JA
Emerson logo
公式取扱説明書

Emerson Rosemount 975 Flame Detectors

12 ページ·453 KB·センサー·PDF·EN
Emerson Rosemount 975 Flame Detectors
目次 14セクション 1 Rosemount 975 series · 2 Certified product identification of the device · 3 Applied standards · 4 Safety parameters · … 表示非表示
Page 1 of the Emerson Rosemount 975 Flame Detectors user manual — Safety Quick Start Guide 00825-0400-4975, Rev AA June 2021
1ページ · クリックして拡大
1ページ

Safety Quick Start Guide 00825-0400-4975, Rev AA June 2021

Rosemount

™ 975

Flame Detectors

Page 2 of the Emerson Rosemount 975 Flame Detectors user manual — Contents
2ページ · クリックして拡大
2ページ

Contents

Rosemount 975 series 3

Certified product identification of the device 4

Applied standards 5

Safety parameters 6

Guidelines for configuring, installing, operating, and service 8

Conditions for safe operating 9

Page 3 of the Emerson Rosemount 975 Flame Detectors user manual — 1 Rosemount 975 series
3ページ · クリックして拡大
3ページ

1 Rosemount 975 series

The flame detectors series Rosemount 975 fulfills the requirements of the IEC 61508 for a Safety Integrity Level (SIL) 2 in a one-channel configuration or up to SIL 3 of IEC 61508 in a redundant configuration.

Page 4 of the Emerson Rosemount 975 Flame Detectors user manual — 2 Certified product identification of the device
4ページ · クリックして拡大
4ページ

2 Certified product identification of the device

Kind of productInfrared and ultraviolet flame detector series
Type designationRosemount 975HR4U, 975MR4U, 975UF4U, 975UR4U
Spectral response:Infrared and ultraviolet bands Supply voltage:18-32 Vdc Max. power consumption:300 mA Max. current:9.6 W Output:0-20 mA Fault relay Alarm relay 0-5 V
Page 5 of the Emerson Rosemount 975 Flame Detectors user manual — N2 EN 54-10:2002 and EN 54-10/A1:2005
5ページ · クリックして拡大
5ページ

3 Applied standards

N1 IEC 61508 Part 1 - 7:2010

Functional safety of electrical/electronic/programmable electronic safety-related systems

N2 EN 54-10:2002 and EN 54-10/A1:2005

Fire detection and fire alarm systems

Part 10Flame detectors - Point detectors
Page 6 of the Emerson Rosemount 975 Flame Detectors user manual — 4.3 Safety relevant parameters
6ページ · クリックして拡大
6ページ

4 Safety parameters

4.1 Safety function

The safety function of the Rosemount 975 flame detector series is to detect flames in which carbon dioxide (CO2) is produced in the combustion process and announce this over the 4-20 mA interface, analog output interface, and/or by opening the alarm-relay-contact.

4.2 Characteristics as per IEC 61508

Emerson Rosemount 975 Flame Detectors — 4.2 Characteristics as per IEC 61508 diagram (page 6)
図 1 · 4.2 Characteristics as per IEC 61508
Safety Integrity Level (SIL)2 (one-channel configuration) and 3 (redundant configuration) HFT (intern)0 Device typeB Mode of operationLow demand mode and high demand or continues mode Average ambient temperaturemax. 55 °C Main time to repair0 h Proof-test interval365 days

4.3 Safety relevant parameters

Emerson Rosemount 975 Flame Detectors — 4.3 Safety relevant parameters diagram (page 6)
図 2 · 4.3 Safety relevant parameters
Rosemount 975HR4U, 975MR4U (IR)Rosemount 975UF4U, 975UR4U (UV/IR) MAORYORYO2FDOMAORYORYO2FDO λ (fit) S9881290129083592312261226770 λ (fit) D9881285128583592312211221770 λ (fit) DU10410710710279828277 λ (fit) DD8841179117973284411391139693 SFF95%96%94%94%96%97%97%95% DC89%92%88%88%91%93%93%90% PFD (1oo1) avg4.6E044.7E044.5E044.5E043.5E043.6E043.4E043.4E04 PFD % SIL2 _4.6%4.7%4.5%4.5%3.5%3.6%3.4%3.4%
Page 7 of the Emerson Rosemount 975 Flame Detectors user manual — Remarks:
7ページ · クリックして拡大
7ページ
Emerson Rosemount 975 Flame Detectors — 4 Safety parameters diagram (page 7)
図 3 · 4 Safety parameters
Rosemount 975HR4U, 975MR4U (IR)Rosemount 975UF4U, 975UR4U (UV/IR) MAORYORYO2FDOMAORYORYO2FDO PFH (1oo1, 1/h)1.0E07N/A1,0E07N/A7.9E08N/A7.7E08N/A PFH % SIL2 _10.4%N/A10.2%N/A7.9%N/A7.7%N/A PFD (1oo2) avg9.4E069.6E069,3E069.2E067.1E067.3E063.4E046.9E06 PFD % SIL3 _ _0.9%1.0%0.9%0.9%0.7%0.7%3.4%0.7% PFH (1oo2, 1/h)2.2E092.2E092.1E092.1E091.6E091.7E097.7E081.6E09 PFH % SIL3 _ _2.2%2.2%2.1%2.1%1.6%1.7%7.7%1.6%

Remarks:

  • N/A.: Not allowed for high demand mode
  • RYO: Using only the alarm-relay for alarming
  • RYO2: Using alarm and acc-relay for alarming (serial connected contacts)
  • MAO: Using the 4-20 mA - Interface for alarming
  • FDO: Using the analog OUT interface for alarming
  • Failure rates of the electronic components as per Siemens SN 29500, calculated based upon an ambient temperature of 55 °C and statistical data of the sensor elements
  • The calculation was performed based on a proof-test interval T1 = 365 days.
  • Without knowledge of the partly redundant internal structure of the detector a calculation with other proof-test intervals (e.g., two years) leads only to an approximate result.
Page 8 of the Emerson Rosemount 975 Flame Detectors user manual — 5 Guidelines for configuring, installing, operating, and service
8ページ · クリックして拡大
8ページ

5 Guidelines for configuring, installing, operating, and service

The alert conditions according to SIL 2 can be implemented by an:

  • Alert signal via 20 mA current loop
  • Alert signal via alarm relay and the fault relay

or

Page 9 of the Emerson Rosemount 975 Flame Detectors user manual — 6.3 Using the alarm and acc-relay for alarming
9ページ · クリックして拡大
9ページ

6 Conditions for safe operating

1. The flame detector shall consist only of the approved hardware and software modules.
2. The 24 V power supply must fulfill the requirements for PELV/SELV of EN 60950.
3. The automatic built-in test (BIT) must be activated.
4. The function of the Rosemount 975 Flame Detector (flame detector, function of the 0-20 mA interface, and relay functions) must be checked completely.

6.1 Using the 0-20 mA interface for alerting

The following parameters shall be set:

  • Automatic built-in test: On
  • Connected to 0-20 mA terminals

The following allowed output current must be supervised with an accuracy of ±5 percent.

  • Normal state: 4 mA
  • Warning state: 16 mA
  • Alarm state: 20 mA

6.2 Using the alarm relay contact for alerting

The following parameters shall be set:

  • Automatic built-in-test: On
  • Connected to normally closed (N.C.) contact of alarm relay terminals
  • Connected to fault relay terminals

The relay contacts (alarm and faulty relay) must be protected with a fuse rated at 0.6 of the nominal specified relay contact current.

The maximum contact rating that is allowed per SIL-2 is 30 Vdc.

The contact of the alarm relay opens if there is a fire alarm.

During the forwarding and evaluation of the alarm, the relay contact opens.

6.3 Using the alarm and acc-relay for alarming

The following parameters shall be set:

  • Automatic built-in-test: On
Page 10 of the Emerson Rosemount 975 Flame Detectors user manual — 6.5 Other
10ページ · クリックして拡大
10ページ
  • Connected to normally closed (N.C.) contact of alarm relay terminals and auxiliary relay terminals.
  • The contacts of alarm relay and auxiliary relay must connected serial.
  • Connected to fault relay terminals.
  • The relay contacts of auxiliary relay, alarm relay and faulty relay must be protected with a fuse rated at 0.6 of the nominal specified relay contact current.
  • The maximum contact rating that is allowed per SIL-2 is 30 Vdc.
  • The contacts of the alarm relay and the auxiliary relay open if there is a fire alarm.
  • During the forwarding and evaluation of the alarm, the relay contacts opens.

6.4 Using the analog voltage output for alerting

The following parameters shall be set:

  • Automatic built-in-test: On
  • Connected to analog voltage output terminal. The following allowed output voltage must be supervised with an accuracy of ±20 percent. — Normal state: 2 V
— Fault state<1 V
— Alarm state5 V

The analog voltage output can be used as low demand only.

6.5 Other

1. The window of the sensor must be examined at appropriate time intervals for partial contamination.
2. The HART ® and the RS-485 interfaces must not be used for the transmission of the safety-related data.
Page 11 of the Emerson Rosemount 975 Flame Detectors user manual — 6.4 Using the analog voltage output for alerting
11ページ · クリックして拡大
11ページ
Page 11 of the Emerson Rosemount 975 Flame Detectors user manual — 6.4 Using the analog voltage output for alerting
Page 12 of the Emerson Rosemount 975 Flame Detectors user manual — *00825-0400-4975* Safety Quick Start Guide 00825-0400-4975, Rev. AA June 2021
12ページ · クリックして拡大
12ページ

*00825-0400-4975* Safety Quick Start Guide 00825-0400-4975, Rev. AA June 2021

For more informationwww.emerson.com
情報源

参考資料・リンク

この取扱説明書で参照されているリンク(メーカー、サポート、ダウンロード等)。

Emerson Rosemount 975 Flame Detectorsについて質問する

ユーザーまたはスタッフが通常1日以内に回答します。あなたの質問が次の人の助けにもなります。

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Emerson Rosemount 975 Flame Detectorsに関する質問はまだありません

最初の質問を投稿しましょう。他のユーザーや当チームが回答します。

原本

Emerson Rosemount 975 Flame Detectors 取扱説明書(PDF)

12 ページ·453 KB·センサー·PDF
上のページをクリックするとここに表示されます
ページ 1 / …
100%
ページを読み込み中…