Form No. PDS 593C.18.7 ELECTRIC AIR CONDITIONER Model 593C (60 Hz) Sizes 018 thru 060 WEA THER-PRO TECTIVE CABINET —Steel is galvaniz ed and coated with a la yer of zinc phosphate . A coat of modified poly- ester powder coating is then applied and bak ed-on, providing each unit with a hard, smooth finish that will last f or many y ears.
— 2 — AIR DISCHARGE AIR DISCHARGE AIR IN AIR IN AIR IN 3 / 8 " DIA. TIEDOWN KNOCKOUTS (2) PLACES L K J E D C L NOTES: 1. ALLOW 30" CLEARANCE TO SERVICE SIDE OF UNIT, 48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE, AND 24" BETWEEN UNITS FOR PROPER AIRFLOW.
— 3 — RECOMMENDED TUBE DIAMETERS * For tube sets betw een 50 and 175 ft, consult Residential Split System Long-Line Application Guideline. CHECK-FLO-RA TER ® PIST ON * Piston listed is f or any appro ved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an appro ved indoor coil.
— 4 — SPECIFICA TIONS See notes on page 5. UNIT SIZE 018-C, D 024-C, D 030-C, D 036-C, D Operating W eight (Lb) 137 143 161 169 ELECTRICAL Unit V olts — Her tz — Phase 208 – 230 — 60 — 1 Operating V oltage Range* 197 — 253 Compressor — Rated Load Amps 8.
— 5 — SPECIFICA TIONS Continued * P er missible limits of the v oltage range at which the unit will operate satisf actorily . Operation outside these limits may result in unit f ailure. † If wire is applied at ambient greater than 30 ° C (86 ° F), consult T able 310-16 of the NEC (ANSI/NFP A 70).
— 6 — A CCESSOR Y DESCRIPTION AND USA GE (Listed Alphabetically) 1. Ball Bearing Fan Motor A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation f eature) or MotorMaster ® Control has been added.
— 7 — A CCESSOR Y DESCRIPTION AND USE (Listed Alphabetically) Continued 17. Time Delay Rela y An SPST dela y relay which brie fl y continues oper ation of the indoor blower motor to pro vide additional cooling after the compressor cycles off.
— 8 — COMBINA TION RA TINGS See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 018-C, D CC5A/CD5AA018* 17,200 NONE 10.
— 9 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 030-C, D CC5A/CD5AA030* 28,600 NONE 10.
— 10 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D CC5A/CD5AA036* 34,600 NONE 10.
— 11 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 036-C, D COILS + 355MA V042040 V ARIABLE-SPEED FURNA CE CC5A/CD5AA036 34,600 NONE 11.
— 12 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 042-C, D CK5A/CK5BA042 39,500 TDR 11 11 10.
— 13 — COMBINA TION RA TINGS Contin ued See notes on page 14. UNIT SIZE-SERIES INDOOR MODEL TOT . CAP . BTUH F ACT ORY- SUPPLIED ENHANCE- MENT ST ANDARD RA TING BR Y ANT GAS FURNA CE OR A CCESSORY TDR † A CCESSORY TXV ‡ 048-C FB4(A,B)NB070 48,000 TDR 11.
— 14 — COMBINA TION RA TINGS Contin ued * T ested combination. † In most cases, only 1 method should be used to achie ve TDR function. Using more than 1 method in a system may cause deg radation in performance. Use either the accessory Time-Dela y Relay KAA TD0101TDR or a fur nace equipped with TDR.
— 15 — DET AILED COOLING CAP ACITIES* See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** Capacity MBt.
— 16 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 17 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 18 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 19 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 20 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 21 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 22 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 23 — DET AILED COOLING CAP ACITIES* Contin ued See notes on page 24. EV APORA T OR AIR CONDENSER ENTERING AIR TEMPERA TURES ° F 85 95 105 115 125 CFM EWB Capacity MBtuh † T otal System kW** C.
— 24 — DET AILED COOLING CAP ACITIES* Contin ued NO TE: When the required data fall betw een the published data, interpolation may be perf ormed. Extrapolation is not an acceptab le practice. * Detailed cooling capacities are based on indoor and outdoor unit at same ele vation per ARI standard 210/240-94.
— 25 — CONDENSER ONL Y RA TINGS* See notes on page 26. SST ° F CONDENSER ENTERING AIR TEMPERA TURES ° F 55 65 75 85 95 105 115 593C018-C, D TCG 17.9 16.6 15.3 14.0 12.7 11.3 10.0 30 SDT 75.7 84.2 93.0 102.0 111.0 120.0 129.0 KW 1.10 1.18 1.26 1.
— 26 — CONDENSER ONL Y RA TINGS* Continued * ARI listing applies only to systems shown in Ratings and P erformance table. KW — T otal P ower (kW) SDT — Saturated T emperature Lea ving Compress.
— 27 — SYSTEM DESIGN 1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan e xter nal static pressure av ailable is less than 0.01-in. wc. 2. Minimum outdoor operating air temperature without lo w ambient operation accessor y is 55 ° F (12.
— 28 — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Cancels: PDS 593C.18.6 © 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St., Indpls., IN 46231 PRINTED IN U.S.A.
デバイスBryant 593Cの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bryant 593Cをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBryant 593Cの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bryant 593Cの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bryant 593Cで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bryant 593Cを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBryant 593Cの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bryant 593Cに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBryant 593Cデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。