AQUASNAP 30RA / 30RH PRO-DIALOG control INST ALLA TION, OPERA TION AND MAINTENANCE INSTRUCTIONS • L L O Y D ' S R E G I S T E R Q U A L I T Y A S S U R A N C E I S O 9 0 0 1.
GB - 1 30RA/30RH Air-cooled liquid chillers and reversible air-to-water heat pumps with integrated hydronic module ENGLISH For the use of the control system, refer to the Pro-Dialog Plus control manual. Contents Page Physical data ....................
30RA GB - 2 30RA 017 021 026 033 Power supply V -ph-Hz 400-3-50 / 400-3-50+N V oltage range V 360-440 Nominal power input* kW 6.43 8.57 9.56 12.39 Effective power input** kW 6.54 8.72 9.75 12.60 Nominal current drawn* A 10.75 15.50 18.80 24.55 Effective current drawn** A 10.
GB - 3 30RH ENGLISH 30RH 017 021 026 033 Power supply V -ph-Hz 400-3-50 / 400-3-50+N V oltage range V 360-440 Nominal power input* kW 6.21 7.95 9.13 11.83 Effective power input** kW 6.30 8.10 9.30 12.00 Nominal current drawn* A 10.75 14.80 18.70 23.65 Effective current drawn** A 10.
30RA/30RH GB - 4 Dimensions and location of hydraulic connections (mm) 200 700 200 400 1. Water inlet 2. W ater outlet 3. 3/4” gas safety valve outlet 1 2 3 1328 1453.5 859 796 175 1 0 5 12x20 1068 635 130 130 578 478 40 1 2 3 1503 180 1 2 5 1003 940 1657.
30RA/30RH GB - 5 ENGLISH General information and hydronic module Unit installation Read this instruction manual thoroughly before starting the installation. This unit complies with low-voltage (EEC/73/23) and electro- magnetic compatibility (EEC/89/336) directives.
30RA/30RH GB - 6 W ater connections T ypical water circuit diagram for units with hydronic module Legend for units without hydronic module: 30RA - RH unit without hydronic module Fan coil unit.
30RA/30RH GB - 7 ENGLISH W ater connections Ethylene glycol curve Freezing temperature of water- ethylene glycol mixture ° C Weight concentration of ethylene glycol in water % Make the plate heat exchanger hydraulic connections with the necessary components, using material which will guarantee that the screwed joints are leakproof.
30RA/30RH GB - 8 W ater connections W ater pressure drop of the unit without hydronic module Outlet available static pressure of the unit with hydronic module Pressure drop , kPa Water flow rate, l/s A. 30RA-RH 017 B. 30RA-RH 021 C. 30RA-RH 026 D. 30RA-RH 033 A vailable static pressure, kPa Water flow rate, l/s A.
30RA/30RH GB - 9 ENGLISH Electrical connections and refrigerant charge Electrical connections W ARNING: T o prevent electrical shock or equipment damage, make sure disconnects are open before electrical connections are made. If this action is not taken, personal injury may occur .
30RA/30RH GB - 10 Refrigerant charge and electronic control Undercharge If there is not enough refrigerant in the system, this is indicated by gas bubbles in the moisture sight glass. There are two possibilities: • Small undercharge (bubbles in the sight glass, no significant change in suction pressure).
GB - 11 30RA/30RH ENGLISH Start-up, compressor and pump replacement, unit protection devices Start-up Unit start-up is done by the electronic control described above, and must always be carried out under the supervision of a qualified air conditioning engineer .
30RA/30RH GB - 12 Unit protection devices , operating limits and operating range T able III: Pressure switch settings Cut-out Reset High pressurestat 30 bar Manual W ARNING: Alteration of factory settings other than the design set-point, without manufacturer's authorisation, may void the warranty .
GB - 13 30RA/30RH ENGLISH General maintenance, maintenance and final recommendations General maintenance A TTENTION: Before starting any servicing or maintenance operation on the unit, make sure that the power supply has been disconnected. A current discharge could cause personal injury .
30RA/30RH GB - 14 T roubleshooting A list of possible faults, as well as the probable cause and suggested solutions is shown as follows. In the event of a unit malfunction it is recommended to disconnect the power supply and ascertain the cause. Symptoms Cause REMEDY Unit does not start : - No power supply; CONNECT POWER SUPPL Y .
L010126H27 - 0 405 Via R. Sanzio, 9 - 20058 V illasanta (MI) Italy - T el. 039/3636.1 The manufacturer reserves the right to change any product specifications without notice.
デバイスCarrier 30RAの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 30RAをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 30RAの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 30RAの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 30RAで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 30RAを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 30RAの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 30RAに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 30RAデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。