Compurメーカー4120の使用説明書/サービス説明書
ページ先へ移動 of 34
Operation Manual Compur Statox 4120.
Compur Statox 4120 This document is subject to changes without notice. Regular updates can be viewed on our web site www.compur.com You are welcome to communicate any proposal how to improve this document to Compur Monitors. Copyright Compur Monitors GmbH & Co.
Compur Statox 4120 Contents Seite 1. Important notice 4 2. The Statox 4120 System: Pur pose of use and description 4 2.1 Statox 4120 sensor head 5 2.2 Statox 4120 rack 6 2.3 Statox 4120 control module 8 2.4 Diagnostic box 9 3. Installation and electrical connections 10 3.
Compur Statox 4120 1. Important notice Statox 4120 is an explosion proof system for the detection of toxic gases. It can be operated in hazardous areas classified division 1 and 2. Before installing and putting Statox into operation read and observe this manual! To operate the system safely, observe this m anual carefully.
Compur Statox 4120 2.1 Statox 4120 sensor head pic. 1: Statox 4120 sensor head 1 Bottom part 2 Statox 4120 sensor 3 Statox 4120 dust filter 4 Gas generator 5 Statox 4120 pump 6 Statox 4120 filter cart.
Compur Statox 4120 pic. 2: Statox 4120 sensor head for Cl 2 und ClO 2 Operation principle Ambient air enters the sensor (2) by diffusion th rough an opening at the bottom. The sensor creates a current - signal proportional to the gas concentra tion. This signal is amplified, temperature compensated and linearised.
Compur Statox 4120 Construction: The system consists of a 19“-4-HE rack with backplane and up to nine Statox 4120 control modules. Each Statox 4120 sensor head is communicating wi th one control module.
Compur Statox 4120 2.3 Statox 4120 control module Each Statox 4120 Control module has its own power supply. The intrinsically safe sensor head supply circuit is supplied by a separate secondary winding.
Compur Statox 4120 LED A1 (9) - On if pre - alarm threshold is exceeded Display A2 (10) - On if main alarm threshold is exceeded Button A1 (4) - Press and hold button A1 to display A1 thres hold. Adjust with Pot. (12). A1 must be < A2. Button A2 (3) - Press and hold button A2 to display A2 threshold.
Compur Statox 4120 3. Installation and electrical connections 3.1. Statox 4120 sensor head 3.1.1. Mounting The sensor head should be installed as close as possibl e to potential leaks. If it is used as industrial hygiene device it should be located between a potent ial leak and personnel working in the area.
Compur Statox 4120 pic.7: Drilling plan for the mounting brackets 3.1.2. Connecting the signal cable The signal cable connects sensor head and control module.
Compur Statox 4120 Example of cable specifications: Max. cable capacity: l x C L = C o - C i = 107 nF Max. cable inductivity: l x L L = L o - L i = 6,6 mH Diameter: > 0,75 mm 2 The Statox 4120 Systems will work reliably if the electrical resistance is : R L < 50 Ω .
Compur Statox 4120 3.2 Statox 4120 rack Statox 4120 Rack must not be installed in hazardous areas. Observe local safety- and installation regulations. Protect any cable from tensile strain. The five - and the nine - contact terminals are plugged in. They can be removed to ease wire connection.
Compur Statox 4120 Installation instructions for the RFI-shielded Statox 4120 rack: Use well shielded signal cable. The shield must make good contact with the RFI resistant cable glands. It must not be interrupted by connection box es. If the signal cable is run through such, these must also be equipped with RFI resistant cable glands.
Compur Statox 4120 Slide sw itch S1: S1 ON OFF 1 Relay active during alarm A2 Relay inactive at alarm A2 2 Relay active during alarm A1 Relay inactive at alarm A1 Toggle sw itch S3: S3 ON OFF 1 Detect.
Compur Statox 4120 DIP switch S1 (see pic. 8) programs gas and meas uring range. If you change your Statox to another gas or measuring range, a hardware modification may be required and the electronics must be re - adjusted. This must be done by authorised personnel.
Compur Statox 4120 Table 4: Sw itch position for Cl 2 Measuring range: 0-1,5 ppm 0-3 ppm 0-10 ppm S1/1 ON ON OFF S1/2 ON ON ON S1/3 ON ON ON S1/4 ON OFF ON S1/5 ON ON OFF S1/6 ON ON ON S1/7 OFF OFF OF.
Compur Statox 4120 Table 8: Sw itch position for SO 2 Table 9: Sw itch position for NO 2 Measuring range: 0-0,5 ppm Measuring range: 0-15 ppm S1/1 OFF S1/1 ON S1/2 ON S1/2 ON S1/3 ON S1/3 ON S1/4 OFF .
Compur Statox 4120 4.5 Manually triggered self test of the sy stem Push and hold button T for 2 s to initiate a self test. The next self test will start automatically after 24 h. 4.6 System failure As soon as the Statox detects a faulty system condition the LED SF goes on and relay SF is activated.
Compur Statox 4120 5.1 Using the diagnostic box Switch the diagnostic box on. Then connect it to t he opto- coupler receptacle on sensor head bottom. Keep the LED`s and the phototransistors of the opto- coupler clean for proper data transmission. 5.1.
Compur Statox 4120 5.1.2 Status messages of the sensor head Button ST scans the system status: Code Status and action required Passed System OK. Error A1 Amplifier defective: Repeat adj ustment or replace pcb. Error B1 Check battery pack connection.
Compur Statox 4120 6. Maintenance and calibration 6.1 Inspection Statox 4120 Sensor head The following maintenance intervals are general re commendations.
Compur Statox 4120 Filter cartridge replacement Remove tube Remove filter cartridge and bearing Clean air access opening Replace filter cartridge and bearing Replace tube Generator.
Compur Statox 4120 Procedure: Remove splash guard and replace it by test gas adapter. Connect span gas cylinder. Do not open regulator yet! Connect diagnostic box to sensor head. Reading diagnostic box: Red LED fl ashing; - “ready” – “x.
Compur Statox 4120 7. The maintenace request option Purpose: This option can differentiate between fatal errors in the sensor head and maintenance requirements. It requires a Statox 4120 control module equipped with EPROM Index ≥ 03. It also sets the analog output to 4 mA during the self test, if required.
Compur Statox 4120 Error C3 (Too low sensitivity during self test): S3/3 on the control module offers the option to c hoose if C3 shall be a maintenance request (position ON) or system failure (position OFF).
Compur Statox 4120 pic.12: Electrical connections and short circuit contacts Short circuit contacts on the maintenance request pcb: Bridge Analog 0-1V Analog 4-20 mA Analog 4(0)-20mA* 1 ● 2 ● ● 3 ● 4 ● ● 5 ● 6 ● ● 7 ● * Analog output 0 mA, if PCS-relay active, f.
Compur Statox 4120 8. The option analog output inhibition This option inhibits the analog output if the logic signal of the control module (see pic. 3, terminal 11) is set to 5 V instead of 0 V.
Compur Statox 4120 9. The option zero adjustment This option is available for COCl 2 sensor heads with measuring range 0.3 ppm only. The zero adjustment of the sensor is started via diagnostic box. System requirements: Sensor head EPROM index 18c, control module EPR OM index 03a, diagnostic box EPROM index 02.
Compur Statox 4120 10. Technical data General: Gas Measuring range Cl 2 0-1.5 ppm, 0-3 ppm, 0-10 ppm CO 0-150 ppm COCl 2 0-0.1 ppm, 0-0.3 ppm, 0-0.5 ppm, 0-1.5 ppm, 0-15 ppm, 0-100 ppm HCN 0-15 ppm, 0-30 ppm, 0-50 ppm, 0-100 ppm HCl 0-100 ppm H 2 S 0-30 ppm, 0-50 ppm, 0-100 ppm ClO 2 0-0.
Compur Statox 4120 Control module: Type: 5331 0x0 (115 / 230 VAC) Operating temperature: -20 to +40 o C Storage temperature: -30 to +60 o C Explosion protection : [EEx ib] IIC Operating environment: II 2 G power: 15 W per control module Supply voltage: 115 / 230 VAC Max.
Compur Statox 4120 11. Accessories and spare parts Art. Nr. STATOX 4120 ACCESSORIES 508885 STATOX Diagnostic box 518876 STATOX Diagnostic box charger 115 V 518850 STATOX Diagnostic box charger 230 V 5.
Compur Statox 4120 558435 STATOX Manual -E- 518330 STATOX Sensor head battery 506947 STATOX Sensor head bearing 236 mm 557874 STATOX Sensor head EPROM "12" 562197 STATOX Sensor head EPROM &q.
Compur Statox 4120 Specifications are subject to c hange without notice, and ar e provided only for comparison of products. The conditions under which our products are used, are beyond our contro l.
デバイスCompur 4120の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Compur 4120をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはCompur 4120の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Compur 4120の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Compur 4120で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Compur 4120を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はCompur 4120の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Compur 4120に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちCompur 4120デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。