NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage.
When outdoor unit is connected to factory-approved indoor unit, outdoor unit contains system refrigerant charge for operation with indoor unit of the same size when connected by 15 ft of field-supplied or factory accessory tubing. For proper unit opera- tion, check refrigerant charge using charging information located on control box cover.
CAUTION: Remove indoor coil piston if unit is to be installed on system with a TXV metering device. Check outdoor unit piston. Remove retainer on liquid service valve and check piston size with matching number listed on outdoor unit rating plate. VII.
IX. MAKE ELECTRICAL CONNECTIONS WARNING: To avoid personal injury or death, do not supply power to unit with compressor terminal box cover removed. Be sure field wiring complies with local and national fire, safety, and electrical codes, and voltage to system is within limits shown on unit rating plate.
24 VAC HOT R G W/W1 Y/Y2 O/W2 R W2 W3 E RVS COOLING C B S1 S2 W2 BRYANT PROGRAMMABLE THERMOSTAT MODEL HP FA, FB, FC, FD, FF, FH FAN COIL HEAT PUMP G Y1/W2 L R O INDOOR FAN HEAT STAGE 2 COOL/HEAT STAGE 1 NOT USED 24 VAC COM NOT USED TROUBLE OPTIONAL OUTDOOR SENSOR CONNECTION Y C C * * * IF AVAILABLE * A97370 Fig.
24 VAC HOT R C W2 Y G R C RVS COOLING C W2 OTHER HP THERMOSTAT FA, FB, FC, FD, FF, FH FAN COIL HEAT PUMP G O E W2 E W3 R Y 24 VAC COM HEAT STAGE 2 COOL/HEAT STAGE 1 INDOOR FAN EMERGENCY HEAT O * * * IF AVAILABLE * A97374 Fig.
CAUTION: To prevent personal injury wear safety glasses, protective clothing, and gloves when handling refrigerant and observe the following: • Back-seating service valves are not equipped with Schrader valves. Fully back seat (counterclockwise) valve stem before removing gage-port cap.
3. Restart unit in heating mode, allowing frost to accumulate on outdoor coil. 4. After a few minutes in heating mode, liquid line tempera- ture should drop below closing point of defrost thermostat (approximately 30 ° F). 5. Short between speed-up terminals with a flat-bladed screw- driver.
デバイスBryant 661Sの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Bryant 661Sをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBryant 661Sの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Bryant 661Sの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Bryant 661Sで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Bryant 661Sを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBryant 661Sの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Bryant 661Sに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBryant 661Sデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。