Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS .................1 INST ALLA TION ............................1 - 9 Step 1 — Complete Pre-Installation Checks ..1 • UNCRA TE UNIT • INSPECT SHIPMENT • CONSIDER SYSTEM REQUIREMENTS Step 2 — Rig and Mount the Unit .
T able 1A — Physical Data (English) UNIT 38AQS008 60 Hz 50 Hz OPERA TING WEIGHT (lb) Aluminum Coils (Standard) 540 594 Copper Coils (Optional) 608 662 RIGGING WEIGHT (lb) Aluminum Coils (Standard) 590 644 Copper Coils (Optional) 658 712 REFRIGERANT* R-22 COMPRESSOR Reciprocating, Semi-Hermetic Quantity .
T able 2 — Refrigerant Piping Sizes LINEAR LENGTH OF PIPING — ft (m) UNIT 38AQS 0-25 (0-7.6) 25-50 (7.6-15.2) 50-75 (15.2-22.9) 75-100 (22.9-30.5) Line Size (in. OD) L S L S LSLS 008 1 ⁄ 2 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 5 ⁄ 8 1 1 ⁄ 8 LEGEND L— Liquid Line O D— Outside Diameter S— Suction Line NOTES: 1.
UNIT 38AQS008 UNIT W/ALUMINUM COIL UNIT W/COPPER COIL WEIGHT CHART (WITH ALUMINUM COIL) WEIGHT CHART (WITH COPPER COIL) Std Unit Corner W Corner X Corner Y Corner Z Std Unit Corner W Corner X Corner Y Corner Z Dim. A Dim. B Dim. A Dim. B Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg 60 Hz 1 ⬘ -8 ⬙ [508.
All field wiring must comply with NEC (U.S.A.) and lo- cal requirements. Install field wiring as follows: 1. Install conduit through side panel openings. 2. Install power lines to connections as shown in Fig. 8. W rap connections with electrical tape.
LEGEND NEC — National Electrical Code TXV — Thermostatic Expansion V alve *Accessory item. †Field supplied. NOTES: 1. All piping must follow standard refrigerant piping techniques. Re- fer to Carrier System Design Manual for details. 2. All wiring must comply with the applicable local and national codes.
T able 4 — Electrical Data UNIT 38AQS NOMINAL VOL T AGE (V -Ph-Hz) VOL T AGE RANGE COMPRESSOR OFM POWER SUPPL Y MINIMUM DISCONNECT Min Max RLA LRA FLA MCA MAX FUSE OR HACR BRKR AMPS FLA LRA 008 208/230-3-60 187 254 31.5 160 3.1 42.5 50 45 177 460-3-60 414 508 15.
T able 5A — Accessory Electric Heater Data (60 Hz) UNIT 40RMQ HEA TER P ART NO. V -PH-Hz NOMINAL kW HEA TER AMPS MCA* MOCP* 008 CAELHEA T001A00 240-3-60 5 12.0 25.6 30 CAELHEA T002A00 480-3-60 6.0 12.3 15 CAELHEA T003A00 575-3-60 5.0 1 1.9 15 CAELHEA T004A00 240-3-60 10 24.
2 CORNER POST RACEWA Y THERMOST A T FIELD CONNECTION POWER WIRING CONNECTIONS Fig. 6 — Fusible Plug Locations LEGEND NO TE: The 8 o’clock position is shown abo ve . Fig. 7 — TXV Sensing Bulb Location TXV — Ther mostatic Expansion V al ve LEGEND Fig.
ST ART -UP Preliminary Checks 1. Check that all internal wiring connections are tight and that all barriers, covers, and panels are in place. 2. Field electrical power source must agree with unit name- plate rating. 3. Ensure all service valves are open.
Should room temperature continue to fall, circuit R-W is made through second-stage thermostat bulb. If optional elec- tric heat package is used, a relay is energized, bringing on supplemental electric heat. When thermostat is satisfied, con- tacts open, deenergizing contactor and relay; motors and heat- ers deenergize.
5. Remove crankcase heater from compressor base. 6. Remove compressor holddown bolts and lift compres- sor of f basepan. 7. Remove compressor from unit. 8. Clean system. Add new liquid line filter drier (biflow type). 9. Install new compressor and position in unit.
Fig. 16 — Cooling Mode Operation Fig. 17 — Heating Mode Operation 13.
TROUBLESHOOTING CHART , COOLING CYCLE LEGEND TXV — Thermostatic Expansion V alve 14.
TROUBLESHOOTING CHART , HEA TING CYCLE LEGEND N.C. — Normally Closed 15.
.
.
Manufacturer reserves the right to discon tinue, or change at any time, specifications or designs without notice and wit hout inc urring obligation s. PC 111 Catalog No.
ST ART -UP CHECKLIST A. Preliminary Information OUTDOOR: MODEL NO. SERIAL NO. INDOOR: AIR HANDLER MANUF ACTURER MODEL NO. SERIAL NO. ADDITIONAL ACCESSORIES B. Pre-Start-Up OUTDOOR UNIT IS THERE ANY SHIPPING DAMAGE? (Y/N) IF SO, WHERE: WILL THIS DAMAGE PREVENT UNIT ST AR T -UP? (Y/N) CHECK POWER SUPPL Y .
Manufacturer reserves the right to discon tinue, or change at any time, specifications or designs without notice and wit hout inc urring obligation s. PC 111 C atalog No.
デバイスCarrier 38AQS008の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 38AQS008をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 38AQS008の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 38AQS008の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 38AQS008で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 38AQS008を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 38AQS008の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 38AQS008に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 38AQS008デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。