www.rosemount.com ¢00825-0100-4801J¤ HART ® Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S Rosemount 3051S Series Pressure T ransmitter with HART ® Protocol Rosemount 3051SF Series Flowmeter T ransmitter with HART ® Protocol © 2008 Rosemount Inc.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 2 Rosemount Inc. 8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001 Emerson Proces s Management GmbH & Co.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 3 W ARNING Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 4 S TEP 1: M OUNT THE T RANSMITTER Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 5 S TEP 1 CONTINUED ... Panel Mount Pipe Mount Coplanar ™ Flange T raditional Flange In-line Housings PlantWeb ™ Junction Box Remote Mount Display 4801_QIG_RevHA.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 6 S TEP 2: C ONSIDER H OUSING R OT ATION S TEP 3: S ET S WITCHES AND J UMPERS If alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off .
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 7 S TEP 4: C ONNECT W IRING AND P OWER U P Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erminals.” 2. Connect the positive lead to the “+” terminal, and the negative lead to the “–” terminal.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 8 S TEP 4 CONTINUED ... Remote Display Wiring and Power Up The Remote Mount Display and Interf ace system consists of a local transmitter and a remote mount LCD display assembly .
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 9 S TEP 4 CONTINUED ... Intrinsic Safety Consideration: The transmitter assembly with remote display has been approved with Belden 3084A DeviceNet cable.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 10 S TEP 4 CONTINUED ... NOTE Wire colors provided on page 9 are per Belden 3084A DeviceNet cable. Wire color may vary depending on cable selected. Belden 3084A DeviceNet cable includes a ground shield.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 11 S TEP 4 CONTINUED ... 2. Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb. (34 N-m). 3. T ighten the set screw using a 3 / 32 -in hex wrench.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 12 S TEP 4 CONTINUED ... Power Supply The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller , indicator , and related pieces.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 13 S TEP 5: V ERIFY C ONFIGURATION Use any HART -compliant master to communicate with and verify configuration of the 3051S. For the HART Diagnostics transmitter (option code DA1), DD revision 3051S HDT Dev .
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 14 S TEP 5 CONTINUED ... Function Fast Key Sequence Saturation Level Configura tion 1, 4, 2, 7, 8 Scaled D/A T rim (4–2.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 15 S TEP 6: T RIM THE T RANSMITTER T ransmitters are shipped fully calibrat ed per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit).
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 16 Using the T ransmitter Zero Adjustment Button Push and hold the zero adjustment button for at least two seconds but no longer than ten seconds. Figure 8. T ransmi tter Adjustme nt Buttons PlantWeb Junction Box Span Zero Span Zero 4801_QIG_RevHA.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 17 S AFETY I NSTRUMENTED S YSTEMS Additional Safety Instrumented System s information is available in the Rosemount 3051S reference manual (document number 00809-0100-4801).
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 18 Inst allation No special installation is required in addition to the st andard installation practices outlined in this document. Always ensure a proper seal by installing the electr onics housing covers so that metal co ntacts metal .
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 19 NOTES 1. T ransmitter output is not safety-rated during the following: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during transmitter configuration and maintenance activities.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 20 Setting the alarm values and directi on is dependent on whether or not the hardware switch option is insta lled. Y ou can use a HAR T master or communicator to set the Alarm and Saturation values.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 21 Operation and Maintenance Proof T est and Inspection The following proof tests are recommended. Proof test result s and corrective actions taken must be documented at www .
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 22 Proof T est 2 This proof test, when combined with the Proof T est 1, will detect over 92% of DU failures not detected by the 3051S_C or 3051S_L automatic diagnostics, and over 95% of DU failures not detected by the 3051S_T automatic diagnostics.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 23 Reference Certification The 3051S Safety-Certified Pressure T ransmitter was designed, developed, and audited to be complia nt to IEC 61508 safety-certified SIL 2 Claim Limit.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 24 P RODUCT C ERTIFICATIONS Approved Manufacturing Locations Rosemount Inc.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 25 Hazardous Locations Certifications North American Certifications FM Approvals E5 Explosion proof for Class I, Division.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 26 European Certifications I1 A TEX Intrinsic Safety Certificate No.: BAS01A TEX1303X II 1 G EEx ia IIC T4 (T a = -60 °C to 70 °C) -HART/Remote Display/Quick Connect/HAR T Diagnostics 1 180 Special Conditions for Safe Use (X) 1.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 27 Special Conditions for Safe Use (x) The apparatus is not capable of withst anding the 500V insulation test required by Clause 9.1 of EN 50021: 1999. This must be taken into account when installing the app aratus.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 28 E1 A TEX Flame-Proof Certificate No.: KEMA00A TEX2143X II 1/2 G EEx d IIC T6 (-50 °C ≤ T amb ≤ 65 °C) EEx d IIC T5 (-50 °C ≤ T amb ≤ 80 °C) V max = 42.4V 1 180 Special conditions for safe use (x) This device contains a thin wall diaphragm.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 29 Australian Certifications E7 SAA Explosion-Proof and Dust Ignition-Proof Certification No.: AUS Ex 3798X Ex d IIC T6 (T a = 60°C) IP66 DIP A21 T A T6 (T a = 60°C) IP66 Conditions for safe use (X) 1.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 30 I7 IECEx Intrinsic Safety Certificate No.: IECExBAS04.0017X Ex ia IIC T4 (T a = -60 °C to 70 °C) -HART/Remote Display/Quick Connect/HAR T Diagnostics IP66 Conditions for safe use (X) 1.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 31 Combinations of Certifications S tainless steel certification t ag is pr ovided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinst al led using any other approval types.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 32 4801_QIG_RevHA.fm Page 32 Wednes day, Februa ry 20, 2008 9:16 AM.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 33 4801_QIG_RevHA.fm Page 33 Wednes day, Februa ry 20, 2008 9:16 AM.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 34 4801_QIG_RevHA.fm Page 34 Wednes day, Februa ry 20, 2008 9:16 AM.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 35 4801_QIG_RevHA.fm Page 35 Wednes day, Februa ry 20, 2008 9:16 AM.
Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 36 NOTES 4801_QIG_RevHA.fm Page 36 Tuesday, Februar y 26, 2008 12:17 PM.
デバイスEmerson 3051Sの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson 3051Sをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson 3051Sの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson 3051Sの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson 3051Sで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson 3051Sを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson 3051Sの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson 3051Sに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson 3051Sデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。