Revised 1-8-2007 Delta Cooling Towers, Inc. TM Series Cooling Tower Installation, Operation & Maintenance Manual.
Revised 1-8-2007 1 Table of Contents Delta Cooling Towers Principle of Cooling Towers………………..……………. 2 Cooling Tower Terms and Definitions…………………… 2 Water Treatment……..………………………….………..
Revised 1-8-2007 2 Delta Cooling Towers Principle of Cooling Towers All Cooling Towers operate on the principle of removing heat from water by evaporating a sm all portion of the water that is recirculated through the unit. The heat that is removed is called the latent heat of vaporization.
Revised 1-8-2007 3 Water Treatment • The Delta Cooling Towers are manufactured from corrosion-resistant plastics which are resistant to water treatment chemicals including com mon fungicides and bactericides. • Follow appropriate water treatment practices as require d and take frequent sample tests to avoid possible water contamination.
Revised 1-8-2007 4 Approximate Weights The TM Series cooling towers are manufactured in three basic sections; a polyethylene tower body, a polyethylene sump, and a fan assembly section. The tower body ships with the fan assem blies installed. The tower sump ships as a separate piece.
Revised 1-8-2007 5 Handling and Installation of Your TM Series Cooling Tower On -Site Inspection Upon arrival at the job site, carefully inspect the shipment for any damage. If shipping dam age has occurred, notify the driver or the carrier immediately and m ake a notation of the damage on the shipping bill of lading.
Revised 1-8-2007 6 Store tower assembly as shipped until the time of installation, in a secure, level and debris free location at the job site. CAUTION : For extended lifts, use duplicate rigging, fabric slings around body as shown, as an additional safety precaution.
Revised 1-8-2007 7 • The body section should then be lifted and carefully position to align the support post of the sump with the corresponding groove of the tower body. Note that the four corner posts are slightly higher than other post to ease installation alignment.
Revised 1-8-2007 8 • On multi cell towers, install PVC water redirector panels between each sump using self-tapping screws provided (See sketch below). Start with screwing the PVC post from the bottom up. Next apply a heavy bead of RTV sealant on the end of each redirector panel.
Revised 1-8-2007 9 Electrical Wiring of Fan Motor and Accessories • Installation of a vibration cut-out switch is recommended. (Refer to tower accessories available). • All electrical work should be performed only by qualified personnel and in accordance to prevailing electrical codes, practices and safety standards.
Revised 1-8-2007 10 PVC Solvent Cementing Instructions The following procedure is recommended for the preparation and cem enting of internal and external piping for Delta Cooling Towers: • Cut ends of pipe square using a handsaw and miter box.
Revised 1-8-2007 11 Operation and Maintenance of Your TM Series Cooling Tower Safety in Operation of the Fan NEVER operate the fan when the access panel or the entire fan guard is removed. NEVER remove access manhole cover while fan is in operation. NEVER operate fan when any work, access, maintenance, trouble-shooting, etc.
Revised 1-8-2007 12 • The maximum operating inlet water temperature should not exceed 140° F. CAUTION: When stepping on top of the fill, distribute th e body weight by means of two plywood plates as described earlier in these instructions.
Revised 1-8-2007 13 • Check spray pattern from nozzles to be sure there is no clogging. Remove drift elim inators for nozzle inspection, then return to proper position. • Start up fan motor and check amperage and voltage against m otor nameplate data.
Revised 1-8-2007 14 Cold Weather Operation Cold Weather Protection The cooling tower may require protection against freezing at light heat loads when the wet-bulb temperature is under 32°F.
15 PVC Distribution System To prevent damage to the PVC distribution system during cold weather shut-down, install an automatic or manual drain line from the hot water inlet piping as close to the cooling tower inlet as possible. The entire inlet and distribution system must be drained for shut-down in sub- freezing weather.
16 Trouble-Shooting Guide For TM Series Induced Draft Cooling Towers Problem Possible Causes Corrective Actions Increase in the leaving water temperature 1. Excess water flow; over pumping. 2. Recirculation of hot discharge air, back into the cooling tower air intakes.
17 Problem Possible Causes Corrective Actions 2. Airlock. 3. Unnecessary obstruction of waterflow (i.e., partially closed valve). 4. Undersized piping. 5. Horizontal pipe run too long. 6. Improper hydraulic pipe design. 7. Outlet vortex breaker provided.
18 Motor Trouble Shooting Guide (General) Problem Possible Causes Corrective Actions High current draw (all 3 phases) 1. Low line voltage (5 to 10% lower than nameplate). 2. 200V motor on 230/240V system. 3. 230V motor on 208V system. 4. Incorrect propeller.
19 TM Series Optional Accessories TM Series Optional Accessories Available Aluminum Ladder(s) with a step platform and railing at the fan elevation custom designed for the cooling tower. Safety cage(s). Two speed motor(s) designed for cooling tower duty to the exclusive specifications of Delta Cooling Towers.
20 Preventative Maintenance Checklist Procedure Monthly Every 3 Months Every 6 months Inspect General Condition of cooling tower. ¨ Check Water Level in cold water basin. Adjust if needed. ¨ Check float ball & Make-up Valve for proper operation.
デバイスDelta TM-105312の購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Delta TM-105312をまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはDelta TM-105312の技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Delta TM-105312の取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Delta TM-105312で得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Delta TM-105312を既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はDelta TM-105312の不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Delta TM-105312に関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちDelta TM-105312デバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。