1 INST ALLA TION, OPERA TING AND SER VICE INSTRUCTIONS FOR Alliance SL ™ Indirect - Fired W ater Heater For service or repairs to the water heater , call your heating contractor . When seeking informa- tion on the water heater , provide Model Number and Serial Number as shown on Rating Label.
2 PLEASE READ INSTRUCTIONS CAREFULL Y BEFORE INST ALLING W A TER HEA TER U.S Boiler Company , Inc. – Burnham Hydronics (herein called the Company) intends that this Alliance SL™ Indirect-Fired W ater Heater be used as a separate zone to a heating system boiler .
3 INDEX General Information ..................................................................................................................... 2 Specications & Ratings .........................................................................
4 A. INSPECTING AND PREP ARING THE W A TER HEA TER q AL27SL thru AL70SL - Remove the cardboard box, which comes packaged with the heater . It should contain the following: TPI thermostat, T&P valve and a “T ee”, foamed lid and screws. q AL1 19SL - Remove the cardboard boxes, which come packaged with the heater .
5 valve must be marked with maximum set pressure not to exceed the marked maximum allowable working pressure of the water heater (150psi). Install the valve into the opening provided and marked for th.
6 q Do not apply heat directly to the cold-water inlet as it is made of plastic and will melt. G. BOILER SUPPL Y CONNECTIONS q W ARNING: Boiler temperature must be controlled by the boiler high limit not to exceed 200°. Failure to do so will create a hazardous installation and void the applicable limited warranties.
7 q Run all 24V AC wiring thru the square notch on bottom of TPI case. (See TPI Diagram 3) q Incoming 24V AC power must be connected to 24V AC connectors on the bottom right corner of TPI control.
8 q Do not apply heat to cold inlet. q If there is a check valve (sometimes in water meter), backow preventer or pressure-reducing valve, install an adequate size expansion tank. G. FILLING THE HEA TER q Completely ll heater .
9 W A TER TEMPERA TURE CONTROLS A periodic inspection of the operating controls, heat exchanger and wiring should be made by qualied ser - vice personnel. T emperature of the water should be tested periodically at the faucet to be sure thermostat is working properly .
10 TPI CONTROL - DIAGRAM 1 Indicating Light T emperature Adjust Differential Adjust TPI CONTROL - DIAGRAM 2 Screw A.
1 1 TPI CONTROL - DIAGRAM 3 Outgoing 24V wires to relay or zone valve Incoming 24V power connection Outgoing 1 10V wires to circulator Chase Nipple Conduit Incoming 24V power connections NOTE: Use pro.
12 FIGURE 1 - Installation Using Zone V alves Installation Diagram Using Zone V alves FIGURE 2 - Installation Using Circulator Installation Diagram Using Separate Circulator.
13 FIGURE 3 - Coil Detail & T ightening Sequence Bolt Steel W asher Coil Plate Plastic O-Ring Housing T ank Flange ‘L ’ Nut Small outside O-ring Large inside O-ring Proper T ightening Sequence for T op Mount Coil CAUTION: Does not require excessive force to seal properly .
14 Low V oltage 120 V olts L1 Hot 120 V olts L2 Neutral Circula tor 24v T emperature Differential Pump/TT 24v LED flashing green = calling for heat solid green = at temperature red = error 20° 15° 1.
15 Zone V alve Wiring Diagrams Wiring for 3 W ire Zone V alve L o w V oltage 120 V olts 120v 24v B oiler C onnec tions T 1 T 2 3 H ot N eutr al Z one V alv e 120v 24v T o B oiler C onnec tions /C ir c.
16 Switching relay Wiring Diagrams Switching Relay SR-502 or SR-503 Switching Relay R8845U or SR 501.
17 Switching relay Wiring Diagrams (con’t) Switching Relay SR-504 with Priority Option L o w V oltage 120 V olts FUSE 1 AMP C OM / 24 V A C FOUR Z ONE SWIT CHING REL A Y WITH OPTIONAL PRIORIT Y Z ON.
18 HOW T O OBT AIN SER VICE ASSIST ANCE U.S. Boiler Company , Inc. – Burnham Hydronics does not have a service department or personnel to ser- vice your heater in the eld.
19 Alliance SL™ Indirect-Fired W ater Heater 10/2/1 LIMITED W ARRANTY T en Y ear Limited T ank Replacement W arranty T wo Y ear Limited T ank Replacement Labor Allowance One Y ear Limited Parts W arranty U.
20 ONE (1) YEAR LIMITED P ARTS W ARRANTY DURA TION: The warranty is effective for one (1) year beginning with the date of original purchase. This warranty shall begin from the date of manufacture as indicated by the serial number .
21 MODEL & SERIAL NUMBER INFORMA TION The following information should be noted At time of installation and retained for Future reference. Model No. Serial No. Date Installed Dealer ’s Name Address City State Zip U.S. Boiler Company , Inc., – P .
22 NOTES.
23 NOTES.
24 Optional Lifetime W arranty Registration Card A vailable to Residential, Single Family Homes Only Y es, I wish to purchase the Optional Lifetime W arranty! DA TE ___________________________________.
デバイスBurnham Indirect - Fired Water Heater AL SLの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Burnham Indirect - Fired Water Heater AL SLをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはBurnham Indirect - Fired Water Heater AL SLの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Burnham Indirect - Fired Water Heater AL SLの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Burnham Indirect - Fired Water Heater AL SLで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Burnham Indirect - Fired Water Heater AL SLを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はBurnham Indirect - Fired Water Heater AL SLの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Burnham Indirect - Fired Water Heater AL SLに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちBurnham Indirect - Fired Water Heater AL SLデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。