38YCW 10 SEER Split-System Heat Pump Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue.
INSTALLATION Step 1 — Check Equipment and Job Site UNPACK UNIT Move to final location. Remove carton, taking care not to damage unit. INSPECT EQUIPMENT File claim with shipping company prior to installation if shipment is damaged or incomplete. Locate unit-rating plate on unit-service panel.
Step 8 — Make Piping Connections Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow-control devices, including solenoid valves. If ANY refrigerant tubing is buried, provide a 6 in.
NOTE: Install branch-circuit disconnect of adequate size per NEC to handle unit-starting current. Locate disconnect within sight from and readily accessible from unit, per Section 440-14 of NEC. ROUTE GROUND AND POWER WIRES Remove access panel and control box to gain access to unit wiring.
COOLING-ONLY PROCEDURE NOTE: If superheat- or subcooling-charging conditions are not favorable, charge must be weighed in accordance with unit-rating plate ±0.6 oz/ft of 3/8-in. liquid line above or below 15 ft respectively. EXAMPLE: To calculate additional charge required for a 25-ft line set: 25 ft – 15 ft = 10 ft X 0.
Fig. 6 — Typical 24v Circuit Connections A01384 24 V AC HOT R C W Y G R C RVS COOLING C W2 OTHER NON-PROGRAMMABLE HP THERMOST A T F A, FB, FC, FD, FF F AN COIL HEA T PUMP G O E W2 R Y 24 V AC COM HE.
SEQUENCE OF OPERATION NOTE: Defrost-control board is equipped with 5-minute lockout timer that may be initiated upon any interruption of power. With power supplied to indoor and outdoor units, transformer is energized. Cooling On a call for cooling, thermostat makes circuits R-O, R-Y, and R-G.
If it is desirable to observe a complete defrost in warmer weather, the thermostat must be closed as follows: 1. Turn off power to outdoor unit. 2. Disconnect outdoor fan motor lead from OF2 on control board. (See Fig. 8.) Tape to prevent grounding. 3.
デバイスCarrier 10 SEER SPLIT-SYSTEM 38YCWの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 10 SEER SPLIT-SYSTEM 38YCWをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 10 SEER SPLIT-SYSTEM 38YCWの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 10 SEER SPLIT-SYSTEM 38YCWの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 10 SEER SPLIT-SYSTEM 38YCWで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 10 SEER SPLIT-SYSTEM 38YCWを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 10 SEER SPLIT-SYSTEM 38YCWの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 10 SEER SPLIT-SYSTEM 38YCWに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 10 SEER SPLIT-SYSTEM 38YCWデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。