Micro Motion ® T -Series Sensor Inst allation Manual Inst allation Manual P/N 20002172, Rev . B July 2008.
©2008, Micro Motion, Inc. All right s reserved. ELITE and ProLink are registered tr ademarks, and MVD and MVD Direct Connect are trademarks of Micro Motion, Inc., Boulder , Colorado. Micro Motion is a registered tra de name of Micro Motion, Inc., Boul der , Colorado.
1 Before Y ou Begin Before Y ou Begin This manual describes ho w to install a Micro Motion ® T -Series sensor . The followi ng informat ion is provided in this manual: Customer service For technical assistance, phone the Micr o Motion Customer Service depa rtment: • In the U.
2 Before Y ou Begin Definitions The term MVD ™ transmitt er refers to the follo wing transmitter models: • Models 1500, 170 0, 2500, an d 2700 • Models 3500 and 3700 with sensor interf ace code .
3 Before Y ou Begin Figure 1 T -Series sensor with core processor Figure 2 T -Series sensor with integrally mounted Model 1700/2700 transmitter Approv al tag Flow direction arrow Core processor housin.
4 Determining a Location Figure 3 T -Series sensor with junction box Step 1 Determining a Location Choose a location for the sensor based on the requirements described in th is section. The foll o wing general guidelines can help you select an appropriate locatio n for the sensor .
5 Determining a Locati on Figure 4 T -Series sensor ambient an d process temperat ure limits Hazardous area approv als may impose additional limits on ambient and process temperature. For the A TEX “T” rating, refer to the A TEX documentation shipped w ith the sensor or av ailable on the Micro Motion web site at www .
6 Determining a Location Maximum wiring distances If the transmitter is mounted remote ly from the sensor , the maximum di stance between the sensor and transmitter depends on cable type. See T able 2. Pipe run Micro Motion sensors d o not require a straight run of pipe upstream or downstream.
7 Orienting the Sensor Step 2 Orienting the Sensor The sensor will function proper ly in an y orientation if the sensor tube s remain f illed with process fluid. Micro Motion recommends orienting the sensor in a v ertical pipeline, with process flu id flo w ing upwa rd through the sensor (see Figure 5).
8 Orientin g the Se nsor Figure 6 Eccentric redu cer • The gap between the ele ctronics housing and se nsor body shou ld be inspected period ically . Man ually clean this gap when necessary . • The ASME Bioprocess Equipment Standard (ASME BPE-19 97), section SC-3.
9 Mounti ng the Sensor Step 3 Mounting the Sensor Use your commo n practices to minimize to rque and bendi ng load on process connections. T o reduce the risk of condensation or excessiv e moisture , the conduit opening should not point upward (if possible).
10 Wiring Step 4 Wiring Hazardous area installations If you are installing the sensor in a hazardous location, verify that the hazardous classif ication information printed on the sensor tag matches the en vironm ent in which the sensor will be installed.
11 Wiring Figure 8 Micro Motion cable g land and he at shrink 4. For conn ection at the core processor housing, pr epare shielded cable as follo ws (for armored cable, omit steps d, e, f, and g): a.
12 Wiring Figure 10 Applying the heat shrink g. Position gland clamping inse rt so the interior end is flush with the heat shrink. h. Fold the cl oth shield or braid and drain wires o ve r the clamping insert and approximately 1/8 inch (3 mm) past the O-ring.
13 Wiring Figure 13 Connecting the wires at th e core processor 7. Reinstall and tighten the co re processor housing co ver . 8. Additional wiring instructions for the tran smitter can be found in the transmitter manual. Note: Never gr ound the 4-wire cable shield an d shield dr ain wir e(s) at the transmitter .
14 Grounding Step 5 Grounding The sensor can be grounde d via the piping if the joints in the pipeline are ground- bonded. If the sen sor is not grounded via the piping, connect a groun d wire to the in ternal or exter nal grounding scre w , which is located on the core processo r housing or junction box.
15 Purge Fittings 4. Connect the supp ly of nitrogen or ar gon g as to the inlet pur ge connection or open inlet pur ge line. Leav e the outlet connec tion open. • Exercise caution to a voi d introducing dirt, moisture, rust, or other contaminants into the sensor case.
16 Return Policy Return Policy Micro Motion procedu res must be followed when retu rning equipment. These procedures ensure le gal compliance with go vernment transpor tation agencies and help pro vide a safe working en vironment for Micro Motion employees.
.
Micro Motion Inc. USA Worldwide Headqu arters 7070 Winchester Circle Boulder , Colorado 80301 T +1 303-527-5200 +1 800-522-6277 F +1 303-530-8459 Micro Motion Europe Emerson Process Management Neonstr.
デバイスEmerson Process Management T-SERIESの購入後に(又は購入する前であっても)重要なポイントは、説明書をよく読むことです。その単純な理由はいくつかあります:
Emerson Process Management T-SERIESをまだ購入していないなら、この製品の基本情報を理解する良い機会です。まずは上にある説明書の最初のページをご覧ください。そこにはEmerson Process Management T-SERIESの技術情報の概要が記載されているはずです。デバイスがあなたのニーズを満たすかどうかは、ここで確認しましょう。Emerson Process Management T-SERIESの取扱説明書の次のページをよく読むことにより、製品の全機能やその取り扱いに関する情報を知ることができます。Emerson Process Management T-SERIESで得られた情報は、きっとあなたの購入の決断を手助けしてくれることでしょう。
Emerson Process Management T-SERIESを既にお持ちだが、まだ読んでいない場合は、上記の理由によりそれを行うべきです。そうすることにより機能を適切に使用しているか、又はEmerson Process Management T-SERIESの不適切な取り扱いによりその寿命を短くする危険を犯していないかどうかを知ることができます。
ですが、ユーザガイドが果たす重要な役割の一つは、Emerson Process Management T-SERIESに関する問題の解決を支援することです。そこにはほとんどの場合、トラブルシューティング、すなわちEmerson Process Management T-SERIESデバイスで最もよく起こりうる故障・不良とそれらの対処法についてのアドバイスを見つけることができるはずです。たとえ問題を解決できなかった場合でも、説明書にはカスタマー・サービスセンター又は最寄りのサービスセンターへの問い合わせ先等、次の対処法についての指示があるはずです。