HEAL TH C ARE CO MMUNI C AT I O N S Y S TE M for Nursin g Homes & Health Care Facilitie s N HX S Y S TE M 838 7 3900 0602 E – 1 – I N S T ALLA TI O N MAN U A L c.
– 2 – CONTENTS Precautions on Installation & Wiring .................................................... 3 1 System Outline & Components ................................................... 4 - 7 • System Outline .........................
– 3 – PRECAUTIONS ON INST ALLA TION & WIRING PRECAUTIONS ON INST ALLA TION & WIRING W ARNIN G 1. Do not connect a power supply other than Aiphone Model P S -24E or P S -2420 to terminals +, – on NHX-80X. Doing so can cause fire or damage to the unit .
– 4 – 1 The NHX is a Health Care Communication System, exclusively designed for patient to staff communications in health care facilities. The NHX system is UL Listed under UL1069 the Standard for Hospital Signalling & Nurse Call Equipment. At Nurses Center , the NHX-50M master station is an extremely compact, low profile console.
– 5 – Sub T runk line 1 PS24 PS24 PS24 PS24 PS24 Sub station NHR-3TS 6(3P) To the farthest sub, max.165' (50m) with min. 22AWG wire. Sub trunk line must not exceed 330' (100m) in total with 22AWG wire.
– 6 – COMPONENTS A V AILABLE • Central Control Unit • Urgent bathroom call sub station (common area) • Bedside sub stations • Master station & Add-on selector • Duty station • Central Control Unit NHX-80X: Central Control Unit(CCU) w/50 or 80 station capacity .
– 7 – Accessories: Aiphone Models & UL Listed locally available • Zone light 4-zone indicator light. Max. 4 units. (NHR-3A-4) Up to 2 units powered by a PS-24E or PS-2420 power supply . • Urgent call switch Provides dry closure contact, with mechanically latching switch.
– 8 – 2 2 NAMES & FEA TURES NHX-50M Desk use only NHX-50M 1 1. Handset 1 2. Speaker 1 3. Directory 1 4. Sub call-in LED 1 5. Sub selector button 1 6. Power on LED 1 7. Mic. 1 8. OFF button 1 9. T ALK button 10. TONE-OFF button 1 1. Attendance LED 12.
– 9 – NHX-30G NHX-30G 1. Directory 2. Sub call-in LED 3. Sub selector button NH-1SA/A 2-gang mounting 1. Speaker/mic. 2. CANCEL button (for routine call only) 3.
– 10 – NHX-80X 1. Power on LED, green 2. Front cover screw (2) 3. Power switch 3-gang mounting 1 2 3 340 98 460 (18- ") / 1 8 (13- ") / 3 8 (3- ") / 7 8 2. NAMES & FEA TURES 1. 24V DC output terminals 2. T erminal for grounding 3.
– 11 – NHR-3TS NHR-4A 2-gang mounting Single-gang mounting Single-gang mounting 1. Lamp cover (2) Red lamps inside 1. Lamp cover White & red lamps inside NHR-SP NHR-7A 2-gang mounting 5-gang mounting 1. Speaker 2. TONE-OFF button 3.
– 12 – System Features 1. Listed UL1069 Patient to Staff Communication System for up to 80 stations. 2. V oice-actuated handset or press-to-talk communication. Single and private channel (cannot be broken into). 3. Up to 8 trunk lines for subs.
– 13 – Mounting location NHX equipment is designed for indoor use only . NHX-80X must be wall-mounted on a UL Listed 3-gang box or in a Listed electrical enclosure. The enclosure should be provided with a solid noncombustible mounting plate board for securing the NHX-80X chassis.
S ub's Block & N u m ber Block # Subs # B at h roo m P u ll cor d Y es or No C orridor lam p Y es or No U r g en t C all S w . Y es or No Zon e # Assigne d – 14 – 3 . IN S T ALLA TI O N & WIRIN G Settin g Station #1 ~ 10 on Sub station s Be f ore installin g sub stations : 1.
– 15 – Initializing NHX-80X for Sub stations The NHX-80X CCU must be set to zero after all the sub station numbers are programmed. Proceed as follows; 1. Remove the switch cover on front cover . Place the dip switch SW2-2(SET) to upper ON position.
– 16 – • NHX-80X 1. Subs trunk lines 1 1 ~ 16: for Block 1 21 ~ 26: for Block 2 31 ~ 36: for Block 3 41 ~ 46: for Block 4 51 ~ 56: for Block 5 61 ~ 66: for Block 6 71 ~ 76: for Block 7 81 ~ 86: for Block 8 1, 2: V oice 3: + 24V 4: GND 5: DA T A + 6: DA T A – 2.
– 17 – 1 ~ 6: Connect 3P cable to Subs Trunk line. T en stations per trunk, connected to NHX-80X 1 1 - 16 (up to 81 - 86) terminals. ZL: Zone light to a Zone No.
To: NHX-50M To: NHR-SP Cable 5P 6 parallel conductors Distance 65' w/22AWG 65' w/22AWG (20m w/0.65mmø) (20m w/0.65mmø) – 18 – * When Duty station (NHR-SP) is installed, remove the shorting connector from CN104 socket . Line-off trouble will be activated at the y( ) g y( ) NHX- 50 M when wires to NHR- S P are broken .
T o: Z one li g ht Cable 5 parallel conductors Distance 165' w/18AWG ( 50m w / 1.0mmø ) – 19 – S chematic dia g ram of Zone li g ht NHR-3A- 4 WIRIN G DIA G RAM S 2. Zone l ig ht s * Take G terminal to earth ground on eac h P S-24E or PS-2420 power suppl y.
– 20 – T runk line from NHX-80X to sub stations should be Aiphone specified cable or UL Listed cable (3 twisted pair). • If 4-zone lamp is included, use 4 twisted pairs. • In a zone with more than 10 stations, additional subs must be wired in a separate trunk line, but the ZL line may be extended from any sub on the previous trunk line.
– 21 – 5. Bathroom call sub station: NHR-3TS WIRING DIAGRAMS 4. Bedside sub stations w/Corridor lamp & Bathroom Pullcord Take G terminal to earth ground on 2 PS-24E or PS-2420 power supplies.
– 22 – WIRING DIAGRAMS Multi-Station Patient Room Applications 1. Four bed application covered by four NH-1SA/A sub stations with a common bathroom pullcord Multiple NH-1SA/A and NH-2SA/A bedside sub stations can also be installed within a patient room.
– 23 – WIRING DIAGRAMS Multi-Station Patient Room Applications 2. Max. 12 bed application covered by six NH-2SA/A sub stations with or without a common bathroom pullcord (*1) Terminal Z1 for lighting Lamp 1 in NHR-3A-4. (*2) NHR-7A may be wired to any sub station convenient.
– 24 – 4 4 MOUNTING The NHX-80X should be mounted on either 3-gang box or on inside UL Listed electrical enclosure. T o open the front cover; 1. On the NHX-80X, pull at bottom of the cover and lift cover off the chassis. 2. Unplug CN-1~CN-5 connectors to disconnect from chassis.
– 25 – 4. MOUNTING Mounting NHX-50M master station As shown, NHX-50M can be wired to NHX-80X CCU, using terminal cord supplied. At NHX-50M end, plug in 10-pin connector . Assembling two Consoles: NHX-50M & NHX-30G On the bottom of the NHX-50M, cut off the socket part and plug 2 connectors from the NHX-30G into the socket.
– 26 – NHR- 3 T S S ub statio n 4. M OU NTIN G 2- g an g semi-flush mountin g (NH-1SA, NH-2SA, NHR-SP , NHR-3TS ) The sub station flush-mounts in 2- g an g box (UL Listed). C over clicks to attach . As shown terminate connector wires to the T runk line with wire nuts, and plug into the socket .
– 27 – 4. MOUNTING NHR-4A 1. Remove the lamp cover, pressing on both sides. 2. Terminate 3 wires from NH-1SA/A or NH-2SA/A bedside sub. 3. Mount NHR-4A on 1-gang box with 2 screws supplied. 4. Reattach the lamp cover. NHR-7A 1. Terminate 3 wires from NH-1SA/A or NH-2SA/A.
– 28 – • Receiving a Routine Call (Bedside) At NHX-50M 5 5 OPERA TIONS on NHX-50M Speaker Handset Power on LED Mic Directory Sub call-in LED Sub Selector button OFF button TALK button TONE-OFF button Attendance LED At NHX-50M At site When a Bedside sub station presses CALL button; 1.
– 29 – 5. OPERA TIONS on NHX-50M • V olume Adjustments Speaker receive voice volume & call tone signal are adjustable as needed on the left side of NHX-50M.
– 30 – T ype of calling Call tone Ligh t A t NHX-50M Master stat i o n • Receiving Routine call S ingle chime, every 6 sec. Blinking, every 2 sec . Bathroom call (ur g ent) S in g le chime, every 2 sec. Double blinkin g , every 1.8 sec . C ord-out trouble call S in g le chime, every 0.
– 31 – 6. TECHNICAL PRECAUTIONS RESET switch Do not use RESET switch except for initializing or testing the NHX-80X. If RESET is pressed while a call is being placed or a Bathroom call or Cord-out trouble call has been placed, it will suspend the call.
– 32 – O ther Operation s ( 1) On a corridor lamp, the white lamp steadily lit (durin g routine call ) ma y var y if another bathroom call o r cor d -out trou bl e ca ll h as b een p l ace d i n t h e sam e tr u n k. ( 2 ) A p ullcord call in a bathroom illuminates the maste r ca ll i n di cator l am p on t h e p ane l.
デバイスAiphone 83873900 0602 Eの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Aiphone 83873900 0602 Eをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはAiphone 83873900 0602 Eの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Aiphone 83873900 0602 Eの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Aiphone 83873900 0602 Eで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Aiphone 83873900 0602 Eを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はAiphone 83873900 0602 Eの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Aiphone 83873900 0602 Eに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちAiphone 83873900 0602 Eデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。