. wg) MANIFOLD PRESSURE (in. wg) NA TURAL GAS PROP ANE* Natural Propane Orifice Drill Size Heating Input (Btuh)† Orifice Drill Size Heating Input (Btuh)† Min Max Min Max Natural Propane 036-072** 2 4.
NOTE: The gas manifold is equipped with a plug located ap- proximately 5 in. down from the gas valve which may also be used to connect the manometer . 4. T urn on gas to unit. 5. Remove cover screw over regulator adjustment screw on gas valve. See Fig.
event of flame rollout. The switch is located above the main burners on the internal wind baf f le. When the temperature at the rollout switch exceeds the maximum allowable tem- perature, the W control circuit trips, deenergizing the gas valve and stopping gas flow to the burners.
When the second stage of cooling is satisfied, the compressor and OFM will be deenergized. The damper position will be determined by the supply-air temperature. When the first stage of cooling is satisfied, there is a 30-second delay before evaporator shuts of f (036-060).
B. V entilation Sequence If unit is equipped with an economizer , the damper will open to the minimum position whenever the evaporator fan runs. The damper motor will be energized with 24 vac power and damper will drive open until SW3 on the damper is de- activated.
T able 9 — 581B036 Air Delivery — V ertical Discharge Units AIRFLOW (Cfm) BEL T DRIVE MOTOR External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 581 0.12 673 0.18 736 0.22 805 0.25 865 0.29 91 1 0.
T able 1 1 — 581B060 Air Delivery — V ertical Discharge Units AIRFLOW (Cfm) BEL T DRIVE MOTOR External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 771 0.37 828 0.44 935 0.58 1027 0.73 1 107 0.
T able 13 — 581B036 Air Delivery — Horizontal Discharge Units AIRFLOW (Cfm) BEL T DRIVE MOTOR External Static Pressure (in. wg) 0.1 0.2 0.3 0.4 0.5 0.6 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 900 526 0.06 584 0.08 656 0.12 734 0.22 818 0.25 875 0.
T able 15 — 581B060 Air Delivery — Horizontal Discharge Units AIRFLOW (Cfm) BEL T DRIVE MOTOR External Static Pressure (in. wg) 0.1 0.2 0.4 0.6 0.8 1.0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 741 0.38 798 0.43 895 0.54 990 0.67 1073 0.
CARE AND MAINTENANMCE T o ensure continuing high performance and to minimize the possibility of premature equipment failure, periodic mainte- nance must be performed on this equipment. This combina- tion heating/cooling unit should be inspected at least once each year by a qualified service person.
D. Filters Clean or replace at start of each heating and cooling season, or more often if operating conditions require it. Replacement filters must be same dimensions as original filters. E. Outdoor-Air Inlet Screens Clean screens with steam or hot water and a mild detergent.
B. Low Charge Cooling Using Cooling Charging Charts, Fig. 39-42, vary refrigerant until the conditions of the appropriate chart are met. Note the charging charts are dif ferent from type normally used. Charts are based on charging the units to the correct super- heat for the various operating conditions.
4. Slide the motor and blower wheel assembly out of the blower housing. The blower wheel can be cleaned at this point. If additional cleaning is required, continue with steps 5 and 6. 5. T o remove blower from the motor shaft, remove 2 setscrews. 6. T o remove motor , remove 4 screws that hold the motor to mounting plate.
A. Removal and Replacement of Gas T rain (See Fig. 31 and 43.) 1. Shut off manual gas valve. 2. Shut off power to unit. 3. Remove compressor access panel. 4. Slide out burner compartment side panel. 5. Remove heat shield. 6. Disconnect gas piping at unit gas valve.
TROUBLESHOOTING T able 18 — LED Error Code Service Analysis PROBLEM CAUSE REMEDY Hardware failure. (LED Off) Loss of power to IGC. Check 5-amp fuse on IGC, power to unit, 24-v circuit breaker , and transformer . Units without a 24-v circuit breaker have an internal over- load in the 24-v transformer .
T able 20 — Cooling Service Analysis PROBLEM CAUSE REMEDY Compressor and condenser fan will not start. Power failure. Call power company . Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker . Defective thermostat, contactor , transformer, control relay or capacitor .
T able 21 — V arislide™ Economizer T roubleshooting PROBLEM CAUSE REMEDY Damper does not open. Indoor (evaporator) fan is off. 1. Check to ensure that 24 vac is present at terminal C1 on the IFC or that 24 vac is present at the IFO terminal. Check whether 24 vac is present at PL6-1 (red wire) and/or PL6-3 (black wire).
T able 22 — P ARABLADE Economizer T roubleshooting PROBLEM CAUSE REMEDY Damper does not open. Evaporator fan not on. Check wiring between G on connection board and indoor fan contactor . No power to economizer motor . 1. Disconnect power at TR and TR1.
Fig. 45 — T ypical Wiring Schematic and Component Arrangement —37—.
LEGEND AND NOTES FOR FIG. 45 — TYPICAL CONTROL WIRING SCHEMA TIC AND COMPONENT ARRANGEMENT AHA — Adjustable Heat Anticipator C— Contactor , Compressor CAP — Capacitor CC — Cooling Compensato.
.
ST ART -UP CHECKLIST (Remove and Store in Job File) I. PRELIMINARY INFORMA TION MODEL NO.: DA TE: SERIAL NO.: TECHNICIAN: II. PRE-ST ART -UP (insert checkmark in box as each item is completed) M VERIF.
デバイスBryant 581Bの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bryant 581Bをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBryant 581Bの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bryant 581Bの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bryant 581Bで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bryant 581Bを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBryant 581Bの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bryant 581Bに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBryant 581Bデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。