Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INST ALLA TION ............................. 1-12 Step 1 — Complete Pre-Installation Checks ....................................1 Step 2 — Rig and Mount the Unit .
NOTE: Service areas — Allow 3 ft (914 mm) on both sides and 2 ft (610 mm) on both ends of unit for servicing. Fig. 1 — Dimensions 2.
13 2 4567 8 12 9 10 11 LEGEND 1— No. 1 Fan 5— No. 2 Fan 9— Compressor 2— High-Pressure Switch 6— T erminal Block 1 (Unit Power) 1 0— Low-Pressure Switch 3— Circuit Breaker — Control Circuit 7— T erminal Block 2 (Control Power) 11 — Hot Gas Bypass Piping Stub ( 3 ⁄ 8 -in.
T able 1A — Physical Data (English, 60 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (lb) With Aluminum-Fin Coil 732 779 789 900 With Copper-Fin Coil 825 919 929 1040 REFRIGERANT* R-22 Shipping Charge (lb) 2.
T able 1B — Physical Data (SI, 60 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (kg) With Aluminum-Fin Coil 332 353 358 408 With Copper-Fin Coil 374 417 421 472 REFRIGERANT* R-22 Shipping Charge (kg) 0.95 1.40 1.40 1.40 Operating Charge, T ypical (kg)† 10.
T able 1C — Physical Data (English, 50 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (lb) With Aluminum-Fin Coil 732 779 789 900 With Copper-Fin Coil 825 919 929 1040 REFRIGERANT* R-22 Shipping Charge (lb) 2.
T able 1D — Physical Data (SI, 50 Hz) UNIT 38AKS 013 014 016 024 OPERA TING WEIGHT (kg) With Aluminum-Fin Coil 332 353 358 408 With Copper-Fin Coil 374 417 421 472 REFRIGERANT* R-22 Shipping Charge (kg) 0.95 1.40 1.40 1.40 Operating Charge, T ypical (kg)† 10.
Step 2 — Rig and Mount the Unit Be sure unit panels are securely in place prior to rigging. RIGGING — These units are designed for overhead rigging only . For this purpose, the transverse base channels extend beyond the sides of the unit, with holes provided in the end plates to attach cables or hooks.
T able 4A — Refrigerant Piping Sizes — 60 Hz Units UNIT 38AKS LENGTH OF INTERCONNECTING PIPING, FT (M) 0-15 (0-4.5) 15-25 (4.5-7.5) 25-50 (7.5-15) 50-75 (15-23) 75-100 (23-30) Line Size (in.
INST ALL FIL TER DRIER(S) AND MOISTURE INDICA- TOR(S) — Every unit should have a filter drier and liquid- moisture indicator (sight glass). In some applications, depending on space and convenience requirements, it may be desirable to install 2 filter driers and sight glasses.
T able 6A — Electrical Data (3 Ph/60 Hz) UNIT 38AKS UNIT COMPR F AN MOT ORS (Single Phase) Model V olts MCA ICF MOCP (Fuse Only) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 1 2 013 501 208-230 187 253 62.5 178 100 43.6 170 2 4.
T able 6B — Electrical Data (3 Ph/50 Hz) UNIT 38AKS UNIT COMPR F AN MOT ORS 230 v (Single Phase) Model V olts MCA ICF MOCP (Fuse Only) RLA LRA T otal Fans FLA (ea) Fan No. kW Nameplate Supplied* Min Max 1 2 013 803 230 198 264 47.5 134 75 32.9 128 2 2.
ST ART -UP Compressor crankcase heater must be on for 24 hours before start-up. After the heater has been on for 24 hours, the unit can be started. If no time has elapsed since the pre- liminary charge step has been completed, it is unnecessary to wait the 24-hour period.
Fig. 10 — 38AKS013 and 38AKS024 Charging Chart 14.
Fig. 1 1 — 38AKS014 Charging Chart 15.
Fig. 12 — 38AKS016 Charging Chart 16.
OPERA TING SEQUENCE Cooling — When the first stage (TC1) of the cooling ther- mostat closes, the timer starts. After approximately 3 seconds, the timer expires, energizing the compressor and fan motor no. 1. When the liquid pressure builds to approxi- mately 257 psig (1772 kPa), fan motor no.
Winter Start Control (If Required) — Install Ac- cessory Package 38AE900021. Crankcase Heater — The heater prevents refrigerant migration and compressor oil dilution during shutdown when- ever compressor is not operating. It is wired to cycle with the compressor; the heater is of f when compressor is run- ning, and on when compressor is of f.
Fig. 15 — Outdoor Fan Fig. 16 — Pivot and Support T op Cover Fig. 17 — Coil Cleaning (T ypical) 19.
TROUBLESHOOTING PROBLEM SOLUTION COMPRESSOR DOES NOT RUN Contactor Open 1. Power off. 1. Restore power . 2. Fuses blown in field power circuit. 2. After finding cause and correcting, replace with correct size fuse. 3. No control power . 3. Check control circuit breaker; reset if tripped or replace if defective.
TROUBLESHOOTING (cont) PROBLEM SOLUTION COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH (cont) Airflow Restricted 1. Coil iced up. 1. Check refrigerant charge. 2. Coil dirty . 2. Clean coil fins. 3. Air filters dirty . 3. Clean or replace filters. 4. Dampers closed.
Copyright 1998 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 Ta b 3 a 2 a PC 1 1 1 Catalog No. 563-701 Printed in U.S.A.
ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST ART -UP? (Y/N) CHECK POWER SUPPL Y .
C. Start-Up CHECK INDOOR UNIT F AN SPEED AND RECORD. CHECK OUTDOOR UNIT F AN SPEED AND RECORD. AFTER A T LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS: OIL PRESSURE SUCTION PRESSURE.
デバイスCarrier 38AKS013-024の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 38AKS013-024をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 38AKS013-024の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 38AKS013-024の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 38AKS013-024で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 38AKS013-024を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 38AKS013-024の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 38AKS013-024に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 38AKS013-024デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。