920i ® Programmable HMI Indicator/Controller Panel Mount Enclosure Installation

This document contains drawings, replacement parts lists and instructions for installing panel mount models of 920i indicators. See the 920i Installation Manual, PN 67887, for general installation, configuration and calibration information.

Use a wrist strap for grounding and to protect components from electrostatic discharge (ESD) when working inside the indicator enclosure.

This unit uses double pole/neutral fusing which could create an electric shock hazard. Procedures requiring work inside the indicator must be performed by qualified service personnel only.

11.56"

10.51"

Outer Perimeter of Exterior Faceplate (Solid Line)

Panel Cutout (Dashed Line)

9.16"

Illustration is not to scale, dimensions

8.02"

are for reference only.

Interior Housing (Dotted Line)

Figure 1. Panel Cutout for Panel Mount Enclosure

PN 69989 Rev B April 20, 2018

Page 2 of the RICE LAKE Programmable HMI Indicator, Controller (920i) user manual — Installation
2ページ · クリックして拡大
2ページ

Installation Use the dimensions shown in Figure 1 to lay out the panel cutout for the panel mount enclosure. See Figure 2 for enclosure dimensions.

RICE LAKE Programmable HMI Indicator, Controller (920i) — Installation diagram (page 2)
図 1 · Installation

Figure 2. Panel Mount Enclosure Dimensions

Once the cutout has been prepared:

1. Insert the enclosure into the cutout from the front of the panel. 2. Install the reinforcing plate on the enclosure from the inside of the panel. 3. Install the clinching bracket on the enclosure from inside the panel. 4. Secure the bracket to the enclosure using the six 1/4" screws provided in the parts kit (PN 71522). 5. Use the nine 1 1/2" screws (PN 82425) to secure the clinching bracket to the panel door.
RICE LAKE Programmable HMI Indicator, Controller (920i) — Installation diagram (page 2)
図 2 · Installation

Figure 3. Clinching Bracket Assembly

© Rice Lake Weighing Systems ● All Rights Reserved 2

Page 3 of the RICE LAKE Programmable HMI Indicator, Controller (920i) user manual — Grounding
3ページ · クリックして拡大
3ページ
RICE LAKE Programmable HMI Indicator, Controller (920i) — Grounding diagram (page 3)
図 3 · Grounding

Panel is located between the front bezel and the reinforcing plate (not shown). The clinch bracket draws the front bezel against the panel when screws are tightened. Clinch Bracket

Figure 4. Panel Mount Enclosure

Grounding Except for the power cord, all cables routed through the cord grips should be grounded against the indicator enclosure.

1. Install the ground clamps on the grounding bar, using the ground clamp screws. Do not tighten the screws at this time. 2. Route cables under cabling bar and through the cord grips and the grounding clamps to determine the cable lengths required to reach the cable connectors.
RICE LAKE Programmable HMI Indicator, Controller (920i) — Grounding diagram (page 3)
図 4 · Grounding

Grounding Clamp Install lock washers first, against enclosure, under grounding clamp

Cabling Bar Use cable ties to bind cables to bar

Figure 5. Cable Installation with Grounding Clamp

3. Mark the cables to remove insulation and shield. See Stripping Cables on next page. 4. Route stripped cables through the cord grips and grounding clamps. 5. Ensure the shields contact the grounding clamps and tighten the ground clamp screws.

3 Visit our website www.RiceLake.com

Page 4 of the RICE LAKE Programmable HMI Indicator, Controller (920i) user manual — Braided Shielding
4ページ · クリックして拡大
4ページ

Stripping Cables

Foil Insulated Cable

Shield wire (cut) Silver side out

Length of foil before folding back on cable insulation

Figure 6. Foil Insulated Cable

1. Strip the insulation and foil from the cable 1/2 (15 mm) past the grounding clamp. 2. Fold the foil shield back on the cable where the cable passes through the clamp. 3. Ensure the silver (conductive) side of the foil is turned outward for contact with the grounding clamp.

Braided Shielding

Figure 7. Braided Insulated Cable

1. Strip the insulation and braided shield from a point just past the grounding clamp.
2. Strip another 1/2 (15 mm) of the insulation to expose the braid where the cable passes through the clamp.

Load Cell Cables Cut the shield wire just past the grounding clamp. Shield wire function is provided by contact between the cable shield and the grounding clamp.

© Rice Lake Weighing Systems ● All Rights Reserved 4

Cut insulation here · Braid · Cut insulation here

Page 5 of the RICE LAKE Programmable HMI Indicator, Controller (920i) user manual — Power Specifications
5ページ · クリックして拡大
5ページ

Power Specifications

Line Voltages 115 or 230 VAC Frequency 50 or 60 Hz Maximum Power Consumption 65W on secondary Primary power consumption:100W TRMS Constant current:1.5 A TRMS (115VAC);

1.0 A TRMS (230VAC) Fusing 115 VAC and 230 VAC North American 2 x 3.15A TR5 sub-miniature fuses Wickmann Time-Lag 19374 Series UL Listed, CSA Certified and Approved 230 VAC European 2 x 3.15A TR5 sub-miniature fuses Wickmann Time-Lag 19372 Series UL Recognized, Semko and VDE Approved See the 920i installation manual for additional specifications.

Parts Kit Contents Table 1-1 lists the parts kit contents for the panel mount version of the 920i.

Part No.DescriptionQty 14626Kep nuts, 8-32NC5 54206Machine screws, 6-32 x 3/82 15133Lock washers, No. 8, Type A5 71522Machine screws, 8-32NC x 1/46 82425Machine screws, 10-32NF x 1-1/29 15631Cable ties4 53075Cable shield ground clamps5 42350Capacity label1 71095Clinching bracket1 158876-position screw terminal for load cell connection1 705996-position screw terminals for J2 and J102 711264-position screw terminal for J9 and optional keyboard connection2 711253-position screw terminal for J111

Table 1-1. Parts Kit Contents

5 Visit our website www.RiceLake.com

Page 6 of the RICE LAKE Programmable HMI Indicator, Controller (920i) user manual — Power Specifications
6ページ · クリックして拡大
6ページ

© Rice Lake Weighing Systems Specifications subject to change without notice.

  • 230 W. Coleman St.
  • Rice Lake, WI 54868
  • USA U.S. 800-472-6703
  • Canada/Mexico 800-321-6703
  • International 715-234-9171
  • Europe +31 (0)26 472 1319

www.ricelake.com PN 69989 Rev B April 20, 2018

RICE LAKE Programmable HMI Indicator, Controller (920i)について質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
RICE LAKE Programmable HMI Indicator, Controller (920i)に関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

RICE LAKE Programmable HMI Indicator, Controller (920i) 取扱説明書(PDF)

6 ページ·270 KB·コントローラー·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…