FAN UNIT

FH4B

Sizes 001 thru 004

PRACTICALITY & PERFORMANCE

Reliability, dependability, and great value are built into the FH4B Fan Units. The unit is compact and easy to install, with capacities ranging from 800 to 2000 CFM. The units are the right choice if you need versatility and affordability in a fan unit.

These fan coil units offer an air handler for practical, no-non- sense application and outstanding performance. The multipoise units allow greater flexibility to meet your upflow, downflow, or horizontal installation requirements, and offer multiple electric entry to permit quick, hassle-free hookup (003 and 004 when coupled with coil are upflow/downflow only). All models come fully equipped with solid-state cooling controls.

The FH4B, with its 3-speed motor and field-installed heater package, provides the application versatility required for most installations. Heater packages are available from 3- through 30- kw, either fused or with a circuit breaker, or non-fused for 10-kw and less.

Form No. PDS FH4B.01.3

Page 2 of the Bryant FH4B user manual — R
2ページ · クリックして拡大
2ページ

FEATURES

•

Prepainted galvanized sheet metal

•

Cooling controls with every unit

•

•

Unique cabinet design to meet air leakages regulations

•

•

Easy access filter for cleaning—no tools required

•

Air sealed filter door

•

Field-installed heater packages 3- through 30-kw, fused, circuit breaker, non-fused (10-kw and down)

•

•

Control board with replaceable 5-amp blade type auto fuse

•

Foil-faced high-density super thick R-4.2 insulation

•

•

HUD approved for manufactured housing

•

•

All models listed with UL (U.S. and Canada) and ARI

MODEL NUMBER NOMENCLATURE

F H 4 B N F 001 015 AEAA

A—Common Unit E—Minor Engineering Change A—Standard Unit A—Standard Unit

Electric Heater (kw) 003 015 005 020 008 024 009 030 010

001—1800 CFM 002—1200 CFM 003—1600 CFM 004—2000 CFM

F— Single Piece Cabinet with 1 in.

N—208/230-1-60

E

D

T

O

E

D

T

O

E

R

T

F

R

S

E

R

T

F

R

S

Bryant FH4B — N—208/230-1-60 diagram (page 2)
図 1

R

E

R

H

O

M

R

E

R

R

O

M

T

U

T

R

Y

E

T

P

P

Y

T

U

T

R

Y

O

N

D

P

Y

F

U

N

U

M

P

N

G

F

U

N

T

O

N

N

G

N

U

T

W

N

U

N

G

T

W

M

H

M

H

E

Q

U

P

M

E

N

T

E

Q

U

P

M

E

N

T

R

S

T

R

D

R

S

T

R

D

N

D

N

D

REGISTERED

QUALITY SYSTEM

CERTIFICATION APPLIES ONLY WHEN THE COMPLETE SYSTEM IS LISTED WITH ARI.

Show 11 more labels / short text on this page
3-speed motor · Factory-supplied cleanable filter · Factory-supplied power plug · Multiple electric entry · 40-va, 208/230-v transformer · Super Thick Insulation · B—Series · 4—Multipoise · H—Fan Unit · F—Fan Coil · ®
Page 3 of the Bryant FH4B user manual — DIMENSIONS
3ページ · クリックして拡大
3ページ

DIMENSIONS

Bryant FH4B — DIMENSIONS diagram (page 3)
図 2
Bryant FH4B — DIMENSIONS diagram (page 3)
図 3
UNITSERIESAB CFACCY. COIL CONFIGURATION OPERATING ” WEIGHT (Lb) In.In. In.In.SLOPE “A FH4BNF001E42-11/1614-5/16 12-7/1612-5/16175 FH4BNF002E49-5/817-5/8 15-3/415-5/8192 FH4BNF003E49-5/821-1/8 19-1/419-1/8106 FH4BNF004E53-7/1621-1/8 19-1/419-1/8114.5
Page 4 of the Bryant FH4B user manual — DIMENSIONS Continued
4ページ · クリックして拡大
4ページ

DIMENSIONS Continued

Bryant FH4B — DIMENSIONS Continued diagram (page 4)
図 4 · DIMENSIONS Continued
Page 5 of the Bryant FH4B user manual — Field-modified Side Return Location
5ページ · クリックして拡大
5ページ

DIMENSIONS Continued

POWER ENTRY

FIELD SUPPLIED SUPPLY DUCT

OPTIONS

LOW VOLT ENTRY OPTIONS

24-IN. FRONT SERVICE CLEARANCE

UNIT FH4B001 FH4B002

A 12 In. 17 In.

1 Ω ″

FIELD MODIFIED SIDE RETURN LOCATION FOR SLOPE COIL UNITS ONLY

2 Ω ″

FIELD SUPPLIED RETURN PLENUM

*Side Return not compatible when used in conjunction with accessory cooling coil

Field-modified Side Return Location

For Slope Coils Only

19″

Page 6 of the Bryant FH4B user manual — SPECIFICATIONS
6ページ · クリックして拡大
6ページ

SPECIFICATIONS

UNIT SIZE001002003004 FAN Air Discharge CFM (Nominal) Motor Hp (PSC)850 1/41300 1/31700 3/42000 3/4 FILTER21-1/2 x 1321-1/2 x 16-3/821-1/2 x 19-7/8 AIRFLOW PERFORMANCE* (CFM) SIZEBLOWER SPEEDEXTERNAL STATIC PRESSURE (IN. WC) 0.100.200.300.400.500.60 208230208230208230208230208230208230 FH4B001HIGH117312701135122510901170104511269931058925981 MED9001025875991847963810922768869695802 LOW579687560663537639505610451554384467 FH4B002HIGH163018411605179815671748152516961480162914151560 MED124414381225140711901383117013421141130811001265 LOW1001117298511479551116930109490810628501024 FH4B003HIGH————2118—206022021949210618531989 MED175720611745201617341985171619431686189016241802 LOW129015351286153512811528127715151263146712451431 FH4B004HIGH————2257—2235—2188—21132336 MED——1930221519142196188721631838210617872047 LOW162018811620187016131864160718531594183615621802 * With factory approved filter, 10-kw elec heat 001 and 002 sizes, 15-kw elec heat 003 and 004 sizes 230-volt. AIRFLOW PERFORMANCE WITH ACCESSORY COIL (CFM) MODEL AND SIZEBLOWER MOTOR SPEEDTOTAL EXTERNAL STATIC PRESSURE (IN. WC) 0.100.200.300.400.500.60 208230208230208230208230208230208230 FH4B001 WITH KFAEC0501024HIGH945975900930840870780805695725560595 MED835900795855745800690740610650470510 LOW605695575665530625485580425510340395 FH4B002 WITH KFAEC0601036HIGH148515501425149013651420130013501230127511501190 MED12351380120013251160126511101210105511409851070 LOW1035118510101150980111594010708901010825935 FH4B003 WITH KFAEC0301048HIGH188019351785183017001735161516451520155514301460 MED174018401660175015851660151015751435148513501390 LOW142516051395155513601495131514301255136011701270 FH4B004 WITH KFAEC0401060HIGH214522452085218520302115196520451905197518301895 MED202521751970211019152050186019901805190517401830 LOW168018951655185516251810159517651555170515001645 NOTES: 1. Airflow based upon dry coil at 230v with factory approved accessory filter and electric heater (10-kw electric heat, sizes 001 and 002; 15-kw electric heat, sizes 003 and 004). 2. To avoid potential for condensate blowing out of drain pan prior to making drain trap: —Return static pressure must be less than 0.4 in. wc —Horizontal applications of 048-070 sizes must have supply static greater than 0.20 in. wc Airflow outside max ARI airflow of 450 cfm/ton on 018-154 sizes Airflow above 400 cfm/ton on 060-070 sizes. Airflows in this region could result in condensate blowing off coil or splashing out of drain pan. FILTER STATIC PRESSURE DROP (IN. WC) UNIT SIZECFM 400600800100012001400160018002000 001—0.0440.0750.110————— 002———0.0720.1000.130——— 003—————0.0920.1200.152— 004——————0.1200.1520.187
Page 7 of the Bryant FH4B user manual — FAN COIL ELECTRICAL DATA (UNITS WITHOUT ELECTRICAL HEAT)
7ページ · クリックして拡大
7ページ

FAN COIL ELECTRICAL DATA (UNITS WITHOUT ELECTRICAL HEAT)

UNIT SIZEVOLTS (1 PHASE)FLAMIN CKT AMPSBRANCH CIRCUIT Min Wire Size AWG*Fuse Amps 001208/2301.82.31415 002208/2302.73.41415 003208/2304.35.41415 004208/2305.46.81415 * Use copper wire only. 75°C must be used in this application. When using non-metallic (NM) sheathed cable, wire size required should be based on that of 60°C conductors, instead of wire sizes shown in table above per NEC 1999 Article 336-26. FLA — Full Load Amps NOTE: If branch circuit wire length exceeds 100 ft., consult NEC 215-2 to determine maximum wire length. Use 2% voltage drop. ELECTRIC HEATER INTERNAL PROTECTION* HEATER KWPHASEFUSES QTY/SIZECKT BKR QTY/SIZE† 31—— 51—1/60 81—1/60 101—1/60 1512/30 – 2/602/60 2014/602/60 243/16/60— 303/16/60— 91/3**—— 153—— 183—— * 5-, 8-, 10-kw factory-installed heat has no internal protection. 15-kw factory-installed heat is internally protected with fuses. ** KFCEH1401N09 is single phase only. † Circuit breakers are 2 pole. ELECTRIC HEATERS HEATER PART NO.KW @ 240VVOLTS/PHASESTAGES (KW OPERATING)INTERNAL CIRCUIT PROTECTIONFAN COIL SIZE USED WITHHEATING CAP. ** @ 230V KFCEH0401N033230/13None0019,400 KFCEH0501N055230/15None001, 00215,700 KFCEH0801N088230/18None001–00425,100 KFCEH0901N1010230/110None001–00431,400 KFCEH3201F2020230/15, 20Fuse‡002–00462,800 KFCEH160131515230/35, 15None002–00447,100 KFCEH200131818230/36, 12, 18None003, 00456,500 KFCEH3401F2424230/3*8, 16, 24Fuse003, 00475,300 KFCEH3501F3030230/3*10, 20, 30Fuse003, 00494,100 KFCEH2401C055230/15Circuit Breaker001, 00215,700 KFCEH2501C088230/18Circuit Breaker001, 00225,100 KFCEH2601C1010230/110Circuit Breaker001–00431,400 KFCEH3301C2020230/15, 20Circuit Breaker002–00462,800 KFCEH2901N099230/1†3, 9None002–00428,200 KFCEH3001F1515230/15, 15Fuse‡001–00447,100 KFCEH3101C1515230/15, 15Circuit Breaker001–00447,100
Page 8 of the Bryant FH4B user manual — ESTIMATED SOUND POWER LEVEL (dBA)
8ページ · クリックして拡大
8ページ

SMART HEAT

HEATER PART NO.KW @ 240VVOLTS/PHASESTAGES (KW OPERATING)INTERNAL CIRCUIT PROTECTIONFAN COIL SIZE USED WITHHEATING CAP. ** @ 230V KFCEH0101H1010230/13, 6, 9None‡001, 00231,400 KFCEH0201H1515230/13, 8, 11, 15Fuse001–00347,100 KFCEH0301H2020230/15, 10, 15, 20Fuse002–00462,800

* Field convertible to 1 phase. † KFAEH2501N09 is field convertible to 3 phase. ‡ Single point wiring kit required for these heaters in Canada. ** Blower motor heat not included.

When using units with 20-, 24-, and 30-kw electric heaters, maintain a 1-in. clearance from combustible materials to discharge plenum and ductwork, and maintain a distance of 36 in. from the unit. Use an accessory downflow base to maintain proper clearance on downflow installations. Use flexible connectors between ductwork and unit to prevent transmission of vibration. When electric heater is installed, use heat resistant material for flexible connector between ductwork and unit at discharge connection. Ductwork passing through unconditioned space must be insulated and covered with vapor barrier.

ESTIMATED SOUND POWER LEVEL (dBA)

UNIT SIZECONDITIONSOCTAVE BAND CENTER FREQUENCY* CFMExt Static Pressure63125250500100020004000 FH4-0018000.2566.062.058.055.053.051.047.0 FH4-00212000.2567.863.859.856.854.852.848.8 FH4-00316000.2569.065.061.058.056.054.050.0 FH4-00420000.2570.066.062.059.057.055.051.0

* Estimated sound power levels have been derived using the method described in the

1987 ASHRAE HVAC Systems & Applications Handbook,

Chapter 52, p. 52.7

Page 9 of the Bryant FH4B user manual — NOTES:
9ページ · クリックして拡大
9ページ

** Includes blower motor amps of largest fan coil used with heater. †† Copper wire must be used. If other than uncoated (non-plated), 75°C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the National Electric Code

BRANCH CIRCUITMax Wire Length 208/230V (Ft)‡‡Dual CircuitL3,L4———————————75/7675/76——59/5959/59————SMART HEAT ELECTRICAL DATABRANCH CIRCUITMax Wire Length 208/230V (Ft)‡‡Dual CircuitL3,L4—73/7493/93FIELD MULTIPOINT WIRING OF 24-AND 30-KW SINGLE PHASEMAX WIRE LENGTH 208/230V (FT)‡‡L5,L673/7359/59 L1,L2———————————78/8078/80——78/8078/80————L1,L2—53/8581/82 L3,L473/7359/59 Single Circuit67/6866/6685/8866/6685/8859/6059/6054/8783/8578/8078/8088/89—56/9076/7785/109—94/95115/11697/98117/150Single Circuit60/6192/9287/111 L1,L259/6078/80 Max Fuse/Ckt Bkr Amps 208/230VDual CircuitL3,L4———————————25/2525/25——50/5050/50————Max Fuse/Ckt Brk Amps 208/230VDual CircuitL3,L4—25/3050/50 MAX FUSE/CKT BKR AMPS 208/230VL5,L640/4050/50 L1,L2———————————60/6060/60——60/6060/60————L1,L2—50/6060/60 L3,L440/4050/50 Single Circuit20/2030/3035/3530/3035/3545/5045/5050/6035/3560/6060/6080/90—50/6060/70100/110—80/80125/15090/100150/175Single Circuit45/5080/90100/110 Min Gnd Wire Size 208/230VDual CircuitL3,L4———————————10/1010/10——10/1010/10————Min Gnd Wire Size 208/230VDual CircuitL3,L4—10/1010/10L1,L245/5060/60 L1,L2———————————10/1010/10——10/1010/10————L1,L2—10/1010/10 MIN GND WIRE SIZE 208/230V10/1010/10 Single Circuit12/1210/1010/1010/1010/1010/1010/1010/1010/1010/1010/108/8—10/1010/88/6—8/86/68/86/6Single Circuit10/108/88/6 MIN WIRE SIZE (AWG) 208/230V††L5,L68/88/8 Min Wire Size (AWG) 208/230V††Dual CircuitL3,L4———————————10/1010/10——8/88/8————Min Wire Size (AWG) 208/230V††Dual CircuitL3,L4—10/108/8 L3,L48/88/8 L1,L2———————————6/66/6——6/66/6————L1,L2—8/66/6 Single Circuit12/1210/108/810/108/88/88/88/68/86/66/64/4—8/66/63/2—4/41/13/30/00Single Circuit8/84/43/2L1,L28/86/6 Min Ampacity 208/230V**Dual CircuitL3,L4———————————22.7/25.022.7/25.0——45.3/50.045.3/50.0————Min Ampacity 208/230V**Dual CircuitL3,L4—23.4/25.445.3/50.0 MIN AMPACITY 208/230V**L5,L636.2/40.045.3/50.0 L1,L2———————————53.8/58.553.8/58.5——53.8/58.553.8/58.5————L1,L2—49.7/54.952.0/56.8 L3,L436.2/40.045.3/50.0 Single Circuit15.9/17.326.0/28.431.2/33.526.0/28.431.2/33.544.7/48.544.7/48.549.5/53.532.0/34.553.8/58.553.8/58.576.3/83.4—47.7/51.855.5/60.498.9/108.4—71.2/77.8116.9/127.986.8/95.0144.8/158.5 Single Circuit44.0/48.373.2/80.397.2/106.7 L1,L244.7/48.553.8/58.5 HEATER AMPS 208/230VDual CircuitL3,L4———————————18.1/20.018.1/20.0——36.2/40.036.2/40.0————HEATER AMPS 208/230VDual CircuitL3,L4—14.4/16.036.2/40.0 HEATER AMPS 208/230VL5,L628.9/32.036.2/40.0 L1,L2———————————36.2/40.036.2/40.0——36.2/40.036.2/40.0————L1,L2—39.7/43.936.2/40.0 Single Circuit10.9/12.018.1/20.018.1/20.018.1/20.018.1/20.028.9/32.028.9/32.032.8/36.018.8/20.836.2/40.036.2/40.054.2/59.9—31.3/34.637.6/41.572.3/79.9—50.1/55.486.7/95.562.6/69.2109.0/120.0Single Circuit32.5/35.954.2/59.972.3/79.9L3,L428.9/32.036.2/40.0 INTERNAL CIRCUIT PROTECTIONNoneNoneNoneCkt BkrCkt BkrNoneCkt BkrNoneNoneNoneCkt BkrFuseCkt BkrNoneNoneFuseCkt BkrFuseFuseFuseFuseINTERNAL CIRCUIT PROTECTIONNoneFuseFuse L1,L228.9/32.036.2/40.0 PHASE111111113111133113131PHASE111PHASE11 KW208v2.33.83.83.83.86.06.06.86.87.57.511.311.311.313.515.015.018.018.022.522.5KW208v7.511.315.0KW208V18.022.5 240v355558899101015151518202024243030240v101520240V2430 HEATER PART NO.KFCEH0401N03KFCEH0501N051KFCEH0501N052KFCEH2401C051KFCEH2401C052KFCEH0801N08KFCEH2501C08KFCEH2901N09***—KFCEH0901N10KFCEH2601C10KFCEH3001F15***KFCEH3101C15***KFCEH1601315KFCEH2001318KFCEH3201F20***KFCEH3301C20***KFCEH3401F24†***KFCEH3501F30†***HEATER PART NO.KFCEH0101H10KFCEH0201H15KFCEH0301H20HEATER PART NO.KFCEH3401F24†KFCEH3501F30†

*** Heaters are Intelligent Heat capable when used with the FK, FV fan coils and corporate 2-speed programmable thermostat (TSTATBBP2S01-A), or Thermidistat™ Control (TSTATBBPRH01-B).

ELECTRIC HEATER ELECTRICAL DATA

‡‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.

3. Single circuit application of F15 and F20 heaters requires single-point wiring kit accessory
2. For fan coil sizes 042-060 and all FK4D, FV4B sizes.

† Field convertible to 1 phase, single or multiple supply circuit.

1. For fan coil sizes 018-036.

‡ Field convertible to 3 phase.

(ANSI/NFPA 70).

NOTES:

Page 10 of the Bryant FH4B user manual — REQUIRED USE:
10ページ · クリックして拡大
10ページ

ELECTRIC HEATER STATIC PRESSURE DROP

The airflow performance data was developed using fan coils with 10-kw electric heaters (2 elements) in the 001 and 002 size units and 15-kw heaters (3 elements) in the 003 and 004 size units.

001, 002 003, 004

HEATER ELEMENTSKWEXTERNAL STATIC PRESSURE CORRECTION 00+0.02 13, 5+0.01 28, 100 39, 15–0.02 420–0.04
HEATER ELEMENTSKWEXTERNAL STATIC PRESSURE CORRECTION 00+0.04 28, 10+0.02 39, 150 420–0.02 618, 24, 30–0.10

The airflow performance data was developed using fan coils with 10-kw electric heaters (2 elements) in the 001 and 002 units and 15-kw heaters (3 elements) in the 003 and 004 units. For fan coils with heaters of a different number of elements, the available external static at a given CFM from the curve may be corrected by adding or subtracting available external static pressure as indicated above.

ACCESSORIES

ITEMACCESSORY PART NO.*FAN COIL SIZE USED WITH Disconnect KitKFADK0101DSCCooling Controls and Heaters 3-kw through 10-kw Downflow Base KitKFACB0101CFB001 KFACB0201CFB002 KFACB0301CFB003, 004 Downflow Conversion KitKFADC0201SLPSlope Coil Units — 001, 002 KFADC0401ACLA-Coil Units — 003, 004 Single-Point Wiring KitKFASP0101SPKOnly with 15and 20-kw Fused Heaters Filter Kit (12 pack)KFAFK0112SML001 KFAFK0212MED002 KFAFK0312LRG003, 004 Evaporator CoilKFAEC0501024001 KFAEC0601036002 KFAEC0301048003 KFAEC0401060004 Downflow/Horizontal Conversion Gasket KitKFAHD0101SLPAll

* Factory authorized and listed, field-installed.

Accessory Kits Description Suggested and Required Use

1. Disconnect Kit

The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely. SUGGESTED USE: FH4 units for 3-kw through 10-kw electric resistance heaters and cooling controls.

2. Downflow Base Kit

This kit is designed to provide a 1-in. minimum clearance between unit discharge plenum, ductwork, and combustible materials. It also provides a gap free seal with the floor.

REQUIRED USE:

This kit must be used whenever FH4 fan coils are used in downflow applications.

3. Downflow Conversion Kit

Fan coils are shipped from the factory for upflow or horizontal-left applications. Downflow conversion kits provide proper condensate water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A-coils.

REQUIRED USE:

This kit must be used whenever FH4A fan coils are used in downflow applications.

4. Single Point Wiring Kit

The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run 2 heavy-gage, high-voltage wires into the fan coil rather than 4 light-gage, high-voltage wires. SUGGESTED USE: FH4 fan coils with 15-kw and 20-kw fused heaters only.

5. Fan Coil Filter

The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevent them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and in turn the efficiency of the system. SUGGESTED USE: To replace filters in FH4 fan coils.

6. Evaporator Coil Kit

The kit contains a heating/cooling coil and drain pan. SUGGESTED USE: Accessory coil used with FH4 fan unit.

7. Downflow/Horizontal Conversion Gasket Kit

This kit provides the proper gasketing of units when applied in either a Downflow or Horizontal application.

REQUIRED USE:

FH4 fan coils.

Page 11 of the Bryant FH4B user manual — MATCHED SYSTEM
11ページ · クリックして拡大
11ページ

MATCHED SYSTEM

Bryant FH4B — MATCHED SYSTEM diagram (page 11)
図 5
Page 12 of the Bryant FH4B user manual — SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
12ページ · クリックして拡大
12ページ

SERVICE TRAINING

Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including:

  • Unit Familiarization
  • Maintenance
  • Installation Overview
  • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book.

Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.

CALL FOR FREE CATALOG 1-800-644-5544

[ ] Packaged Service Training [ ] Classroom Service Training

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE

UNIT MUST BE INSTALLED IN ACCORDANCE

WITH INSTALLATION INSTRUCTIONS

CancelsPDS FH4B.01.2

Form PDS FH4B.01.3

© 2003 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231 PRINTED IN U.S.A. Catalog No. 12FH-4B2 9-03