Carrierメーカー38HDL018-060の使用説明書/サービス説明書
ページ先へ移動 of 12
Installation, Start-Up and Service Instructions CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INST ALLA TION ..............................1 - 7 Step 1 — Complete Pre-Installation Checks ....................................1 • UNP ACK UNIT • INSPECT SHIPMENT • CONSIDER SYSTEM REQUIREMENTS Step 2 — Rig and Mount Unit .
UNIT SIZE 38HDL ABC D E F G H J K L M OPERA TING WEIGHT ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm lb kg 018 2-1 1 ⁄ 8 638.2 3-0 15 ⁄ 16 938.2 1-2 9 ⁄ 16 369.9 1-4 406.
Step 2 — Rig and Mount Unit MOUNTING ON GROUND — Mount unit on a solid, level concrete pad. Position unit so water or ice from roof does not fall directly into unit.
with a wet cloth, the tubing set can be brazed to the service valve using either silver bearing or non-silver bearing braz- ing material. Consult local code requirements. Refrigerant tubing and indoor coil are ready for leak testing. NOTE: Unit is shipped with R-22 full factory charge indi- cated on nameplate.
T able 1A — Physical Data (English) UNIT 38HDL 018 024 030 036 048 060 NOMINAL CAP ACITY (Btuh) 18,000 24,000 30,000 36,000 48,000 60,000 UNIT OPERA TING WEIGHT (lb) 130 136 161 185 222 249 COMPRESS.
LEGEND C— Contactor (12-va) HC — Heating Control IFM — Indoor-Fan Motor IFR — Indoor-Fan Relay TRANS — T ransformer Field Wiring Factory Wiring *The IFR and IFM are located in indoor unit on heating-cooling applications. If accessory IFR is required for cooling-only applic- tions, locate (IFR) in fan coil.
T able 2 — American/European W ire Conversions AMERICAN EUROPEAN Industry Standard Size American Conversion (mm) Industry Standard Size (mm 2 ) 18 A WG 0.82 1.0 16 A WG 1.30 1.5 14 A WG 2.08 2.5 12 A WG 3.30 4.0 10 A WG 5.25 6.0 8A W G 6.36 10.0 6A W G 13.
T able 3 — Electrical Data UNIT SIZE 38HDL V -PH-Hz OPERA TIONAL VOL T AGE* COMPRESSOR POWER SUPPL Y Min Max RLA LRA Fan FLA MCA Max Fuse† or HACR-T ype Ckt Bkr Amps 018 208/230-1-60 187 254 10.7 47.0 .70 14.1 25 024 13.2 59.0 .70 17.2 30 030 15.7 73.
SUBCOOLING METHOD (COOLING, TXV) — T o check and adjust charge during cooling season, use T ables 6A and 6B and the following procedure: 1. Operate unit a minimum of 15 minutes before checking charge. 2. Measure liquid line temperature near liquid line service valve, and measure liquid pressure at liquid line service valve.
MAINTENANCE Before performing recommended maintenance, be sure unit main power is of f. Failure to do so may result in electrical shock or injury from rotating fan blades. Lubrication F AN-MOTOR BEARINGS — Oiling holes are provided at each end of the condenser-fan motor .
TROUBLESHOOTING TROUBLESHOOTING CHART — COOLING CYCLE 11.
Copyright 1998 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 Ta b 3 a 2 a PC 1 1 1 Catalog No. 563-899 Printed in U.S.A.
デバイスCarrier 38HDL018-060の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Carrier 38HDL018-060をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCarrier 38HDL018-060の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Carrier 38HDL018-060の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Carrier 38HDL018-060で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Carrier 38HDL018-060を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCarrier 38HDL018-060の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Carrier 38HDL018-060に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCarrier 38HDL018-060デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。